International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962
Volume-12, Issue-1, (February 2022)
www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6
41 This work is licensed under Creative Commons Attribution 4.0 International License.
Assessment of the Static Stability Margin and Voltage Profile
Improvement in the SOUTH- SNEL Power Network using a SVC under
MATLAB / PSAT Environment
Daniel MBURASEK1
, Idriss KYONI2
and Odon MUSIMBI3
1
Research Assistant, Department of Electrical Engineering, University Nouveaux Horizons, DR. CONGO
2
Assistant Professor, Department of Electromechanical Engineering, University of Lubumbashi, DR. CONGO
3
Assistant Professor, Department of Mechanical Engineering Technology, Metropolitan State University of Denver, USA
1
Corresponding Author: danielmburasek@gmail.com
ABSTRACT
The huge increase in the demand of electric power
and the economic constraints to build new facilities, lead the
power systems to operate near of their stability limits. Indeed,
instability has become a major problem in the management
of power systems. Unavoidable disturbances such as short
circuits, momentary unavailability of transmission lines,
generators as well as transformers can affect the stability of
the power system at any time and bring it into a state of
instability or collapse. These collapses become a major
problem for energy consumers, because the lack of energy
leads them to use backup energy sources that are relatively
expensive and polluting. This situation lowers the
productivity of the industry, and for the national electric
company of the Congo, (SNEL), the time to get rid of the
magnetization of the network and to take all the loads, can
generate penalties, which is a loss of revenue for the
company. This paper aims to assess the stability margin and
to improve the quality of electrical energy in the south-SNEL
transmission system.
Keywords-- Stability Margin, Sensitivity Factor, Voltage
Stability, SNEL, Voltage Collapse, SVC, PSAT
I. INTRODUCTION
The huge increase in the demand of electric
power and the economic constraints to build new facilities,
lead the power systems to operate near of their stability
limits [1]. Indeed, instability has become a major problem
in the management of power systems. Unavoidable
disturbances such as short circuits, momentary
unavailability of transmission lines, generators as well as
transformers can affect the stability of the power system at
any time and bring it into a state of instability or collapse.
The stability of a power system is therefore the ability of
the system to remain in an equilibrium state, for normal
operating conditions, and to return to a stable equilibrium
state after a disturbance [2].
The Flexible AC Transmission System (FACTS)
can therefore only offer both benefits of increased stability
margin and improved power quality by placing it at
strategic locations in the power system.
The work of optimal location of different types of
FACTS devices in the power system has attempted to use
different techniques such as genetic algorithm (GA),
hybrid Tabu approach and simulated annealing. The best
location for a phase change set was found by genetic
algorithm to reduce the flow in heavily loaded lines
resulting in increased load capacity of the power network
while reducing losses [3].
The modeling of FACTS devices for power flow
studies and the integration of these devices into power
flow studies has been reported in [4, 5].
In this paper, we used the Matlab/PSAT toolbox
to evaluate the stability margin of the South-SNEL
transmission system which consists of 21 nodes. The
procedure is to model the loads as voltage dependent, then
gradually load the power network with a constant
parameter until it collapses. This stability margin is a key
indicator of the static stability of a power system, however
its evaluation remains complex and depends on several
parameters. Next we have evaluated the voltage sensitivity
factor by calculating the voltage deviation at each node of
the power network. The nodes which present a strong
variation will be considered as the strategic place where
the SVC will be placed in order to improve the voltage
profile.
II. PRESENTATION OF SOUTH- SNEL
POWER NETWORK
The South-SNEL power system includes four
hydroelectric power plants represented at the NSEKE,
NZILO, MWADINGUSHA and KONI nodes with an
exploitable power of 468 MW [6], A static compensator of
12.4 MVA is connected to KARAVIA node, a High
Voltage Direct Current (HVDC) injection at KOLWEZI
SCK node with three synchronous power compensators of
70 MVA. We have considered the NSEKE node as a
balancing node, because it has the most powerful generator
International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962
Volume-12, Issue-1, (February 2022)
www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6
42 This work is licensed under Creative Commons Attribution 4.0 International License.
KASSAPA
120 kV
KASSAPA
220 kV
RS 220 kV
RS 120 kV
RC 120 kV
RO 120 kV
TENKE
NZILO
SHILATEMBO
KASUMBALESA
MICHELO
KARAVIA
PANDA
RC 220 kV
FGUME
120 kV
FGUME
220 kV
SCK
NSEKE
220 kV
NSEKE
120 kV
MWADINGUSHA
KONI
SLACK
BUS
INJECTION
INGA
(HVDC)
in the network, i.e. 69 MVA, and this power is considered
as base power. The generators are considered with the
limitation on the reactive power. The simplified diagram of
the TRS SNEL South network is given in the Figure 1
below:
Figure 1: South-SNEL transmission network
III. LOADS
Loads of power systems are divided into
industrial, commercial, residential and agriculture [7]. The
load is modeled by the PQ model, i.e. it does not depend
on the voltage and is defined by the equations (1) and (2)
below, with a constant power factor:
(1)
(2)
with λ denoting the load factor; initial active power at
node ; initial reactive power at node
IV. GENERATORS
It is the essential component of power systems
[8]. The power generated by the generators is defined by
the following equation:
(3)
with the power generated by machine in the initial
case; ; the contribution factor of each generator to
satisfy the load demand, the value usually used is 1.
V. TRANSMISSION LINES
The transmission line given in Figure 2 is
modeled by an equivalent diagram in . It is composed of
a series impedance (resistance in series with an inductive
reactance ), and a shunt admittance which consists of a
capacitive susceptance (due to the capacitive effect of
the line with the earth) in parallel with an insulating
conductance
International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962
Volume-12, Issue-1, (February 2022)
www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6
43 This work is licensed under Creative Commons Attribution 4.0 International License.
R j X
i j
2
jB
G 
2
jB
G 
Figure 2: Transmission line
Legend: resistance of the line, inductive reactance of
the line, susceptance of the line, conductance of the
line.
VI. POWER FLOW EQUATION
Considering that the powers are balanced at
node , the power balance for a power network of nodes
gives:
(4)
Gi
Ypij
Ysij
SDi
jeu de barre i
vers jeu de barres j
SGi
vers autres jeux de
barres
Figure 3: Bus with generation, load and transmission line
Where: is the generated power and is the requested
power
VII. POWER FLOW IN A
TRANSMISSION LINE
The power flow in transmission lines allows us to
locate overloaded lines and to evaluate the power losses.
The power lost in a transmission line connecting nodes
and is given by:
(5)
(6)
with and respectively the active and reactive losses
when the power flows from node to node ; and
respectively the active and reactive losses when the
power flows from node to node .
VIII. VOLTAGE STABILITY
The multiplication of interconnected power
systems has led to several research works on angular
stability which have contributed to the attenuation of
angular oscillations [9]. However, disturbances cause
voltage drops without altering the synchronization of the
generators, this phenomenon is known as voltage collapse.
It is mainly caused by:
 Generation too far away from consumption,
 Local lack of reactive energy [9].
 Loads called too large
Variations in active power and reactive power are
the key parameters that lead the network to voltage
collapse or Jacobian matrix singularity.
(7)
where represents the state vector of the power flow
problem that encompasses the vectors of voltages and
phase shifts ; the variable represents a scalar parameter
or the load factor used to simulate the load increase that
leads to system collapse.
The increases in consumed active power ,
consumed reactive power , and generated power at
node , can be expressed as a function of the initial active
power , the initial reactive power , the initial
generated power and the lambda load parameter λ
expressed by the following system of equations:
(8)
IX. LOAD MARGIN
The load margin is the most commonly used
index in the evaluation of static voltage stability: it is the
amount of additional load that would cause a voltage
collapse. In simpler terms, it is the distance between the
current operating point and the point that would cause
voltage collapse. In most static voltage stability studies,
the load is chosen as the critical parameter that drives the
system to collapse.
International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962
Volume-12, Issue-1, (February 2022)
www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6
44 This work is licensed under Creative Commons Attribution 4.0 International License.
0 0.5 1 1.5
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
Lambda (p.u.)
Tension
(pu)
VBus1 TENKE 120 kV
VBus2 RS 120kV
VBus8 LIKASI / RC 120 kV
X. OPTIMAL LOCATION OF THE SVC
The optimal location of the SVC is realized at the
critical node. This node is identified using the voltage
sensitivity factor ( ) given by:
(9)
with voltage sensitivity factor of node ; tangent
at node k around the voltage collapse point; number of
nodes.
XI. RESULTS AND DISCUSSION
From Figure 3, it can be noticed that as the power
demand increases, the voltages progressively decrease
until reaching the critical value at the collapse point which
corresponds to the maximum load factor 1.5385
which is equivalent to a power of 106.2 MW. At this
point, almost all generators reach their reactive power
limits. We can also notice that the voltage variation of
these three curves is different, which explains why the
three nodes give different responses in terms of voltage
instability.
Beyond this point, the voltages drop abruptly and
uncontrollably; this is the voltage collapse phenomenon.
This phenomenon can be explained as follows: when the
load increases, the current flowing in the line also
increases, resulting in a voltage drop that is all the greater
as the current is greater, and therefore the voltage across
the load decreases. The stability margin of our power
network is estimated to 37.2 MW.
Figure 4: Voltage collapse curve
Figure 4, represents the voltage profile for the
nominal load. We can notice that the LIKASI RC and RS
120 kV nodes have lower voltages compared to the others.
This voltage degradation at the RS node is due to the long
distance between generation and consumption on the one
hand, and by the high power demand on the other hand. On
the other hand, the RC node is close to the generation
centers compared to other load nodes, but has a high
voltage drop. This high voltage drop can be reflected in the
reactive energy transfer sensitivity, which is even higher if
the short-circuit power is low, i.e. 928.5 MVA for RC.
International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962
Volume-12, Issue-1, (February 2022)
www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6
45 This work is licensed under Creative Commons Attribution 4.0 International License.
Figure 5: Voltage profile
From Figure 5, it is important to note that the
reactive energy transfers always go in the direction of
decreasing voltages, while the active energy transfers are
in the direction of decreasing relative angles, where we can
observe a significant transfer of active power at the RS 120
kV node that results in a relatively large decrease in the
voltage angle, or -58.6°,
Figure 6: Angles profile
Table 1 shows the results of the power
distribution, i.e., the electrical state of the network for the
constraints imposed on the , and balance nodes. For
each bus, the first column represents the nominal voltages
( ), and the second column represents the phase shifts of
the voltages with respect to the balance node. The other
columns represent the active and reactive powers
generated by the different production machines and those
consumed by the loads connected to the network nodes.
Thus we can directly observe that the powers delivered by
the generators are far greater than those assigned to them,
so the generators are operating in overload. The machines
are therefore unable to cover all the loads of the network
simultaneously, hence the selective load shedding is used
to ensure the balance between production and
consumption,
International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962
Volume-12, Issue-1, (February 2022)
www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6
46 This work is licensed under Creative Commons Attribution 4.0 International License.
Bus V phase P gen Q gen P load Q load
[p.u.] [rad] [p.u.] [p.u.] [p.u.] [p.u.]
Bus1 RO 220kV 1,048 -0,377 0,000 0,000 0,000 0,000
Bus1 TENKE 120 kV 0,952 -0,540 0,000 0,000 0,000 0,000
Bus10 NSEKE 220 kV 1,045 -0,450 0,000 0,000 0,000 0,000
Bus11 KLZ SCK 220kV 1,045 -0,463 2,174 5,955 0,145 0,130
Bus12 FUNGURUME 220 kV 0,985 -0,618 0,000 0,000 2,304 1,116
Bus13 KARAVIA 220 kV 1,000 -0,840 0,014 6,486 2,391 1,158
Bus13 KASUMBALESA 220 kV 0,995 -0,847 0,000 0,000 0,391 0,158
Bus13 LIKASI / PANDA 220 kV 0,981 -0,703 0,000 0,000 0,000 0,000
Bus2 NSEKE 120 kV 1,060 0,000 12,428 1,580 0,000 0,000
Bus2 RS 120 kV 0,888 -1,023 0,000 0,000 3,651 1,768
Bus3 FUNGURUME 120 kV 0,955 -0,635 0,000 0,000 0,000 0,000
Bus3 RS 220kV 0,995 -0,844 0,000 0,000 0,000 0,000
Bus4 KASAPA 220kV 0,986 -0,858 0,000 0,000 0,000 0,000
Bus4 NZILO 120 kV 1,045 -0,183 1,174 1,760 0,000 0,000
Bus5 KASAPA 120kV 0,972 -0,881 0,000 0,000 0,000 0,000
Bus5 KLZ / RO 120 kV 1,002 -0,265 0,000 0,000 3,493 1,692
Bus6 LIKASI / SHITURU 220 kV 0,981 -0,703 0,000 0,000 0,000 0,000
Bus6 MICHELO 0,996 -0,846 0,000 0,000 0,391 0,158
Bus7 MWADINGUSHA 120 kV 1,045 -0,952 0,493 1,686 0,000 0,000
Bus7 SHILATEMBO 120 kV 0,933 -0,974 0,000 0,000 0,000 0,000
Bus8 LIKASI / RC 120 kV 0,882 -0,920 0,000 0,000 1,826 0,884
Bus9 KONI 120 kV 1,045 -0,950 0,203 -0,095 0,000 0,000
Figure 6 gives the sensitivity factors at the
different nodes of the network. We can notice a high
voltage sensitivity at the LIKASI RC node, i.e. 0.273. This
means that this node experiences a large voltage drop as
the load increases. It is therefore considered as the weak or
critical node of our
network. Therefore, installing a SVC in this node will give
the best voltage stability margin compared to other load
nodes. Nodes with very low or zero VSF, such as
KARAVIA and RS 220 kV nodes, are insensitive to load
variations,
Figure 7: Voltage sensitivity factor
International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962
Volume-12, Issue-1, (February 2022)
www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6
47 This work is licensed under Creative Commons Attribution 4.0 International License.
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
Lambda (p.u.)
Tension
(pu)
VBus8 LIKASI / RC 120 kV
Figure 7 shows the voltage profiles, with and
without SVC, the installation of SVC at the RC node,
remarkably improves the voltage profile at the different
load nodes except at the RS 120 kV node, which
undergoes a slight improvement but is still unacceptable,
as it is less than 0. . This node can be considered as a
critical node for another case with SVC,
Figure 8: Voltage profile
Legend: series 1, without SVC; series 2, with SVC.
Figure 8 illustrates the influence of SVC on the
static voltage stability. We can see that installing SVC at
the RC node increases the voltage stability margin up to
1.7423 with the initial case of 1.5385 . Thus, we
benefit from an increase in the static voltage stability
margin of 0.2038 or 14.1 MW. We can also notice that
the SVC maintains the voltage at the RC node around the
reference value = 1.0019 , via an appropriate
susceptance regulation. The bifurcation curve (PV) appears
flat because of the sufficient reactive energy support
Figure 9: Voltage collapse curve to RC node
International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962
Volume-12, Issue-1, (February 2022)
www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6
48 This work is licensed under Creative Commons Attribution 4.0 International License.
To better visualize the optimality of our site
selection, as well as the effectiveness of the voltage
sensitivity factor, the SVC is installed in different nodes of
the network and a comparative study is conducted with the
critical node (LIKASI RC) given in the following Table 2 :
Table 1: Comparison of the stability margin at different nodes
Nœud TENKE RS
FUNGURUME
120 kV
PANDA
Lambda (pu) 1.6523 1.6548 1.6697 1.5844
XII. CONCLUSION
The problem of choosing the location of the SVC
was discussed, and the LIKASI RC node was selected as
the most favorable location for the implementation of the
SVC. The voltage deviation to the nodes or VSF is the key
parameter that allowed us to orient our choice towards the
LIKASI RC. The presence of this SVC in the power
network allowed us to both increase the stability margin
and improve the voltage profile in all nodes except the RS
node which can be considered as a weak node for another
SVC placement. A comparative study was performed by
placing the SVC in other nodes of the network, the
response given by the LIKASI RC node remains
satisfactory.
Further work may focus on a comparison of
performance between this method and those of SVC
placement by swarm particles multi-objective.
REFERENCES
[1] A. LAIFA. (1995). Evaluation de la stabilité de tension
d’un réseau d’énergie électrique développement et
application des indices de stabilité, thèse de Magister,
Ecole Nationale polytechnique.
[2] M. CRAPP. (2003). Stabilité et sauvegarde des réseaux
électriques, LAVOISIER, Ed. France: Bermes science
publication.
[3] Talpasai Lakkaraju. (2006). Selection of pilot buses for
VAR support and voltage stability risk analysis, Master of
science thesis, Lane Department of Computer Science and
Electrical Engineering Morgantown, West Virginia, USA.
[4] Stéphane GERBEX. (2003). Metaheuristique appliquée
au placement optimal de dispositifs FACTS dans un réseau
électrique, thèse PhD, Ecole polytechnique de Lausanne,
Lausanne.
[5] E. G. Shahraki. (2003). Apport de l’UPFC à
l’amélioration de la stabilité transitoire des réseaux
électriques, thèse de Doctorat, Université Henri Poincaré,
Nancy-I.
[6] Idriss KYONI et al. (2019). Stratégies d’amélioration
de la sécurité d’approvisionnement électrique de la
province de Katange RD/Congo, Available at
https://hal.archives-ouvertes.fr/hal-02074381/document.
[7] DEBAPRIYA DAS. (2006). Electrical power systems.
New Delhi, India: New Age International (P).
[8] Hadi SAADAT. (1999). Power system analysis. New
York: The McGraw-Hill Companies.
[9] G. K. Morison et al. (1993). Voltage stability analysis
using static and dynamic approaches. IEEE Trans. on
Power Systems, 8(3), 1159-1171.

More Related Content

What's hot

when a coil is rotated or turned under a magnetic field, there occurs a force...
when a coil is rotated or turned under a magnetic field, there occurs a force...when a coil is rotated or turned under a magnetic field, there occurs a force...
when a coil is rotated or turned under a magnetic field, there occurs a force...theijes
 
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...IAEME Publication
 
NON-ISOLATED SOFT SWITCHING DC-DC CONVERTER AND LOAD AT FULL RANGE OF ZVS
NON-ISOLATED SOFT SWITCHING DC-DC CONVERTER AND LOAD AT FULL RANGE OF ZVS NON-ISOLATED SOFT SWITCHING DC-DC CONVERTER AND LOAD AT FULL RANGE OF ZVS
NON-ISOLATED SOFT SWITCHING DC-DC CONVERTER AND LOAD AT FULL RANGE OF ZVS IAEME Publication
 
6.[36 45]seven level modified cascaded inverter for induction motor drive app...
6.[36 45]seven level modified cascaded inverter for induction motor drive app...6.[36 45]seven level modified cascaded inverter for induction motor drive app...
6.[36 45]seven level modified cascaded inverter for induction motor drive app...Alexander Decker
 
Single Phase Matrix Converter for Input Power Factor Improvement
Single Phase Matrix Converter for Input Power Factor ImprovementSingle Phase Matrix Converter for Input Power Factor Improvement
Single Phase Matrix Converter for Input Power Factor Improvementiosrjce
 
Grid connected pv system using 9 level flying capacitor multilevel inverter
Grid connected pv system using 9 level flying capacitor multilevel inverterGrid connected pv system using 9 level flying capacitor multilevel inverter
Grid connected pv system using 9 level flying capacitor multilevel inverterIAEME Publication
 
Application of single phase matrix converter topology to an uninterruptible p...
Application of single phase matrix converter topology to an uninterruptible p...Application of single phase matrix converter topology to an uninterruptible p...
Application of single phase matrix converter topology to an uninterruptible p...eSAT Publishing House
 
Bd32773778
Bd32773778Bd32773778
Bd32773778IJMER
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultselelijjournal
 
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...IJSRD
 
Base paper
Base paperBase paper
Base paperRAGHRAGH
 
Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...YogeshIJTSRD
 
POWER SYSTEM STABILITY OF MULTI MACHINE BY USING STATIC SYNCHRONOUS SERIES CO...
POWER SYSTEM STABILITY OF MULTI MACHINE BY USING STATIC SYNCHRONOUS SERIES CO...POWER SYSTEM STABILITY OF MULTI MACHINE BY USING STATIC SYNCHRONOUS SERIES CO...
POWER SYSTEM STABILITY OF MULTI MACHINE BY USING STATIC SYNCHRONOUS SERIES CO...ijiert bestjournal
 
IRJET- Generalized UPQC System with an Improved Control Method under Distorte...
IRJET- Generalized UPQC System with an Improved Control Method under Distorte...IRJET- Generalized UPQC System with an Improved Control Method under Distorte...
IRJET- Generalized UPQC System with an Improved Control Method under Distorte...IRJET Journal
 

What's hot (19)

At4101261265
At4101261265At4101261265
At4101261265
 
when a coil is rotated or turned under a magnetic field, there occurs a force...
when a coil is rotated or turned under a magnetic field, there occurs a force...when a coil is rotated or turned under a magnetic field, there occurs a force...
when a coil is rotated or turned under a magnetic field, there occurs a force...
 
main-project1
main-project1main-project1
main-project1
 
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
 
NON-ISOLATED SOFT SWITCHING DC-DC CONVERTER AND LOAD AT FULL RANGE OF ZVS
NON-ISOLATED SOFT SWITCHING DC-DC CONVERTER AND LOAD AT FULL RANGE OF ZVS NON-ISOLATED SOFT SWITCHING DC-DC CONVERTER AND LOAD AT FULL RANGE OF ZVS
NON-ISOLATED SOFT SWITCHING DC-DC CONVERTER AND LOAD AT FULL RANGE OF ZVS
 
6.[36 45]seven level modified cascaded inverter for induction motor drive app...
6.[36 45]seven level modified cascaded inverter for induction motor drive app...6.[36 45]seven level modified cascaded inverter for induction motor drive app...
6.[36 45]seven level modified cascaded inverter for induction motor drive app...
 
Single Phase Matrix Converter for Input Power Factor Improvement
Single Phase Matrix Converter for Input Power Factor ImprovementSingle Phase Matrix Converter for Input Power Factor Improvement
Single Phase Matrix Converter for Input Power Factor Improvement
 
Grid connected pv system using 9 level flying capacitor multilevel inverter
Grid connected pv system using 9 level flying capacitor multilevel inverterGrid connected pv system using 9 level flying capacitor multilevel inverter
Grid connected pv system using 9 level flying capacitor multilevel inverter
 
Application of single phase matrix converter topology to an uninterruptible p...
Application of single phase matrix converter topology to an uninterruptible p...Application of single phase matrix converter topology to an uninterruptible p...
Application of single phase matrix converter topology to an uninterruptible p...
 
Bd32773778
Bd32773778Bd32773778
Bd32773778
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
 
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
 
Base paper
Base paperBase paper
Base paper
 
Non isolated coupled converter tied voltage source inverter drive
Non isolated coupled converter tied voltage source inverter driveNon isolated coupled converter tied voltage source inverter drive
Non isolated coupled converter tied voltage source inverter drive
 
Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
 
POWER SYSTEM STABILITY OF MULTI MACHINE BY USING STATIC SYNCHRONOUS SERIES CO...
POWER SYSTEM STABILITY OF MULTI MACHINE BY USING STATIC SYNCHRONOUS SERIES CO...POWER SYSTEM STABILITY OF MULTI MACHINE BY USING STATIC SYNCHRONOUS SERIES CO...
POWER SYSTEM STABILITY OF MULTI MACHINE BY USING STATIC SYNCHRONOUS SERIES CO...
 
IRJET- Generalized UPQC System with an Improved Control Method under Distorte...
IRJET- Generalized UPQC System with an Improved Control Method under Distorte...IRJET- Generalized UPQC System with an Improved Control Method under Distorte...
IRJET- Generalized UPQC System with an Improved Control Method under Distorte...
 
A1103030111
A1103030111A1103030111
A1103030111
 
Dw25743750
Dw25743750Dw25743750
Dw25743750
 

Similar to Assessment of the Static Stability Margin and Voltage Profile Improvement in the SOUTH- SNEL Power Network using a SVC under MATLAB / PSAT Environment

Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...IJMTST Journal
 
POWER QUALITY IMPROVEMENT IN A PV DISTRIBUTION SYSTEM BY USING D-STATCOM
POWER QUALITY IMPROVEMENT IN A PV DISTRIBUTION SYSTEM BY USING D-STATCOMPOWER QUALITY IMPROVEMENT IN A PV DISTRIBUTION SYSTEM BY USING D-STATCOM
POWER QUALITY IMPROVEMENT IN A PV DISTRIBUTION SYSTEM BY USING D-STATCOMpechetti surya venkata subrahmanyam
 
Performance Analysis of CSI Based PV system During LL and TPG faults
Performance Analysis of CSI Based PV system During LL and TPG faultsPerformance Analysis of CSI Based PV system During LL and TPG faults
Performance Analysis of CSI Based PV system During LL and TPG faultsIOSR Journals
 
IRJET- Assessment of Voltage Stability in a Power System Network and its Impr...
IRJET- Assessment of Voltage Stability in a Power System Network and its Impr...IRJET- Assessment of Voltage Stability in a Power System Network and its Impr...
IRJET- Assessment of Voltage Stability in a Power System Network and its Impr...IRJET Journal
 
IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...
IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...
IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...IRJET Journal
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)ijceronline
 
IRJET- Novel Control Operation of PV-STATCOM as Reactive Power Compensator an...
IRJET- Novel Control Operation of PV-STATCOM as Reactive Power Compensator an...IRJET- Novel Control Operation of PV-STATCOM as Reactive Power Compensator an...
IRJET- Novel Control Operation of PV-STATCOM as Reactive Power Compensator an...IRJET Journal
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET Journal
 
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic Controller
IRJET-  	  Power Quality Improvement in Solar by using Fuzzy Logic ControllerIRJET-  	  Power Quality Improvement in Solar by using Fuzzy Logic Controller
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic ControllerIRJET Journal
 
Reactive Power Compensation and Power Factor Correction by Reactive VAR Compe...
Reactive Power Compensation and Power Factor Correction by Reactive VAR Compe...Reactive Power Compensation and Power Factor Correction by Reactive VAR Compe...
Reactive Power Compensation and Power Factor Correction by Reactive VAR Compe...ijtsrd
 
IRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOM
IRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOMIRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOM
IRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOMIRJET Journal
 
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...IAES-IJPEDS
 
Single core configurations of saturated core fault current limiter performanc...
Single core configurations of saturated core fault current limiter performanc...Single core configurations of saturated core fault current limiter performanc...
Single core configurations of saturated core fault current limiter performanc...IJECEIAES
 
Reparation of Inductive Power in Power System by the use of FACTS devices
Reparation of Inductive Power in Power System by the use of FACTS devicesReparation of Inductive Power in Power System by the use of FACTS devices
Reparation of Inductive Power in Power System by the use of FACTS devicesIJMTST Journal
 
IRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQCIRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQCIRJET Journal
 
Improved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsImproved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsIJMTST Journal
 
Power Flow & Voltage Stability Analysis using MATLAB
Power Flow & Voltage Stability Analysis using MATLAB Power Flow & Voltage Stability Analysis using MATLAB
Power Flow & Voltage Stability Analysis using MATLAB IRJET Journal
 
IRJET-Power Flow & Voltage Stability Analysis using MATLAB
IRJET-Power Flow & Voltage Stability Analysis using MATLAB IRJET-Power Flow & Voltage Stability Analysis using MATLAB
IRJET-Power Flow & Voltage Stability Analysis using MATLAB IRJET Journal
 

Similar to Assessment of the Static Stability Margin and Voltage Profile Improvement in the SOUTH- SNEL Power Network using a SVC under MATLAB / PSAT Environment (20)

Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
 
POWER QUALITY IMPROVEMENT IN A PV DISTRIBUTION SYSTEM BY USING D-STATCOM
POWER QUALITY IMPROVEMENT IN A PV DISTRIBUTION SYSTEM BY USING D-STATCOMPOWER QUALITY IMPROVEMENT IN A PV DISTRIBUTION SYSTEM BY USING D-STATCOM
POWER QUALITY IMPROVEMENT IN A PV DISTRIBUTION SYSTEM BY USING D-STATCOM
 
Performance Analysis of CSI Based PV system During LL and TPG faults
Performance Analysis of CSI Based PV system During LL and TPG faultsPerformance Analysis of CSI Based PV system During LL and TPG faults
Performance Analysis of CSI Based PV system During LL and TPG faults
 
IRJET- Assessment of Voltage Stability in a Power System Network and its Impr...
IRJET- Assessment of Voltage Stability in a Power System Network and its Impr...IRJET- Assessment of Voltage Stability in a Power System Network and its Impr...
IRJET- Assessment of Voltage Stability in a Power System Network and its Impr...
 
IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...
IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...
IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)
 
IRJET- Novel Control Operation of PV-STATCOM as Reactive Power Compensator an...
IRJET- Novel Control Operation of PV-STATCOM as Reactive Power Compensator an...IRJET- Novel Control Operation of PV-STATCOM as Reactive Power Compensator an...
IRJET- Novel Control Operation of PV-STATCOM as Reactive Power Compensator an...
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
 
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic Controller
IRJET-  	  Power Quality Improvement in Solar by using Fuzzy Logic ControllerIRJET-  	  Power Quality Improvement in Solar by using Fuzzy Logic Controller
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic Controller
 
Reactive Power Compensation and Power Factor Correction by Reactive VAR Compe...
Reactive Power Compensation and Power Factor Correction by Reactive VAR Compe...Reactive Power Compensation and Power Factor Correction by Reactive VAR Compe...
Reactive Power Compensation and Power Factor Correction by Reactive VAR Compe...
 
IRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOM
IRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOMIRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOM
IRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOM
 
B010240820
B010240820B010240820
B010240820
 
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
 
Single core configurations of saturated core fault current limiter performanc...
Single core configurations of saturated core fault current limiter performanc...Single core configurations of saturated core fault current limiter performanc...
Single core configurations of saturated core fault current limiter performanc...
 
Reparation of Inductive Power in Power System by the use of FACTS devices
Reparation of Inductive Power in Power System by the use of FACTS devicesReparation of Inductive Power in Power System by the use of FACTS devices
Reparation of Inductive Power in Power System by the use of FACTS devices
 
Stability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faultsStability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faults
 
IRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQCIRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQC
 
Improved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsImproved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading Conditions
 
Power Flow & Voltage Stability Analysis using MATLAB
Power Flow & Voltage Stability Analysis using MATLAB Power Flow & Voltage Stability Analysis using MATLAB
Power Flow & Voltage Stability Analysis using MATLAB
 
IRJET-Power Flow & Voltage Stability Analysis using MATLAB
IRJET-Power Flow & Voltage Stability Analysis using MATLAB IRJET-Power Flow & Voltage Stability Analysis using MATLAB
IRJET-Power Flow & Voltage Stability Analysis using MATLAB
 

More from Dr. Amarjeet Singh

Total Ionization Cross Sections due to Electron Impact of Ammonia from Thresh...
Total Ionization Cross Sections due to Electron Impact of Ammonia from Thresh...Total Ionization Cross Sections due to Electron Impact of Ammonia from Thresh...
Total Ionization Cross Sections due to Electron Impact of Ammonia from Thresh...Dr. Amarjeet Singh
 
A Case Study on Small Town Big Player – Enjay IT Solutions Ltd., Bhilad
A Case Study on Small Town Big Player – Enjay IT Solutions Ltd., BhiladA Case Study on Small Town Big Player – Enjay IT Solutions Ltd., Bhilad
A Case Study on Small Town Big Player – Enjay IT Solutions Ltd., BhiladDr. Amarjeet Singh
 
Effect of Biopesticide from the Stems of Gossypium Arboreum on Pink Bollworm ...
Effect of Biopesticide from the Stems of Gossypium Arboreum on Pink Bollworm ...Effect of Biopesticide from the Stems of Gossypium Arboreum on Pink Bollworm ...
Effect of Biopesticide from the Stems of Gossypium Arboreum on Pink Bollworm ...Dr. Amarjeet Singh
 
Artificial Intelligence Techniques in E-Commerce: The Possibility of Exploiti...
Artificial Intelligence Techniques in E-Commerce: The Possibility of Exploiti...Artificial Intelligence Techniques in E-Commerce: The Possibility of Exploiti...
Artificial Intelligence Techniques in E-Commerce: The Possibility of Exploiti...Dr. Amarjeet Singh
 
Factors Influencing Ownership Pattern and its Impact on Corporate Performance...
Factors Influencing Ownership Pattern and its Impact on Corporate Performance...Factors Influencing Ownership Pattern and its Impact on Corporate Performance...
Factors Influencing Ownership Pattern and its Impact on Corporate Performance...Dr. Amarjeet Singh
 
An Analytical Study on Ratios Influencing Profitability of Selected Indian Au...
An Analytical Study on Ratios Influencing Profitability of Selected Indian Au...An Analytical Study on Ratios Influencing Profitability of Selected Indian Au...
An Analytical Study on Ratios Influencing Profitability of Selected Indian Au...Dr. Amarjeet Singh
 
A Study on Factors Influencing the Financial Performance Analysis Selected Pr...
A Study on Factors Influencing the Financial Performance Analysis Selected Pr...A Study on Factors Influencing the Financial Performance Analysis Selected Pr...
A Study on Factors Influencing the Financial Performance Analysis Selected Pr...Dr. Amarjeet Singh
 
An Empirical Analysis of Financial Performance of Selected Oil Exploration an...
An Empirical Analysis of Financial Performance of Selected Oil Exploration an...An Empirical Analysis of Financial Performance of Selected Oil Exploration an...
An Empirical Analysis of Financial Performance of Selected Oil Exploration an...Dr. Amarjeet Singh
 
A Study on Derivative Market in India
A Study on Derivative Market in IndiaA Study on Derivative Market in India
A Study on Derivative Market in IndiaDr. Amarjeet Singh
 
Theoretical Estimation of CO2 Compression and Transport Costs for an hypothet...
Theoretical Estimation of CO2 Compression and Transport Costs for an hypothet...Theoretical Estimation of CO2 Compression and Transport Costs for an hypothet...
Theoretical Estimation of CO2 Compression and Transport Costs for an hypothet...Dr. Amarjeet Singh
 
Analytical Mechanics of Magnetic Particles Suspended in Magnetorheological Fluid
Analytical Mechanics of Magnetic Particles Suspended in Magnetorheological FluidAnalytical Mechanics of Magnetic Particles Suspended in Magnetorheological Fluid
Analytical Mechanics of Magnetic Particles Suspended in Magnetorheological FluidDr. Amarjeet Singh
 
Techno-Economic Aspects of Solid Food Wastes into Bio-Manure
Techno-Economic Aspects of Solid Food Wastes into Bio-ManureTechno-Economic Aspects of Solid Food Wastes into Bio-Manure
Techno-Economic Aspects of Solid Food Wastes into Bio-ManureDr. Amarjeet Singh
 
Crypto-Currencies: Can Investors Rely on them as Investment Avenue?
Crypto-Currencies: Can Investors Rely on them as Investment Avenue?Crypto-Currencies: Can Investors Rely on them as Investment Avenue?
Crypto-Currencies: Can Investors Rely on them as Investment Avenue?Dr. Amarjeet Singh
 
Awareness of Disaster Risk Reduction (DRR) among Student of the Catanduanes S...
Awareness of Disaster Risk Reduction (DRR) among Student of the Catanduanes S...Awareness of Disaster Risk Reduction (DRR) among Student of the Catanduanes S...
Awareness of Disaster Risk Reduction (DRR) among Student of the Catanduanes S...Dr. Amarjeet Singh
 
Role of Indians in the Battle of 1857
Role of Indians in the Battle of 1857Role of Indians in the Battle of 1857
Role of Indians in the Battle of 1857Dr. Amarjeet Singh
 
Haryana's Honour Killings: A Social and Legal Point of View
Haryana's Honour Killings: A Social and Legal Point of ViewHaryana's Honour Killings: A Social and Legal Point of View
Haryana's Honour Killings: A Social and Legal Point of ViewDr. Amarjeet Singh
 
Optimization of Digital-Based MSME E-Commerce: Challenges and Opportunities i...
Optimization of Digital-Based MSME E-Commerce: Challenges and Opportunities i...Optimization of Digital-Based MSME E-Commerce: Challenges and Opportunities i...
Optimization of Digital-Based MSME E-Commerce: Challenges and Opportunities i...Dr. Amarjeet Singh
 
Modal Space Controller for Hydraulically Driven Six Degree of Freedom Paralle...
Modal Space Controller for Hydraulically Driven Six Degree of Freedom Paralle...Modal Space Controller for Hydraulically Driven Six Degree of Freedom Paralle...
Modal Space Controller for Hydraulically Driven Six Degree of Freedom Paralle...Dr. Amarjeet Singh
 
Capacity Expansion Banes in Indian Steel Industry
Capacity Expansion Banes in Indian Steel IndustryCapacity Expansion Banes in Indian Steel Industry
Capacity Expansion Banes in Indian Steel IndustryDr. Amarjeet Singh
 
Metamorphosing Indian Blockchain Ecosystem
Metamorphosing Indian Blockchain EcosystemMetamorphosing Indian Blockchain Ecosystem
Metamorphosing Indian Blockchain EcosystemDr. Amarjeet Singh
 

More from Dr. Amarjeet Singh (20)

Total Ionization Cross Sections due to Electron Impact of Ammonia from Thresh...
Total Ionization Cross Sections due to Electron Impact of Ammonia from Thresh...Total Ionization Cross Sections due to Electron Impact of Ammonia from Thresh...
Total Ionization Cross Sections due to Electron Impact of Ammonia from Thresh...
 
A Case Study on Small Town Big Player – Enjay IT Solutions Ltd., Bhilad
A Case Study on Small Town Big Player – Enjay IT Solutions Ltd., BhiladA Case Study on Small Town Big Player – Enjay IT Solutions Ltd., Bhilad
A Case Study on Small Town Big Player – Enjay IT Solutions Ltd., Bhilad
 
Effect of Biopesticide from the Stems of Gossypium Arboreum on Pink Bollworm ...
Effect of Biopesticide from the Stems of Gossypium Arboreum on Pink Bollworm ...Effect of Biopesticide from the Stems of Gossypium Arboreum on Pink Bollworm ...
Effect of Biopesticide from the Stems of Gossypium Arboreum on Pink Bollworm ...
 
Artificial Intelligence Techniques in E-Commerce: The Possibility of Exploiti...
Artificial Intelligence Techniques in E-Commerce: The Possibility of Exploiti...Artificial Intelligence Techniques in E-Commerce: The Possibility of Exploiti...
Artificial Intelligence Techniques in E-Commerce: The Possibility of Exploiti...
 
Factors Influencing Ownership Pattern and its Impact on Corporate Performance...
Factors Influencing Ownership Pattern and its Impact on Corporate Performance...Factors Influencing Ownership Pattern and its Impact on Corporate Performance...
Factors Influencing Ownership Pattern and its Impact on Corporate Performance...
 
An Analytical Study on Ratios Influencing Profitability of Selected Indian Au...
An Analytical Study on Ratios Influencing Profitability of Selected Indian Au...An Analytical Study on Ratios Influencing Profitability of Selected Indian Au...
An Analytical Study on Ratios Influencing Profitability of Selected Indian Au...
 
A Study on Factors Influencing the Financial Performance Analysis Selected Pr...
A Study on Factors Influencing the Financial Performance Analysis Selected Pr...A Study on Factors Influencing the Financial Performance Analysis Selected Pr...
A Study on Factors Influencing the Financial Performance Analysis Selected Pr...
 
An Empirical Analysis of Financial Performance of Selected Oil Exploration an...
An Empirical Analysis of Financial Performance of Selected Oil Exploration an...An Empirical Analysis of Financial Performance of Selected Oil Exploration an...
An Empirical Analysis of Financial Performance of Selected Oil Exploration an...
 
A Study on Derivative Market in India
A Study on Derivative Market in IndiaA Study on Derivative Market in India
A Study on Derivative Market in India
 
Theoretical Estimation of CO2 Compression and Transport Costs for an hypothet...
Theoretical Estimation of CO2 Compression and Transport Costs for an hypothet...Theoretical Estimation of CO2 Compression and Transport Costs for an hypothet...
Theoretical Estimation of CO2 Compression and Transport Costs for an hypothet...
 
Analytical Mechanics of Magnetic Particles Suspended in Magnetorheological Fluid
Analytical Mechanics of Magnetic Particles Suspended in Magnetorheological FluidAnalytical Mechanics of Magnetic Particles Suspended in Magnetorheological Fluid
Analytical Mechanics of Magnetic Particles Suspended in Magnetorheological Fluid
 
Techno-Economic Aspects of Solid Food Wastes into Bio-Manure
Techno-Economic Aspects of Solid Food Wastes into Bio-ManureTechno-Economic Aspects of Solid Food Wastes into Bio-Manure
Techno-Economic Aspects of Solid Food Wastes into Bio-Manure
 
Crypto-Currencies: Can Investors Rely on them as Investment Avenue?
Crypto-Currencies: Can Investors Rely on them as Investment Avenue?Crypto-Currencies: Can Investors Rely on them as Investment Avenue?
Crypto-Currencies: Can Investors Rely on them as Investment Avenue?
 
Awareness of Disaster Risk Reduction (DRR) among Student of the Catanduanes S...
Awareness of Disaster Risk Reduction (DRR) among Student of the Catanduanes S...Awareness of Disaster Risk Reduction (DRR) among Student of the Catanduanes S...
Awareness of Disaster Risk Reduction (DRR) among Student of the Catanduanes S...
 
Role of Indians in the Battle of 1857
Role of Indians in the Battle of 1857Role of Indians in the Battle of 1857
Role of Indians in the Battle of 1857
 
Haryana's Honour Killings: A Social and Legal Point of View
Haryana's Honour Killings: A Social and Legal Point of ViewHaryana's Honour Killings: A Social and Legal Point of View
Haryana's Honour Killings: A Social and Legal Point of View
 
Optimization of Digital-Based MSME E-Commerce: Challenges and Opportunities i...
Optimization of Digital-Based MSME E-Commerce: Challenges and Opportunities i...Optimization of Digital-Based MSME E-Commerce: Challenges and Opportunities i...
Optimization of Digital-Based MSME E-Commerce: Challenges and Opportunities i...
 
Modal Space Controller for Hydraulically Driven Six Degree of Freedom Paralle...
Modal Space Controller for Hydraulically Driven Six Degree of Freedom Paralle...Modal Space Controller for Hydraulically Driven Six Degree of Freedom Paralle...
Modal Space Controller for Hydraulically Driven Six Degree of Freedom Paralle...
 
Capacity Expansion Banes in Indian Steel Industry
Capacity Expansion Banes in Indian Steel IndustryCapacity Expansion Banes in Indian Steel Industry
Capacity Expansion Banes in Indian Steel Industry
 
Metamorphosing Indian Blockchain Ecosystem
Metamorphosing Indian Blockchain EcosystemMetamorphosing Indian Blockchain Ecosystem
Metamorphosing Indian Blockchain Ecosystem
 

Recently uploaded

Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 

Recently uploaded (20)

Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 

Assessment of the Static Stability Margin and Voltage Profile Improvement in the SOUTH- SNEL Power Network using a SVC under MATLAB / PSAT Environment

  • 1. International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962 Volume-12, Issue-1, (February 2022) www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6 41 This work is licensed under Creative Commons Attribution 4.0 International License. Assessment of the Static Stability Margin and Voltage Profile Improvement in the SOUTH- SNEL Power Network using a SVC under MATLAB / PSAT Environment Daniel MBURASEK1 , Idriss KYONI2 and Odon MUSIMBI3 1 Research Assistant, Department of Electrical Engineering, University Nouveaux Horizons, DR. CONGO 2 Assistant Professor, Department of Electromechanical Engineering, University of Lubumbashi, DR. CONGO 3 Assistant Professor, Department of Mechanical Engineering Technology, Metropolitan State University of Denver, USA 1 Corresponding Author: danielmburasek@gmail.com ABSTRACT The huge increase in the demand of electric power and the economic constraints to build new facilities, lead the power systems to operate near of their stability limits. Indeed, instability has become a major problem in the management of power systems. Unavoidable disturbances such as short circuits, momentary unavailability of transmission lines, generators as well as transformers can affect the stability of the power system at any time and bring it into a state of instability or collapse. These collapses become a major problem for energy consumers, because the lack of energy leads them to use backup energy sources that are relatively expensive and polluting. This situation lowers the productivity of the industry, and for the national electric company of the Congo, (SNEL), the time to get rid of the magnetization of the network and to take all the loads, can generate penalties, which is a loss of revenue for the company. This paper aims to assess the stability margin and to improve the quality of electrical energy in the south-SNEL transmission system. Keywords-- Stability Margin, Sensitivity Factor, Voltage Stability, SNEL, Voltage Collapse, SVC, PSAT I. INTRODUCTION The huge increase in the demand of electric power and the economic constraints to build new facilities, lead the power systems to operate near of their stability limits [1]. Indeed, instability has become a major problem in the management of power systems. Unavoidable disturbances such as short circuits, momentary unavailability of transmission lines, generators as well as transformers can affect the stability of the power system at any time and bring it into a state of instability or collapse. The stability of a power system is therefore the ability of the system to remain in an equilibrium state, for normal operating conditions, and to return to a stable equilibrium state after a disturbance [2]. The Flexible AC Transmission System (FACTS) can therefore only offer both benefits of increased stability margin and improved power quality by placing it at strategic locations in the power system. The work of optimal location of different types of FACTS devices in the power system has attempted to use different techniques such as genetic algorithm (GA), hybrid Tabu approach and simulated annealing. The best location for a phase change set was found by genetic algorithm to reduce the flow in heavily loaded lines resulting in increased load capacity of the power network while reducing losses [3]. The modeling of FACTS devices for power flow studies and the integration of these devices into power flow studies has been reported in [4, 5]. In this paper, we used the Matlab/PSAT toolbox to evaluate the stability margin of the South-SNEL transmission system which consists of 21 nodes. The procedure is to model the loads as voltage dependent, then gradually load the power network with a constant parameter until it collapses. This stability margin is a key indicator of the static stability of a power system, however its evaluation remains complex and depends on several parameters. Next we have evaluated the voltage sensitivity factor by calculating the voltage deviation at each node of the power network. The nodes which present a strong variation will be considered as the strategic place where the SVC will be placed in order to improve the voltage profile. II. PRESENTATION OF SOUTH- SNEL POWER NETWORK The South-SNEL power system includes four hydroelectric power plants represented at the NSEKE, NZILO, MWADINGUSHA and KONI nodes with an exploitable power of 468 MW [6], A static compensator of 12.4 MVA is connected to KARAVIA node, a High Voltage Direct Current (HVDC) injection at KOLWEZI SCK node with three synchronous power compensators of 70 MVA. We have considered the NSEKE node as a balancing node, because it has the most powerful generator
  • 2. International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962 Volume-12, Issue-1, (February 2022) www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6 42 This work is licensed under Creative Commons Attribution 4.0 International License. KASSAPA 120 kV KASSAPA 220 kV RS 220 kV RS 120 kV RC 120 kV RO 120 kV TENKE NZILO SHILATEMBO KASUMBALESA MICHELO KARAVIA PANDA RC 220 kV FGUME 120 kV FGUME 220 kV SCK NSEKE 220 kV NSEKE 120 kV MWADINGUSHA KONI SLACK BUS INJECTION INGA (HVDC) in the network, i.e. 69 MVA, and this power is considered as base power. The generators are considered with the limitation on the reactive power. The simplified diagram of the TRS SNEL South network is given in the Figure 1 below: Figure 1: South-SNEL transmission network III. LOADS Loads of power systems are divided into industrial, commercial, residential and agriculture [7]. The load is modeled by the PQ model, i.e. it does not depend on the voltage and is defined by the equations (1) and (2) below, with a constant power factor: (1) (2) with λ denoting the load factor; initial active power at node ; initial reactive power at node IV. GENERATORS It is the essential component of power systems [8]. The power generated by the generators is defined by the following equation: (3) with the power generated by machine in the initial case; ; the contribution factor of each generator to satisfy the load demand, the value usually used is 1. V. TRANSMISSION LINES The transmission line given in Figure 2 is modeled by an equivalent diagram in . It is composed of a series impedance (resistance in series with an inductive reactance ), and a shunt admittance which consists of a capacitive susceptance (due to the capacitive effect of the line with the earth) in parallel with an insulating conductance
  • 3. International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962 Volume-12, Issue-1, (February 2022) www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6 43 This work is licensed under Creative Commons Attribution 4.0 International License. R j X i j 2 jB G  2 jB G  Figure 2: Transmission line Legend: resistance of the line, inductive reactance of the line, susceptance of the line, conductance of the line. VI. POWER FLOW EQUATION Considering that the powers are balanced at node , the power balance for a power network of nodes gives: (4) Gi Ypij Ysij SDi jeu de barre i vers jeu de barres j SGi vers autres jeux de barres Figure 3: Bus with generation, load and transmission line Where: is the generated power and is the requested power VII. POWER FLOW IN A TRANSMISSION LINE The power flow in transmission lines allows us to locate overloaded lines and to evaluate the power losses. The power lost in a transmission line connecting nodes and is given by: (5) (6) with and respectively the active and reactive losses when the power flows from node to node ; and respectively the active and reactive losses when the power flows from node to node . VIII. VOLTAGE STABILITY The multiplication of interconnected power systems has led to several research works on angular stability which have contributed to the attenuation of angular oscillations [9]. However, disturbances cause voltage drops without altering the synchronization of the generators, this phenomenon is known as voltage collapse. It is mainly caused by:  Generation too far away from consumption,  Local lack of reactive energy [9].  Loads called too large Variations in active power and reactive power are the key parameters that lead the network to voltage collapse or Jacobian matrix singularity. (7) where represents the state vector of the power flow problem that encompasses the vectors of voltages and phase shifts ; the variable represents a scalar parameter or the load factor used to simulate the load increase that leads to system collapse. The increases in consumed active power , consumed reactive power , and generated power at node , can be expressed as a function of the initial active power , the initial reactive power , the initial generated power and the lambda load parameter λ expressed by the following system of equations: (8) IX. LOAD MARGIN The load margin is the most commonly used index in the evaluation of static voltage stability: it is the amount of additional load that would cause a voltage collapse. In simpler terms, it is the distance between the current operating point and the point that would cause voltage collapse. In most static voltage stability studies, the load is chosen as the critical parameter that drives the system to collapse.
  • 4. International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962 Volume-12, Issue-1, (February 2022) www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6 44 This work is licensed under Creative Commons Attribution 4.0 International License. 0 0.5 1 1.5 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 Lambda (p.u.) Tension (pu) VBus1 TENKE 120 kV VBus2 RS 120kV VBus8 LIKASI / RC 120 kV X. OPTIMAL LOCATION OF THE SVC The optimal location of the SVC is realized at the critical node. This node is identified using the voltage sensitivity factor ( ) given by: (9) with voltage sensitivity factor of node ; tangent at node k around the voltage collapse point; number of nodes. XI. RESULTS AND DISCUSSION From Figure 3, it can be noticed that as the power demand increases, the voltages progressively decrease until reaching the critical value at the collapse point which corresponds to the maximum load factor 1.5385 which is equivalent to a power of 106.2 MW. At this point, almost all generators reach their reactive power limits. We can also notice that the voltage variation of these three curves is different, which explains why the three nodes give different responses in terms of voltage instability. Beyond this point, the voltages drop abruptly and uncontrollably; this is the voltage collapse phenomenon. This phenomenon can be explained as follows: when the load increases, the current flowing in the line also increases, resulting in a voltage drop that is all the greater as the current is greater, and therefore the voltage across the load decreases. The stability margin of our power network is estimated to 37.2 MW. Figure 4: Voltage collapse curve Figure 4, represents the voltage profile for the nominal load. We can notice that the LIKASI RC and RS 120 kV nodes have lower voltages compared to the others. This voltage degradation at the RS node is due to the long distance between generation and consumption on the one hand, and by the high power demand on the other hand. On the other hand, the RC node is close to the generation centers compared to other load nodes, but has a high voltage drop. This high voltage drop can be reflected in the reactive energy transfer sensitivity, which is even higher if the short-circuit power is low, i.e. 928.5 MVA for RC.
  • 5. International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962 Volume-12, Issue-1, (February 2022) www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6 45 This work is licensed under Creative Commons Attribution 4.0 International License. Figure 5: Voltage profile From Figure 5, it is important to note that the reactive energy transfers always go in the direction of decreasing voltages, while the active energy transfers are in the direction of decreasing relative angles, where we can observe a significant transfer of active power at the RS 120 kV node that results in a relatively large decrease in the voltage angle, or -58.6°, Figure 6: Angles profile Table 1 shows the results of the power distribution, i.e., the electrical state of the network for the constraints imposed on the , and balance nodes. For each bus, the first column represents the nominal voltages ( ), and the second column represents the phase shifts of the voltages with respect to the balance node. The other columns represent the active and reactive powers generated by the different production machines and those consumed by the loads connected to the network nodes. Thus we can directly observe that the powers delivered by the generators are far greater than those assigned to them, so the generators are operating in overload. The machines are therefore unable to cover all the loads of the network simultaneously, hence the selective load shedding is used to ensure the balance between production and consumption,
  • 6. International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962 Volume-12, Issue-1, (February 2022) www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6 46 This work is licensed under Creative Commons Attribution 4.0 International License. Bus V phase P gen Q gen P load Q load [p.u.] [rad] [p.u.] [p.u.] [p.u.] [p.u.] Bus1 RO 220kV 1,048 -0,377 0,000 0,000 0,000 0,000 Bus1 TENKE 120 kV 0,952 -0,540 0,000 0,000 0,000 0,000 Bus10 NSEKE 220 kV 1,045 -0,450 0,000 0,000 0,000 0,000 Bus11 KLZ SCK 220kV 1,045 -0,463 2,174 5,955 0,145 0,130 Bus12 FUNGURUME 220 kV 0,985 -0,618 0,000 0,000 2,304 1,116 Bus13 KARAVIA 220 kV 1,000 -0,840 0,014 6,486 2,391 1,158 Bus13 KASUMBALESA 220 kV 0,995 -0,847 0,000 0,000 0,391 0,158 Bus13 LIKASI / PANDA 220 kV 0,981 -0,703 0,000 0,000 0,000 0,000 Bus2 NSEKE 120 kV 1,060 0,000 12,428 1,580 0,000 0,000 Bus2 RS 120 kV 0,888 -1,023 0,000 0,000 3,651 1,768 Bus3 FUNGURUME 120 kV 0,955 -0,635 0,000 0,000 0,000 0,000 Bus3 RS 220kV 0,995 -0,844 0,000 0,000 0,000 0,000 Bus4 KASAPA 220kV 0,986 -0,858 0,000 0,000 0,000 0,000 Bus4 NZILO 120 kV 1,045 -0,183 1,174 1,760 0,000 0,000 Bus5 KASAPA 120kV 0,972 -0,881 0,000 0,000 0,000 0,000 Bus5 KLZ / RO 120 kV 1,002 -0,265 0,000 0,000 3,493 1,692 Bus6 LIKASI / SHITURU 220 kV 0,981 -0,703 0,000 0,000 0,000 0,000 Bus6 MICHELO 0,996 -0,846 0,000 0,000 0,391 0,158 Bus7 MWADINGUSHA 120 kV 1,045 -0,952 0,493 1,686 0,000 0,000 Bus7 SHILATEMBO 120 kV 0,933 -0,974 0,000 0,000 0,000 0,000 Bus8 LIKASI / RC 120 kV 0,882 -0,920 0,000 0,000 1,826 0,884 Bus9 KONI 120 kV 1,045 -0,950 0,203 -0,095 0,000 0,000 Figure 6 gives the sensitivity factors at the different nodes of the network. We can notice a high voltage sensitivity at the LIKASI RC node, i.e. 0.273. This means that this node experiences a large voltage drop as the load increases. It is therefore considered as the weak or critical node of our network. Therefore, installing a SVC in this node will give the best voltage stability margin compared to other load nodes. Nodes with very low or zero VSF, such as KARAVIA and RS 220 kV nodes, are insensitive to load variations, Figure 7: Voltage sensitivity factor
  • 7. International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962 Volume-12, Issue-1, (February 2022) www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6 47 This work is licensed under Creative Commons Attribution 4.0 International License. 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 Lambda (p.u.) Tension (pu) VBus8 LIKASI / RC 120 kV Figure 7 shows the voltage profiles, with and without SVC, the installation of SVC at the RC node, remarkably improves the voltage profile at the different load nodes except at the RS 120 kV node, which undergoes a slight improvement but is still unacceptable, as it is less than 0. . This node can be considered as a critical node for another case with SVC, Figure 8: Voltage profile Legend: series 1, without SVC; series 2, with SVC. Figure 8 illustrates the influence of SVC on the static voltage stability. We can see that installing SVC at the RC node increases the voltage stability margin up to 1.7423 with the initial case of 1.5385 . Thus, we benefit from an increase in the static voltage stability margin of 0.2038 or 14.1 MW. We can also notice that the SVC maintains the voltage at the RC node around the reference value = 1.0019 , via an appropriate susceptance regulation. The bifurcation curve (PV) appears flat because of the sufficient reactive energy support Figure 9: Voltage collapse curve to RC node
  • 8. International Journal of Engineering and Management Research e-ISSN: 2250-0758 | p-ISSN: 2394-6962 Volume-12, Issue-1, (February 2022) www.ijemr.net https://doi.org/10.31033/ijemr.12.1.6 48 This work is licensed under Creative Commons Attribution 4.0 International License. To better visualize the optimality of our site selection, as well as the effectiveness of the voltage sensitivity factor, the SVC is installed in different nodes of the network and a comparative study is conducted with the critical node (LIKASI RC) given in the following Table 2 : Table 1: Comparison of the stability margin at different nodes Nœud TENKE RS FUNGURUME 120 kV PANDA Lambda (pu) 1.6523 1.6548 1.6697 1.5844 XII. CONCLUSION The problem of choosing the location of the SVC was discussed, and the LIKASI RC node was selected as the most favorable location for the implementation of the SVC. The voltage deviation to the nodes or VSF is the key parameter that allowed us to orient our choice towards the LIKASI RC. The presence of this SVC in the power network allowed us to both increase the stability margin and improve the voltage profile in all nodes except the RS node which can be considered as a weak node for another SVC placement. A comparative study was performed by placing the SVC in other nodes of the network, the response given by the LIKASI RC node remains satisfactory. Further work may focus on a comparison of performance between this method and those of SVC placement by swarm particles multi-objective. REFERENCES [1] A. LAIFA. (1995). Evaluation de la stabilité de tension d’un réseau d’énergie électrique développement et application des indices de stabilité, thèse de Magister, Ecole Nationale polytechnique. [2] M. CRAPP. (2003). Stabilité et sauvegarde des réseaux électriques, LAVOISIER, Ed. France: Bermes science publication. [3] Talpasai Lakkaraju. (2006). Selection of pilot buses for VAR support and voltage stability risk analysis, Master of science thesis, Lane Department of Computer Science and Electrical Engineering Morgantown, West Virginia, USA. [4] Stéphane GERBEX. (2003). Metaheuristique appliquée au placement optimal de dispositifs FACTS dans un réseau électrique, thèse PhD, Ecole polytechnique de Lausanne, Lausanne. [5] E. G. Shahraki. (2003). Apport de l’UPFC à l’amélioration de la stabilité transitoire des réseaux électriques, thèse de Doctorat, Université Henri Poincaré, Nancy-I. [6] Idriss KYONI et al. (2019). Stratégies d’amélioration de la sécurité d’approvisionnement électrique de la province de Katange RD/Congo, Available at https://hal.archives-ouvertes.fr/hal-02074381/document. [7] DEBAPRIYA DAS. (2006). Electrical power systems. New Delhi, India: New Age International (P). [8] Hadi SAADAT. (1999). Power system analysis. New York: The McGraw-Hill Companies. [9] G. K. Morison et al. (1993). Voltage stability analysis using static and dynamic approaches. IEEE Trans. on Power Systems, 8(3), 1159-1171.