KoCoS America
                            IEEE Switchgear Committee
n Breaker Analysis
n Relay Testing
n Digital Fault Recording
                            Testing Breakers with Both Sides
n Meter Testing             Grounded
n Power Quality Analysis
n Optical Measurement       www.kocos.com
KoCoS Presentation outline


              Background
               • Main Contact Timing
               • Both Side Grounded
              Measuring Methods
               • Conventional
               • Dynamic Timing
               • New Method
              Tested sample
              Comparison
KOCOS AMERICA LLC

Founded:               October 2001


Located in:            136 Oak St. Suite A
                       Westerly, RI
                       Phone +1 401 213 6518
                       Email: gwasfy@kocos.com
                       www.kocos.com
•                      http://twitter.com/KoCoS_America


Managing Directors:    Guy Wasfy
                       Thomas Becker
KOCOS AMERICA LLC


Jean-Guy Wasfy
43 years old
Born in Montreal.
Guy Wasfy received his BSEE from
University of Rhode Island, graduating in
1990.
First job was for Doble Engineering,
performed many roles, such as as a client
service engineer, a product manager, and
an International Sales manager.
In 2001, formed a subsidiary along with
KoCoS AG, for all of North American
Operations.
KoCoS Presentation


          Context / Background



 Switching devices are essential equipment in a substation.

 The current must be interrupted if a failure occurs.

 To guarantee the operation the circuit breaker need
  maintenance.

 Reasons:
  • Wear of the moving parts
  • leak on valves and seals
  • Failures in control circuits
  • Deterioration of contact parts
  • Problems with compressors, springs, and other “speed”
  parts
KoCoS Presentation

          Why is a determination
          of the main contact timing important?


 Fundamental and important test for testing circuit
  breakers:
   Determination of main contact timing

 Determination of timing from command until execution.

  Circuit breaker need maintenance

 Determination of:
  1) Synchronisation between poles
  2) Synchronisation of contacts within one pole
KoCoS Presentation


         Parameters measured



 -   main contact velocity,
 -   main contact travel and
 -   the operating times of all switching contacts.
 -   Coil operating currents,
 -   the operating currents of spring-tensioning or pump
     motors,
 -   valve pressures,
 -   valve travel and mechanical main contact travel,
 -   in addition main and auxiliary contact state,
 -   Main contact resistance.
KoCoS Presentation


                      Typical Close-Open-Operation



     Main contacts




                                                               Closed position

                                                               Contact closure
                           Closing                   Opening
                           time                      time




Main contact travel



       Coil current
KoCoS Presentation


      Example: main contact timing
KoCoS Presentation


          Conventional Method



 Decommission of circuit breaker - danger through:
  • undesirable electrical potential
  • capacitive or inductively coupled voltages

 Safety through connection of the circuit breaker to ground.

 Exception: measurement of main contact timing

 Practice: the ground must be removed on one side of the
  breaker pole for test

 Used for the conventional measurement method.
KoCoS Presentation


           Conventional Method



   Ground both sides of the breaker with grounding cables
   Connect timing set to breaker
   Remove ground from one side of breaker
   Perform tests
   Ground the one side that is not connected
   Remove leads

 IEEE and OSHA Require that the breaker be grounded at
  both sides during maintenance
 Accepted exception to laws and standards that call for both
  sides to be grounded at all times, but not recommended.
KoCoS Presentation


         Conventional Method



 Electrical Risk!
   - Fault
   - Lightning
   - Electrical coupling
       • IEC ® EN 61010 considers any current above 3.5
         mA dangerous
KoCoS Presentation


           Why test with Both Sides Grounded?



 Financial – the cost of removing the ground from one side
  of the breaker can be costly – utility studies have shown
  the cost could reach $6,000 or higher.
   -   Overtime
   -   Bucket truck
   -   Harness
   -   Supervisor
   -   GCB, big conductors

 Safety through connection of the circuit breaker to ground.
   - Testing and operations can be done inside the ground circuit
     of the breaker
 Ease of use
 Reduced switching time
 Less paperwork
KoCoS Presentation


      Example: Earthed on both sides
KoCoS Presentation


          Conventional measuring method

 Binary measurement inputs for main contact timing
   by comparator method




 Signal threshold:
  • R < 30 Ω         Main and resistive contact closed
  • 30 Ω < R < 30 kΩ Resistive contact closed
  • R > 30 kΩ        Main and resistive contact open

 Earthing: main contact status CLOSED
   • total resistance of the earth loop < 30 Ω

 The earth must be removed on one side of the breaker!
KoCoS Presentation

      Connection diagram with
      Main Contacts IN

                          Circuit breaker must be
                           grounded on both sides when
                           the measuring leads are being
                           attached.

                          The ground must be removed
                           on one side of the breaker for
                           the test.

                          The ground connection should
                           always remain in place on the
                           side on which there is the
                           greatest danger of capacitive
                           or inductively coupled
                           voltages.
KoCoS Presentation


          Analog main contact measurement inputs

 Hardware option Dynamic Timing

 Voltage drop measurement with test current 10 A

 Determination of operating instants  special algorithm

 ACTAS P22: 6 analog voltage measurement inputs
  • per Pole: 2 measurement inputs
  • Range: 200 mV / 10 V
  • 10 A constant-current source per pole
KoCoS Presentation

        Connection diagram for
        voltage drop measurement

       -Sense
                -ICONST    Leads for the electricity supply
                             and the voltage drop
                             measurement are not attached
                             at the same place.
  +ICONST

       +Sense              The measuring leads should be
                             attached close to the test
                             object.

                           The earth connections may
                             remain connected on both
                             sides of the breaker pole
                             during tests!
KoCoS Presentation


          Kelvin (4-wire) resistance measurement



 Measurement of electrical resistance

 Known current through test object (resistance)

 Measurement of voltage drop

 Measuring faults through voltage drop on current lead are
  avoided

 Calculation of the resistance is based on Ohm’s Law:
  R=V/I
KoCoS Presentation

          Diagram: Kelvin (4-wire) resistance
          measurement


                   RWIRE



                              RWIRE
                                                ICONST


                                  UOBJECT        ROBJECT
 ICONST                       RWIRE




                   RWIRE
KoCoS Presentation


          Basic information: Earthing



 For grounded long connection leads: ~ 20 mΩ

 Contact resistance of the circuit breaker: ~ 20 μΩ

 Target: reliable detection of contact state

 Resistance of ground has no affect of the test.
KoCoS Presentation


      Basic information


                                   ICONST




                                        U




                                  RCONTACT




                                             RWIRE
                          RWIRE
KoCoS Presentation


           Worked sample: Without Earthing

Circuit breaker: OPEN            Circuit breaker: CLOSED

    ICONST = 10 A                    ICONST = 10 A




                                     RCB = 20 μΩ



      V~5V                           V = 0.2 mV
KoCoS Presentation


                  Worked sample: With Earthing

       Circuit breaker: OPEN              Circuit breaker: CLOSED

           ICONST = 10 A                      ICONST = 10 A




                                              RCB = 20 μΩ


           V = 200 mV                        V = 0.199 mV
RW =                       RW =    RW =       ICB = 9.99 A    RW =

10 mΩ                      10 mΩ   10 mΩ                      10 mΩ




                                            IWIRE = 0.009 A
KoCoS Presentation

                  Measurement of the Earth Current (new
                  development)




Another method to determine the times at both side grounded breaker is to
capture a current change in the ground lines during a switching operation.

The grounding at both ends of the switching device results in a parallel
connection of the contact and the earth.

A constant current is connected to the contact, and is divided in the parallel
circuit to a ground current and current to the contact.

If the contact is open the constant current flows through the earth, with
closed contact to inform on the current.
KoCoS Presentation

                 Measurement of the Earth Current (new
                 development)




These current changes the switching times of the contact can be determined
For feeding the constant current sources are the dynamic timing function
(ICON = 10 A) connected to the switching unit. The current probes detect
the current IE in the ground wire and connected to the 200mV/10V-
measurement inputs.

Both methods for determining the switching times, the above-described 4-
wire method, and the earth current measurement are selectable in the
software.
KoCoS Presentation


      New method




         IK         IK


           CB         RCB


           ICB

          IE

                           RE
KoCoS Presentation


      Test with Main Contact IN - CLOSE
KoCoS Presentation


      Test with Main Contact IN - OPEN
KoCoS Presentation

         Test with Dynamic Timing – CLOSE
         without Earthing (Short Circuit)




                             Measurement of voltage drop
                             3 phase




 Short circuit: ~ 3 mΩ (~ 32 mV, 10 A)
KoCoS Presentation

      Test with Dynamic Timing – OPEN
      without Earthing (Short Circuit)
KoCoS Presentation


         Comparison


                               C Time    A       B       C
CLOSE – Operation     Main Contact IN   64.10   63.90   64.90 ms
                      Dynamic Timing    64.40   64.60   65.40 ms
                      (without)

                      Dynamic Timing    64.10   63.80   65.20 ms
                      (with)


OPEN - Operation               O Time    A       B       C
                      Main Contact IN   34.70   34.60   34.90 ms
                      Dynamic Timing    35.10   34.80   35.20 ms
                      (without)

                      Dynamic Timing    35.50   35.00   35.40 ms
                      (with)
KoCoS Presentation


              Advantages



 Test with both sides earthing
  possible.

 No additional equipment required

 Safety of the operator is secured

 Determination of
  Graphite Contacts




                                      ©RWE
KoCoS Presentation


                   Advantages



 Additional external measuring devices are not
    required.
   No special measuring cables are necessary.
   Connect directly to a device. The workload is
    therefore low.
   No calibration or adjustment to the electrical
    conditions of the apparatus.
    No triggering of external devices and the
    associated distortion of the switching times
    needed.
    The measuring current may be permanently
    made ​available. A waiting time until the next
    circuit is not required.
    A dynamic analysis is the recorded traces. This
    allows for precise analysis of contact systems with
    material transitions, such as Graphite-metal.


                                                          ©RWE
KoCoS Presentation


      Method used on any breaker
KoCoS America

n Breaker Analysis
n Relay Testing
n Digital Fault Recording   Thank you for your interest.
n Meter Testing
n Power Quality Analysis
n Optical Measurement       www.kocos.com

More Related Content

Viewers also liked (9)

Powerpoint.j
Powerpoint.jPowerpoint.j
Powerpoint.j
 
INDEC Brochure
INDEC BrochureINDEC Brochure
INDEC Brochure
 
Bai giang-spm-11mar14
Bai giang-spm-11mar14Bai giang-spm-11mar14
Bai giang-spm-11mar14
 
Bai giang-uml-25-27feb14
Bai giang-uml-25-27feb14Bai giang-uml-25-27feb14
Bai giang-uml-25-27feb14
 
Bai giang-se-03mar14
Bai giang-se-03mar14Bai giang-se-03mar14
Bai giang-se-03mar14
 
KoCoS Brochure
KoCoS BrochureKoCoS Brochure
KoCoS Brochure
 
Cuadernillo e instalaciones
Cuadernillo e instalacionesCuadernillo e instalaciones
Cuadernillo e instalaciones
 
A última pergunta - Isaac Asimov
A última pergunta -  Isaac AsimovA última pergunta -  Isaac Asimov
A última pergunta - Isaac Asimov
 
Response to Intervention (RtI): Port Washington-Saukville, Wis.
Response to Intervention (RtI): Port Washington-Saukville, Wis.Response to Intervention (RtI): Port Washington-Saukville, Wis.
Response to Intervention (RtI): Port Washington-Saukville, Wis.
 

Similar to Both Sides Grounded

VLSI D PPT.pdf
VLSI D PPT.pdfVLSI D PPT.pdf
VLSI D PPT.pdfAMohan12
 
2012 FEPA Presentation: Ted Huck
2012 FEPA Presentation: Ted Huck2012 FEPA Presentation: Ted Huck
2012 FEPA Presentation: Ted HuckFloridaPipeTalk
 
2012 FEPA Presentation: Jeff Didas
2012 FEPA Presentation: Jeff Didas2012 FEPA Presentation: Jeff Didas
2012 FEPA Presentation: Jeff DidasFloridaPipeTalk
 
Webinar 03 electrical installation of pv system
Webinar 03 electrical installation of pv system Webinar 03 electrical installation of pv system
Webinar 03 electrical installation of pv system solpowerpeople
 
Substationoverview
Substationoverview Substationoverview
Substationoverview sailusree
 
Cooper Power Connectors - MV-HV Specifiers Guide 5kV-35kV
Cooper Power Connectors - MV-HV Specifiers Guide 5kV-35kVCooper Power Connectors - MV-HV Specifiers Guide 5kV-35kV
Cooper Power Connectors - MV-HV Specifiers Guide 5kV-35kVThorne & Derrick International
 
Decoupler Interaction With CP Systems - Mike Tachick
Decoupler Interaction With CP Systems - Mike TachickDecoupler Interaction With CP Systems - Mike Tachick
Decoupler Interaction With CP Systems - Mike Tachicknacetwincities
 
ACVG vs DCVG: Does It Matter? - Jim Walton
ACVG vs DCVG: Does It Matter? - Jim WaltonACVG vs DCVG: Does It Matter? - Jim Walton
ACVG vs DCVG: Does It Matter? - Jim Waltonnacetwincities
 
Load Cell Lunch and Learn Presented by Interface
Load Cell Lunch and Learn Presented by InterfaceLoad Cell Lunch and Learn Presented by Interface
Load Cell Lunch and Learn Presented by InterfaceInterface
 
Solar Power Based Buck boost Regulator
Solar Power Based Buck boost RegulatorSolar Power Based Buck boost Regulator
Solar Power Based Buck boost RegulatorAntesh Jain
 

Similar to Both Sides Grounded (20)

VLSI D PPT.pdf
VLSI D PPT.pdfVLSI D PPT.pdf
VLSI D PPT.pdf
 
2012 FEPA Presentation: Ted Huck
2012 FEPA Presentation: Ted Huck2012 FEPA Presentation: Ted Huck
2012 FEPA Presentation: Ted Huck
 
2012 FEPA Presentation: Jeff Didas
2012 FEPA Presentation: Jeff Didas2012 FEPA Presentation: Jeff Didas
2012 FEPA Presentation: Jeff Didas
 
Technotoy stage 4
Technotoy stage 4Technotoy stage 4
Technotoy stage 4
 
Technotoy stage 4
Technotoy stage 4Technotoy stage 4
Technotoy stage 4
 
Webinar 03 electrical installation of pv system
Webinar 03 electrical installation of pv system Webinar 03 electrical installation of pv system
Webinar 03 electrical installation of pv system
 
Substation overview
Substation overviewSubstation overview
Substation overview
 
Substationoverview
Substationoverview Substationoverview
Substationoverview
 
Ehv ac transmission line
Ehv ac transmission lineEhv ac transmission line
Ehv ac transmission line
 
Dc voltage
Dc voltageDc voltage
Dc voltage
 
Cable Sizing Calculations
Cable Sizing CalculationsCable Sizing Calculations
Cable Sizing Calculations
 
Distribution systems
Distribution systemsDistribution systems
Distribution systems
 
Cooper Power Connectors - MV-HV Specifiers Guide 5kV-35kV
Cooper Power Connectors - MV-HV Specifiers Guide 5kV-35kVCooper Power Connectors - MV-HV Specifiers Guide 5kV-35kV
Cooper Power Connectors - MV-HV Specifiers Guide 5kV-35kV
 
Decoupler Interaction With CP Systems - Mike Tachick
Decoupler Interaction With CP Systems - Mike TachickDecoupler Interaction With CP Systems - Mike Tachick
Decoupler Interaction With CP Systems - Mike Tachick
 
ACVG vs DCVG: Does It Matter? - Jim Walton
ACVG vs DCVG: Does It Matter? - Jim WaltonACVG vs DCVG: Does It Matter? - Jim Walton
ACVG vs DCVG: Does It Matter? - Jim Walton
 
Load Cell Lunch and Learn Presented by Interface
Load Cell Lunch and Learn Presented by InterfaceLoad Cell Lunch and Learn Presented by Interface
Load Cell Lunch and Learn Presented by Interface
 
Solar Power Based Buck boost Regulator
Solar Power Based Buck boost RegulatorSolar Power Based Buck boost Regulator
Solar Power Based Buck boost Regulator
 
Technotoy5
Technotoy5Technotoy5
Technotoy5
 
Technotoy5
Technotoy5Technotoy5
Technotoy5
 
Datasheet Seaward HV Indicators
Datasheet Seaward HV IndicatorsDatasheet Seaward HV Indicators
Datasheet Seaward HV Indicators
 

Both Sides Grounded

  • 1. KoCoS America IEEE Switchgear Committee n Breaker Analysis n Relay Testing n Digital Fault Recording Testing Breakers with Both Sides n Meter Testing Grounded n Power Quality Analysis n Optical Measurement www.kocos.com
  • 2. KoCoS Presentation outline  Background • Main Contact Timing • Both Side Grounded  Measuring Methods • Conventional • Dynamic Timing • New Method  Tested sample  Comparison
  • 3. KOCOS AMERICA LLC Founded: October 2001 Located in: 136 Oak St. Suite A Westerly, RI Phone +1 401 213 6518 Email: gwasfy@kocos.com www.kocos.com • http://twitter.com/KoCoS_America Managing Directors: Guy Wasfy Thomas Becker
  • 4. KOCOS AMERICA LLC Jean-Guy Wasfy 43 years old Born in Montreal. Guy Wasfy received his BSEE from University of Rhode Island, graduating in 1990. First job was for Doble Engineering, performed many roles, such as as a client service engineer, a product manager, and an International Sales manager. In 2001, formed a subsidiary along with KoCoS AG, for all of North American Operations.
  • 5. KoCoS Presentation Context / Background  Switching devices are essential equipment in a substation.  The current must be interrupted if a failure occurs.  To guarantee the operation the circuit breaker need maintenance.  Reasons: • Wear of the moving parts • leak on valves and seals • Failures in control circuits • Deterioration of contact parts • Problems with compressors, springs, and other “speed” parts
  • 6. KoCoS Presentation Why is a determination of the main contact timing important?  Fundamental and important test for testing circuit breakers:  Determination of main contact timing  Determination of timing from command until execution.   Circuit breaker need maintenance  Determination of: 1) Synchronisation between poles 2) Synchronisation of contacts within one pole
  • 7. KoCoS Presentation Parameters measured - main contact velocity, - main contact travel and - the operating times of all switching contacts. - Coil operating currents, - the operating currents of spring-tensioning or pump motors, - valve pressures, - valve travel and mechanical main contact travel, - in addition main and auxiliary contact state, - Main contact resistance.
  • 8. KoCoS Presentation Typical Close-Open-Operation Main contacts Closed position Contact closure Closing Opening time time Main contact travel Coil current
  • 9. KoCoS Presentation Example: main contact timing
  • 10. KoCoS Presentation Conventional Method  Decommission of circuit breaker - danger through: • undesirable electrical potential • capacitive or inductively coupled voltages  Safety through connection of the circuit breaker to ground.  Exception: measurement of main contact timing  Practice: the ground must be removed on one side of the breaker pole for test  Used for the conventional measurement method.
  • 11. KoCoS Presentation Conventional Method  Ground both sides of the breaker with grounding cables  Connect timing set to breaker  Remove ground from one side of breaker  Perform tests  Ground the one side that is not connected  Remove leads  IEEE and OSHA Require that the breaker be grounded at both sides during maintenance  Accepted exception to laws and standards that call for both sides to be grounded at all times, but not recommended.
  • 12. KoCoS Presentation Conventional Method  Electrical Risk! - Fault - Lightning - Electrical coupling • IEC ® EN 61010 considers any current above 3.5 mA dangerous
  • 13. KoCoS Presentation Why test with Both Sides Grounded?  Financial – the cost of removing the ground from one side of the breaker can be costly – utility studies have shown the cost could reach $6,000 or higher. - Overtime - Bucket truck - Harness - Supervisor - GCB, big conductors  Safety through connection of the circuit breaker to ground. - Testing and operations can be done inside the ground circuit of the breaker  Ease of use  Reduced switching time  Less paperwork
  • 14. KoCoS Presentation Example: Earthed on both sides
  • 15. KoCoS Presentation Conventional measuring method  Binary measurement inputs for main contact timing  by comparator method  Signal threshold: • R < 30 Ω Main and resistive contact closed • 30 Ω < R < 30 kΩ Resistive contact closed • R > 30 kΩ Main and resistive contact open  Earthing: main contact status CLOSED • total resistance of the earth loop < 30 Ω  The earth must be removed on one side of the breaker!
  • 16. KoCoS Presentation Connection diagram with Main Contacts IN  Circuit breaker must be grounded on both sides when the measuring leads are being attached.  The ground must be removed on one side of the breaker for the test.  The ground connection should always remain in place on the side on which there is the greatest danger of capacitive or inductively coupled voltages.
  • 17. KoCoS Presentation Analog main contact measurement inputs  Hardware option Dynamic Timing  Voltage drop measurement with test current 10 A  Determination of operating instants  special algorithm  ACTAS P22: 6 analog voltage measurement inputs • per Pole: 2 measurement inputs • Range: 200 mV / 10 V • 10 A constant-current source per pole
  • 18. KoCoS Presentation Connection diagram for voltage drop measurement -Sense -ICONST  Leads for the electricity supply and the voltage drop measurement are not attached at the same place. +ICONST +Sense  The measuring leads should be attached close to the test object.  The earth connections may remain connected on both sides of the breaker pole during tests!
  • 19. KoCoS Presentation Kelvin (4-wire) resistance measurement  Measurement of electrical resistance  Known current through test object (resistance)  Measurement of voltage drop  Measuring faults through voltage drop on current lead are avoided  Calculation of the resistance is based on Ohm’s Law: R=V/I
  • 20. KoCoS Presentation Diagram: Kelvin (4-wire) resistance measurement RWIRE RWIRE ICONST UOBJECT ROBJECT ICONST RWIRE RWIRE
  • 21. KoCoS Presentation Basic information: Earthing  For grounded long connection leads: ~ 20 mΩ  Contact resistance of the circuit breaker: ~ 20 μΩ  Target: reliable detection of contact state  Resistance of ground has no affect of the test.
  • 22. KoCoS Presentation Basic information ICONST U RCONTACT RWIRE RWIRE
  • 23. KoCoS Presentation Worked sample: Without Earthing Circuit breaker: OPEN Circuit breaker: CLOSED ICONST = 10 A ICONST = 10 A RCB = 20 μΩ V~5V V = 0.2 mV
  • 24. KoCoS Presentation Worked sample: With Earthing Circuit breaker: OPEN Circuit breaker: CLOSED ICONST = 10 A ICONST = 10 A RCB = 20 μΩ V = 200 mV V = 0.199 mV RW = RW = RW = ICB = 9.99 A RW = 10 mΩ 10 mΩ 10 mΩ 10 mΩ IWIRE = 0.009 A
  • 25. KoCoS Presentation Measurement of the Earth Current (new development) Another method to determine the times at both side grounded breaker is to capture a current change in the ground lines during a switching operation. The grounding at both ends of the switching device results in a parallel connection of the contact and the earth. A constant current is connected to the contact, and is divided in the parallel circuit to a ground current and current to the contact. If the contact is open the constant current flows through the earth, with closed contact to inform on the current.
  • 26. KoCoS Presentation Measurement of the Earth Current (new development) These current changes the switching times of the contact can be determined For feeding the constant current sources are the dynamic timing function (ICON = 10 A) connected to the switching unit. The current probes detect the current IE in the ground wire and connected to the 200mV/10V- measurement inputs. Both methods for determining the switching times, the above-described 4- wire method, and the earth current measurement are selectable in the software.
  • 27. KoCoS Presentation New method IK IK CB RCB ICB IE RE
  • 28. KoCoS Presentation Test with Main Contact IN - CLOSE
  • 29. KoCoS Presentation Test with Main Contact IN - OPEN
  • 30. KoCoS Presentation Test with Dynamic Timing – CLOSE without Earthing (Short Circuit) Measurement of voltage drop 3 phase  Short circuit: ~ 3 mΩ (~ 32 mV, 10 A)
  • 31. KoCoS Presentation Test with Dynamic Timing – OPEN without Earthing (Short Circuit)
  • 32. KoCoS Presentation Comparison C Time A B C CLOSE – Operation Main Contact IN 64.10 63.90 64.90 ms Dynamic Timing 64.40 64.60 65.40 ms (without) Dynamic Timing 64.10 63.80 65.20 ms (with) OPEN - Operation O Time A B C Main Contact IN 34.70 34.60 34.90 ms Dynamic Timing 35.10 34.80 35.20 ms (without) Dynamic Timing 35.50 35.00 35.40 ms (with)
  • 33. KoCoS Presentation Advantages  Test with both sides earthing possible.  No additional equipment required  Safety of the operator is secured  Determination of Graphite Contacts ©RWE
  • 34. KoCoS Presentation Advantages  Additional external measuring devices are not required.  No special measuring cables are necessary.  Connect directly to a device. The workload is therefore low.  No calibration or adjustment to the electrical conditions of the apparatus.  No triggering of external devices and the associated distortion of the switching times needed.  The measuring current may be permanently made ​available. A waiting time until the next circuit is not required.  A dynamic analysis is the recorded traces. This allows for precise analysis of contact systems with material transitions, such as Graphite-metal. ©RWE
  • 35. KoCoS Presentation Method used on any breaker
  • 36. KoCoS America n Breaker Analysis n Relay Testing n Digital Fault Recording Thank you for your interest. n Meter Testing n Power Quality Analysis n Optical Measurement www.kocos.com