SlideShare a Scribd company logo
1 of 40
FREQUENCY RESPONSE
ANALYSIS (FRA)
By Raveendra Nath Macherla, Senior Electrical Engineer
(Some Images Courtesy: Megger)
Standard
•IEC 60076-18
What is FRA test?
FRA is a diagnostic tool to
check for changes in internal
geometry of the active part of
transformer for displacements
or deformations.
When to
perform
frequency
response?
On all new transformers for fingerprinting purposes (FAT and
Pre-commissioning)
As part of routine electrical tests
After relocation
To assess damages following a through fault or long duration
short circuit
To assess damage following a tap-changer fault (or) After
repair to winding / tap changer
To assess damage during transportation,
To assess damage following a seismic event
Some of the causes affect frequency response
of Transformer
Winding deformations and displacements
Shorted turns and open windings
Loose or broken clamping structures
Core displacements
Faulty core grounds
Hoop Buckling (winding compressive failure)
Partial Winding collapse
Why FRA shall be done immediately
after Transformer arrival
(transportation)?
• Frequency response analysis is commonly used a tool to the detection
and evaluation of damage to a transformer during transportation. The
method can provide information about the mechanical condition of the
core, the windings, and the clamping structures with one set of
measurements. All these parts are susceptible to transportation damage.
Core to frame and tank insulation resistance should also be checked for
any transportation damage detection.
Does electrical tests are not sufficient? Why
FRA required?
Traditional electrical tests such as winding capacitance, excitation current and
leakage reactance measurements have proven to be not particularly sensitive
to detect winding movement.
 Winding capacitance measurement can detect winding movement only if
reference data is available or if measurements can be made on each phase.
 The excitation current can detect turn to turn failure as a result of winding
movement. However, if a turn-to-turn failure is absent, winding movement can
remain undetected.
 Leakage reactance , the discrepancies from the nameplate value of 3% can be
a reason for concern. This makes accurate assessments of the mechanical
integrity of the transformer very difficult.
PRINCIPLE OF FRA
Principle of FRA is the measurement of steady electrical response against a
steady sinusoidal input given to the test object.
How to perform FRA?
To make a frequency response measurement, a low voltage
is applied to one terminal of the test object with respect to
the tank. The voltage measured at this input terminal is
used as reference signal and a second voltage signal (the
response signal) is measured at a second terminal with
reference to the tank. The frequency response is the scalar
ratio between the response signal (Vout) and the reference
voltage (Vin) (presented in dB) as a function of the
frequency. The phase of the frequency response is the
phase difference between Vin and Vout (presented in
degrees).
Condition of Test object
• The test object shall be fully assembled as for service complete with all bushings (but coolers and related auxiliaries do not need to be
assembled.) and transformers shall be filled with liquid or gas of the same type as that which is to be used in service.
• The transformer under test must be completely disconnected from the network
• Neutral must be removed to ensure that the transformer under test is floating
• If internal CTs secondary terminals shall be shorted and earthed, if not connected to any load.
• The core and frame to tank connections shall be complete and the tank shall be connected to earth.
• If stabilizing winding (additional delta winding), where two terminals brought out shall be shorted but earth shall be disconnected.
• If DC testing was performed, the core must be demagnetized before any SFRA measurements
• Measurement must be made at the highest tap position ( full winding)
• It is not recommended to perform SFRA while the test object temperature is changing rapidly for example immediately following oil
treatment.
Checks prior to
measurement
The continuity of the test leads shall be verified.
If specified, zero-check measurement shall be
carried out as an additional measurement.
On completion of the standard measurements,
the first measurement shall be repeated and
recorded for repeatability check.
Instrument performance check (either by
calibration or by measuring the response of a
known test object)
Data to be recorded for each measurement
• Transformer serial number, Make, Rating, Tag No.
• Date (DD-MM-YYYY) and Time
• Test Instrument Make, Model, serial No.
• Peak voltage used for the measurement
• Reference terminal, Response terminal
• Terminals connected together
• Terminals earthed
• OLTC Tap position
• Previous OLTC Tap position, the tap position from which the tap-changer was moved to reach the tap position used during the measurement.
• Insulation medium filled or not
• Each data file shall be named as “Transformer tag no_reference terminal_response terminal_tap position_date_time”
• Any additional data shall be filled as per requirement
Measurement configuration
• The standard measurements shall be end-to-end measurements of each
phase of each winding, with the phases and windings separated as far as
possible and with all other terminals left floating.
• Measurement must be made at the highest tap position ( full winding)
• For two-winding three-phase transformers, the standard measurements
shall be one measurement of each phase of each winding, a total of 6
measurements for a transformer without tap and 9 for a transformer with
OLTC.
Measurement configuration
Star Connection winding Delta Connected Winding
Recommended measuring frequency range
• The lowest frequency measurement shall be at or below 20Hz.
• The minimum highest frequency measurement for test objects
- with highest voltage > 72.5 kV shall be 1 MHz.
- with highest voltage ≤ 72.5 kV shall be 2 MHz.
It is recommended that a highest measurement frequency of at
least 2 MHz is used for compatibility and simplicity for all test
objects.
Frequency
response
region -
dominated by:
Lower frequency region (up to 2 kHz) – Core
Middle frequency region (in between 2 kHz and 20
kHz) – Interactions between the windings
Higher frequency region (in between 20 kHz and 1
MHz) – individual winding structure, internal
connections
Highest frequencies – connection leads
Influence
regions
What to identify while comparison of
frequency responses?
• Changes in the overall shape of the frequency response;
• Changes in the number of resonances (maxima) and anti-resonances
(minima);
• Shifts in the position of the resonant frequencies.
Typical Frequency Response for HV Star winding
• For three phase three limb core-form
transformers, the middle phase would
have a single anti-resonance in this
frequency region due to the
symmetrical magnetic reluctance paths
seen by the middle phase of the
through the other phases. The outer
phases generally have two anti-
resonances since they experience two
different magnetic reluctance paths
one through the nearest (middle)
phase and one through the furthest
phase (the other outer phase).
Typical Frequency response for HV winding-
Delta (D)
Typical SFRA graph for HV winding- Zigzag (Z)
HV and LV winding frequency response
characteristics
• Typically , the response of the HV winding of large power transformers with a
high winding series capacitance shows a generic rising amplitude trend with few
resonances and anti-resonances.
• On the other hand, the LV winding with low series capacitance generally shows
flat amplitude trend and superimposed by a series of anti-resonances and
resonances.
• AT the highest frequencies of above 1 MHz (>72.5kV) or above 2 Mhz (≤ 72.5 kV),
the response is less repeatable and is influenced by the measurement set-up,
especially by the earthing connections, which effectively relies on the length of
the bushing.
Influence of Stabilizing winding
• If the stabilizing delta winding
connection is made outside the
tank and earthed, for better
phase comparison the earth
connection should be removed
leaving the delta connection
intact.
Influence of delta stabilizing winding
Influence of Tap position on Frequency
response
• When comparing the two
extreme tap positions to each
other, the curves follow each
other very closely in the lower
frequency ranges and then
upon reaching 40 kHz, they
diverge similarly to the
comparison of the nominal to
the extreme raised tap
position, though not as
significantly.
Influence of measurement direction
• It is important to record in
the measurement, in which
terminal the signal is being
injected into and from which
terminal the response
measurement is being made.
Influence of tap reversing switch on
frequency response
• When testing a transformer with an OLTC that
has a reversing switch, even if two measurements
are carried out at the same nominal tap position,
the results may vary slightly based on how the
tap position is approached. This happens on
designs where the reversing switch contacts are
positioned differently when the tap changer is
lowered to the nominal position compared with
when it is raised to the nominal position.
• Attached graph, there is no deviation between
the curves, most probably because the
transformer has a reactive type tap
changer. Nevertheless, care should still be taken
during SFRA testing always to approach the
nominal tap position from the R1 tap, and this
should be noted on the report to ensure
consistent testing in the future.
Influence of Insulation medium
Influence of DC injection frequency response
• DC injection test (Switching
impulse tests and winding
resistance tests) can leave
residual magnetism in the core
and can cause discrepancies
between frequency response
measurements especially in
the core influence region in
the low frequency range.
Influence of bushings on frequency response
• It is possible that different
bushings are used during FAT
compared to those fitted at site. This
may cause difference in the higher
frequencies.
• Larger discrepancies may be
expected in the higher frequencies if
the transformer is directly connected
to the SF6 insulated busbars and the
measurement is made by connecting
to the disconnected earth
connection of an earth switch.
Influence of shorting lead length in short-
circuit measurement response
The shorting connections used for short-circuit
measurements should be point-to-point – that is, as
short as possible.
The length of the shorting leads can influence
measurements in the high frequency range (1 MHz)
Influence of test voltage for frequency response
• changing the test voltage can
affect the sweep in the low
frequency region because of
the core influence. At higher
frequencies where the winding
dominates, the sweep
becomes independent of the
applied test voltage.
Influence of
removing core
ground
Influence of temperature on frequency response
• Temperature affects the frequency
response when the temperature
variation is larger than 50°C. The
Temperature differences cause changes
in winding resistance and hence the
amplitude of the frequency response.
Changes in fluid density and dielectric
constant with temperature together
with possible physical expansion can
also cause minor but consistent shifts
in resonant frequencies across the
frequency range.
Influence of grounding braid length on frequency response
Influence of
cable shield
grounding
on frequency
response
Influence of test instrument grounding on
frequency response
• Even though the grounding of
the test instrument does not
affect the measurements, it
must nevertheless be always
grounded to ensure safe
operation.
Some factors that influence Frequency responses:
1. SFRA measurement is sensitive to DC magnetization of the core and hence it has to be carried out before
application of any DC voltage. If any DC measurement was carried out before SFRA measurement, it should be
properly demagnetized.
2. SFRA plot may distort from the actual one in case of a loose connection. (may lead to variation in amplitude)
3. Proper grounding of the test instrument is essential, it is required that the bushing flange be solidly grounded
to the transformer tank.
4. Tap positions may have changed; there may be design difference between ‘sister units’.
5. Different measurement set-up and practice
6. Different internal lead lengths
7. Different winding inter-connections
8. Residual magnetization of the core also influences the frequency response in this region.
Is it safe to perform FRA on a transformer
without oil?
Yes.
FRA is safe to perform on a suitably prepared transformer without oil as
the test is low voltage one.
The effect of removing the oil is to reduce the capacitance of the
transformer, by changing a key dielectric from oil to air. This alters the
position of the resonances and their amplitude.
Conclusion
FRA is a powerful tool for use in analyzing transformer health and mechanical integrity.
FRA simulation does not provide “exact” matches with measured results; instead, it is
a tool to aid the understanding and interpretation of the measured results.
In order to interpret a measured frequency response, a comparison is made between
the measured response and a previous baseline measurement. If the baseline
measurement is unavailable, comparison can be made with the response measured
on a twin transformer.
“Don’t jump to conclusions”.
Where there are differences between phases or between successive measurements on the
same unit, the first question that must be asked is “ what are the possible causes of
the difference?”.

More Related Content

What's hot

Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of GeneratorRahuldey1991
 
3 phase transformer protection
3 phase transformer protection3 phase transformer protection
3 phase transformer protectionHimanshu Paghdal
 
Impulse test for power transformers
Impulse test for power transformersImpulse test for power transformers
Impulse test for power transformersjibinjoy1988
 
Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protectionRishi Tandon
 
Protection of transformer
Protection of transformerProtection of transformer
Protection of transformerSumeet Ratnawat
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers PremanandDesai
 
Distribution Transformer testing, West Bengal, India
Distribution Transformer testing,  West Bengal, IndiaDistribution Transformer testing,  West Bengal, India
Distribution Transformer testing, West Bengal, IndiaRajuMondal18
 
High voltage testing of electrical transformer
High voltage testing of electrical transformerHigh voltage testing of electrical transformer
High voltage testing of electrical transformerPraveenKumar5880
 
Line Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relayLine Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relaydavid roy
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protectionashwin fcc
 
Power System Protection
Power System ProtectionPower System Protection
Power System ProtectionRahul Mehra
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptxDirectional relay & Differential relay.pptx
Directional relay & Differential relay.pptxUtthejNani1
 
Stability test of transformer
Stability test of transformerStability test of transformer
Stability test of transformerSantu Mondal
 
Alternator protection
Alternator protectionAlternator protection
Alternator protectionjawaharramaya
 

What's hot (20)

Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of Generator
 
Transformer tests
Transformer testsTransformer tests
Transformer tests
 
3 phase transformer protection
3 phase transformer protection3 phase transformer protection
3 phase transformer protection
 
Impulse test for power transformers
Impulse test for power transformersImpulse test for power transformers
Impulse test for power transformers
 
Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protection
 
Protection of transformer
Protection of transformerProtection of transformer
Protection of transformer
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Substation
Substation Substation
Substation
 
Distribution Transformer testing, West Bengal, India
Distribution Transformer testing,  West Bengal, IndiaDistribution Transformer testing,  West Bengal, India
Distribution Transformer testing, West Bengal, India
 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
 
High voltage testing of electrical transformer
High voltage testing of electrical transformerHigh voltage testing of electrical transformer
High voltage testing of electrical transformer
 
Line Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relayLine Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relay
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 
Power System Protection
Power System ProtectionPower System Protection
Power System Protection
 
Switch yard & Protection
Switch yard & ProtectionSwitch yard & Protection
Switch yard & Protection
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptxDirectional relay & Differential relay.pptx
Directional relay & Differential relay.pptx
 
Stability test of transformer
Stability test of transformerStability test of transformer
Stability test of transformer
 
Alternator protection
Alternator protectionAlternator protection
Alternator protection
 

Similar to Frequency response analysis (FRA) of transformer

Impulse testing of transformer
Impulse testing of transformerImpulse testing of transformer
Impulse testing of transformerPreet_patel
 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHShankar Singh
 
Module 2 ee369 KTU syllabus-high voltage ac generation,resonant circuits
Module 2 ee369 KTU syllabus-high voltage ac generation,resonant circuitsModule 2 ee369 KTU syllabus-high voltage ac generation,resonant circuits
Module 2 ee369 KTU syllabus-high voltage ac generation,resonant circuitsAsha Anu Kurian
 
TESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptTESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptChristinaBoyd12
 
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.pptsantubanga333
 
TESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptTESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptssuser1f60f6
 
Transformers pptxx.ppt
Transformers pptxx.pptTransformers pptxx.ppt
Transformers pptxx.pptjaajasnjkja
 
Power-Transformer-Testing-Brochure-ENU.pdf
Power-Transformer-Testing-Brochure-ENU.pdfPower-Transformer-Testing-Brochure-ENU.pdf
Power-Transformer-Testing-Brochure-ENU.pdfNguyenXuanTung12
 
Switchgear & Rectifier ppt
Switchgear & Rectifier pptSwitchgear & Rectifier ppt
Switchgear & Rectifier pptvikas kumar
 
Exit Presentation - RC Calibration
Exit Presentation - RC CalibrationExit Presentation - RC Calibration
Exit Presentation - RC CalibrationScott Shermer
 
Gate Pulse Triggering of Single Phase Thyristor Circuit through Opto-Coupling
Gate Pulse Triggering of Single Phase Thyristor Circuit through Opto-CouplingGate Pulse Triggering of Single Phase Thyristor Circuit through Opto-Coupling
Gate Pulse Triggering of Single Phase Thyristor Circuit through Opto-CouplingNusrat Mary
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformervikasgupta1965
 
Lightning impulse test in precise
Lightning impulse test in  preciseLightning impulse test in  precise
Lightning impulse test in preciseMuthar Hussain
 
Power Electronics - Phase Controlled Converters.pptx
Power Electronics - Phase Controlled Converters.pptxPower Electronics - Phase Controlled Converters.pptx
Power Electronics - Phase Controlled Converters.pptxPoornima D
 

Similar to Frequency response analysis (FRA) of transformer (20)

Impulse testing of transformer
Impulse testing of transformerImpulse testing of transformer
Impulse testing of transformer
 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
 
Module 2 ee369 KTU syllabus-high voltage ac generation,resonant circuits
Module 2 ee369 KTU syllabus-high voltage ac generation,resonant circuitsModule 2 ee369 KTU syllabus-high voltage ac generation,resonant circuits
Module 2 ee369 KTU syllabus-high voltage ac generation,resonant circuits
 
TESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptTESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.ppt
 
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
 
TESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptTESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.ppt
 
Transformers pptxx.ppt
Transformers pptxx.pptTransformers pptxx.ppt
Transformers pptxx.ppt
 
Power-Transformer-Testing-Brochure-ENU.pdf
Power-Transformer-Testing-Brochure-ENU.pdfPower-Transformer-Testing-Brochure-ENU.pdf
Power-Transformer-Testing-Brochure-ENU.pdf
 
Switchgear & Rectifier ppt
Switchgear & Rectifier pptSwitchgear & Rectifier ppt
Switchgear & Rectifier ppt
 
Exit Presentation - RC Calibration
Exit Presentation - RC CalibrationExit Presentation - RC Calibration
Exit Presentation - RC Calibration
 
Gate Pulse Triggering of Single Phase Thyristor Circuit through Opto-Coupling
Gate Pulse Triggering of Single Phase Thyristor Circuit through Opto-CouplingGate Pulse Triggering of Single Phase Thyristor Circuit through Opto-Coupling
Gate Pulse Triggering of Single Phase Thyristor Circuit through Opto-Coupling
 
Ratio, Burden, and Admittance Testing
Ratio, Burden, and Admittance TestingRatio, Burden, and Admittance Testing
Ratio, Burden, and Admittance Testing
 
Voltage Regulation
Voltage RegulationVoltage Regulation
Voltage Regulation
 
ET 5 LESSON 2 TEST EQUIPMENT.pptx
ET 5 LESSON 2 TEST EQUIPMENT.pptxET 5 LESSON 2 TEST EQUIPMENT.pptx
ET 5 LESSON 2 TEST EQUIPMENT.pptx
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
Lightning impulse test in precise
Lightning impulse test in  preciseLightning impulse test in  precise
Lightning impulse test in precise
 
waveguide-1
waveguide-1waveguide-1
waveguide-1
 
Power Electronics - Phase Controlled Converters.pptx
Power Electronics - Phase Controlled Converters.pptxPower Electronics - Phase Controlled Converters.pptx
Power Electronics - Phase Controlled Converters.pptx
 
Transformer
TransformerTransformer
Transformer
 
Abb b.g. controlled switching ed4
Abb b.g. controlled switching ed4Abb b.g. controlled switching ed4
Abb b.g. controlled switching ed4
 

Recently uploaded

Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 

Recently uploaded (20)

Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 

Frequency response analysis (FRA) of transformer

  • 1. FREQUENCY RESPONSE ANALYSIS (FRA) By Raveendra Nath Macherla, Senior Electrical Engineer (Some Images Courtesy: Megger)
  • 3. What is FRA test? FRA is a diagnostic tool to check for changes in internal geometry of the active part of transformer for displacements or deformations.
  • 4. When to perform frequency response? On all new transformers for fingerprinting purposes (FAT and Pre-commissioning) As part of routine electrical tests After relocation To assess damages following a through fault or long duration short circuit To assess damage following a tap-changer fault (or) After repair to winding / tap changer To assess damage during transportation, To assess damage following a seismic event
  • 5. Some of the causes affect frequency response of Transformer Winding deformations and displacements Shorted turns and open windings Loose or broken clamping structures Core displacements Faulty core grounds Hoop Buckling (winding compressive failure) Partial Winding collapse
  • 6. Why FRA shall be done immediately after Transformer arrival (transportation)? • Frequency response analysis is commonly used a tool to the detection and evaluation of damage to a transformer during transportation. The method can provide information about the mechanical condition of the core, the windings, and the clamping structures with one set of measurements. All these parts are susceptible to transportation damage. Core to frame and tank insulation resistance should also be checked for any transportation damage detection.
  • 7. Does electrical tests are not sufficient? Why FRA required? Traditional electrical tests such as winding capacitance, excitation current and leakage reactance measurements have proven to be not particularly sensitive to detect winding movement.  Winding capacitance measurement can detect winding movement only if reference data is available or if measurements can be made on each phase.  The excitation current can detect turn to turn failure as a result of winding movement. However, if a turn-to-turn failure is absent, winding movement can remain undetected.  Leakage reactance , the discrepancies from the nameplate value of 3% can be a reason for concern. This makes accurate assessments of the mechanical integrity of the transformer very difficult.
  • 8. PRINCIPLE OF FRA Principle of FRA is the measurement of steady electrical response against a steady sinusoidal input given to the test object.
  • 9. How to perform FRA? To make a frequency response measurement, a low voltage is applied to one terminal of the test object with respect to the tank. The voltage measured at this input terminal is used as reference signal and a second voltage signal (the response signal) is measured at a second terminal with reference to the tank. The frequency response is the scalar ratio between the response signal (Vout) and the reference voltage (Vin) (presented in dB) as a function of the frequency. The phase of the frequency response is the phase difference between Vin and Vout (presented in degrees).
  • 10. Condition of Test object • The test object shall be fully assembled as for service complete with all bushings (but coolers and related auxiliaries do not need to be assembled.) and transformers shall be filled with liquid or gas of the same type as that which is to be used in service. • The transformer under test must be completely disconnected from the network • Neutral must be removed to ensure that the transformer under test is floating • If internal CTs secondary terminals shall be shorted and earthed, if not connected to any load. • The core and frame to tank connections shall be complete and the tank shall be connected to earth. • If stabilizing winding (additional delta winding), where two terminals brought out shall be shorted but earth shall be disconnected. • If DC testing was performed, the core must be demagnetized before any SFRA measurements • Measurement must be made at the highest tap position ( full winding) • It is not recommended to perform SFRA while the test object temperature is changing rapidly for example immediately following oil treatment.
  • 11. Checks prior to measurement The continuity of the test leads shall be verified. If specified, zero-check measurement shall be carried out as an additional measurement. On completion of the standard measurements, the first measurement shall be repeated and recorded for repeatability check. Instrument performance check (either by calibration or by measuring the response of a known test object)
  • 12. Data to be recorded for each measurement • Transformer serial number, Make, Rating, Tag No. • Date (DD-MM-YYYY) and Time • Test Instrument Make, Model, serial No. • Peak voltage used for the measurement • Reference terminal, Response terminal • Terminals connected together • Terminals earthed • OLTC Tap position • Previous OLTC Tap position, the tap position from which the tap-changer was moved to reach the tap position used during the measurement. • Insulation medium filled or not • Each data file shall be named as “Transformer tag no_reference terminal_response terminal_tap position_date_time” • Any additional data shall be filled as per requirement
  • 13. Measurement configuration • The standard measurements shall be end-to-end measurements of each phase of each winding, with the phases and windings separated as far as possible and with all other terminals left floating. • Measurement must be made at the highest tap position ( full winding) • For two-winding three-phase transformers, the standard measurements shall be one measurement of each phase of each winding, a total of 6 measurements for a transformer without tap and 9 for a transformer with OLTC.
  • 14. Measurement configuration Star Connection winding Delta Connected Winding
  • 15. Recommended measuring frequency range • The lowest frequency measurement shall be at or below 20Hz. • The minimum highest frequency measurement for test objects - with highest voltage > 72.5 kV shall be 1 MHz. - with highest voltage ≤ 72.5 kV shall be 2 MHz. It is recommended that a highest measurement frequency of at least 2 MHz is used for compatibility and simplicity for all test objects.
  • 16. Frequency response region - dominated by: Lower frequency region (up to 2 kHz) – Core Middle frequency region (in between 2 kHz and 20 kHz) – Interactions between the windings Higher frequency region (in between 20 kHz and 1 MHz) – individual winding structure, internal connections Highest frequencies – connection leads
  • 18. What to identify while comparison of frequency responses? • Changes in the overall shape of the frequency response; • Changes in the number of resonances (maxima) and anti-resonances (minima); • Shifts in the position of the resonant frequencies.
  • 19. Typical Frequency Response for HV Star winding • For three phase three limb core-form transformers, the middle phase would have a single anti-resonance in this frequency region due to the symmetrical magnetic reluctance paths seen by the middle phase of the through the other phases. The outer phases generally have two anti- resonances since they experience two different magnetic reluctance paths one through the nearest (middle) phase and one through the furthest phase (the other outer phase).
  • 20. Typical Frequency response for HV winding- Delta (D)
  • 21. Typical SFRA graph for HV winding- Zigzag (Z)
  • 22. HV and LV winding frequency response characteristics • Typically , the response of the HV winding of large power transformers with a high winding series capacitance shows a generic rising amplitude trend with few resonances and anti-resonances. • On the other hand, the LV winding with low series capacitance generally shows flat amplitude trend and superimposed by a series of anti-resonances and resonances. • AT the highest frequencies of above 1 MHz (>72.5kV) or above 2 Mhz (≤ 72.5 kV), the response is less repeatable and is influenced by the measurement set-up, especially by the earthing connections, which effectively relies on the length of the bushing.
  • 23. Influence of Stabilizing winding • If the stabilizing delta winding connection is made outside the tank and earthed, for better phase comparison the earth connection should be removed leaving the delta connection intact.
  • 24. Influence of delta stabilizing winding
  • 25. Influence of Tap position on Frequency response • When comparing the two extreme tap positions to each other, the curves follow each other very closely in the lower frequency ranges and then upon reaching 40 kHz, they diverge similarly to the comparison of the nominal to the extreme raised tap position, though not as significantly.
  • 26. Influence of measurement direction • It is important to record in the measurement, in which terminal the signal is being injected into and from which terminal the response measurement is being made.
  • 27. Influence of tap reversing switch on frequency response • When testing a transformer with an OLTC that has a reversing switch, even if two measurements are carried out at the same nominal tap position, the results may vary slightly based on how the tap position is approached. This happens on designs where the reversing switch contacts are positioned differently when the tap changer is lowered to the nominal position compared with when it is raised to the nominal position. • Attached graph, there is no deviation between the curves, most probably because the transformer has a reactive type tap changer. Nevertheless, care should still be taken during SFRA testing always to approach the nominal tap position from the R1 tap, and this should be noted on the report to ensure consistent testing in the future.
  • 29. Influence of DC injection frequency response • DC injection test (Switching impulse tests and winding resistance tests) can leave residual magnetism in the core and can cause discrepancies between frequency response measurements especially in the core influence region in the low frequency range.
  • 30. Influence of bushings on frequency response • It is possible that different bushings are used during FAT compared to those fitted at site. This may cause difference in the higher frequencies. • Larger discrepancies may be expected in the higher frequencies if the transformer is directly connected to the SF6 insulated busbars and the measurement is made by connecting to the disconnected earth connection of an earth switch.
  • 31. Influence of shorting lead length in short- circuit measurement response The shorting connections used for short-circuit measurements should be point-to-point – that is, as short as possible. The length of the shorting leads can influence measurements in the high frequency range (1 MHz)
  • 32. Influence of test voltage for frequency response • changing the test voltage can affect the sweep in the low frequency region because of the core influence. At higher frequencies where the winding dominates, the sweep becomes independent of the applied test voltage.
  • 34. Influence of temperature on frequency response • Temperature affects the frequency response when the temperature variation is larger than 50°C. The Temperature differences cause changes in winding resistance and hence the amplitude of the frequency response. Changes in fluid density and dielectric constant with temperature together with possible physical expansion can also cause minor but consistent shifts in resonant frequencies across the frequency range.
  • 35. Influence of grounding braid length on frequency response
  • 37. Influence of test instrument grounding on frequency response • Even though the grounding of the test instrument does not affect the measurements, it must nevertheless be always grounded to ensure safe operation.
  • 38. Some factors that influence Frequency responses: 1. SFRA measurement is sensitive to DC magnetization of the core and hence it has to be carried out before application of any DC voltage. If any DC measurement was carried out before SFRA measurement, it should be properly demagnetized. 2. SFRA plot may distort from the actual one in case of a loose connection. (may lead to variation in amplitude) 3. Proper grounding of the test instrument is essential, it is required that the bushing flange be solidly grounded to the transformer tank. 4. Tap positions may have changed; there may be design difference between ‘sister units’. 5. Different measurement set-up and practice 6. Different internal lead lengths 7. Different winding inter-connections 8. Residual magnetization of the core also influences the frequency response in this region.
  • 39. Is it safe to perform FRA on a transformer without oil? Yes. FRA is safe to perform on a suitably prepared transformer without oil as the test is low voltage one. The effect of removing the oil is to reduce the capacitance of the transformer, by changing a key dielectric from oil to air. This alters the position of the resonances and their amplitude.
  • 40. Conclusion FRA is a powerful tool for use in analyzing transformer health and mechanical integrity. FRA simulation does not provide “exact” matches with measured results; instead, it is a tool to aid the understanding and interpretation of the measured results. In order to interpret a measured frequency response, a comparison is made between the measured response and a previous baseline measurement. If the baseline measurement is unavailable, comparison can be made with the response measured on a twin transformer. “Don’t jump to conclusions”. Where there are differences between phases or between successive measurements on the same unit, the first question that must be asked is “ what are the possible causes of the difference?”.