SlideShare a Scribd company logo
1 of 4
Download to read offline
Elspec Power Quality Solutions	 www.elspec-ltd.com
1
In This Document
while the reactive power is
proportional to the second
power of the voltage (V²).
The Elspec Solution
Elspec Ride Through solution for
asynchronous Turbine is based
on Elspec Real Time Static
Var Compensation technology
which is used worldwide.
The Equalizer, a transient free
static compensation system,
was modified in order to boost
supplied kVAr capacity for short
time voltage dips applications.
The commercial name of
the new system is known as
Equalizer RT. The Equalizer RT system
is based on the following features:
•	 Transient-free connection of
capacitors
•	 Voltage Control operation mode –
optimized to fulfill the PO12.3 Grid
Code requirements.
•	 Ultra fast acquisition time - full
compensation within less than
10mSec
Spanish PO12.3 Grid Code
Compliance
The purpose of this code is to provide
a procedure to ensure the uniformity
of tests and simulations, the precision
of measurements, and the assessment
of the response of wind farms in the
event of voltage dips.
Case Study
Elspec Develops the World’s 1st Ride Through Compliant
SVC “kVAR Booster” solution: Equalizer RT
Lanternoso Site
Overview
Asynchronous generators, including
doubly-fed rotors, are widely used in
wind farms. During voltage drops, any
slight speed deviation of these rotors
consumes large amounts of reactive
energy. Due to the large demand
for reactive power during significant
voltage drops, FRT regulations have
been implemented in many modern
grid codes.
A typical voltage drop event is the
result of a short circuit on one of the
network branches. It takes at least
100-200 ms to isolate the faulty
substation, potentially deteriorating
the voltage stability. The majority
of modern grid standards require
reactive energy to be generated by
local networks during a fault.
The most reliable reactive energy
solutions are based on capacitor
banks, Static VAR Compensation
(SVC).  However, utilizing an SVC
as a ride-through solution has its
disadvantages.  The provided reactive
current is proportional to the voltage,
Measurement Techniques
The code requires that for all field
tests, all of the records of voltage and
current sampled for each phase must
be carried out at a sampling frequency
of 5 kHz minimum.
Note: T1-T4 are defined by the dip
threshold (IEC 61000—4-30).
Zone Classification
A, B, and C below are used to define
three zones during the voltage dip.
These zones are classified as a
function of the dip threshold and the
residual voltage. See figure 2.
•	 Zone A: all of the values of voltage
Uef (1/4) between T2 and T2 +
150 ms.
•	 Zone B: all of the values of voltage
Uef (1/4) between T2 + 150 ms
and T3.
Voltage Dip Classification
Read how the Elspec Equalizer RT test installation:
•	 Successfully provided dynamic ride through compensation for an asyn-
chronous 1.5 MS turbine
•	 Provided results that proved the Equalizer RT can be a solution for the
FRT Spanish PO 12.3 Grid Code requirements
Elspec Power Quality Solutions	 www.elspec-ltd.com2
•	 Zone C: all of the values of voltage
Uef (1/4) between T3 and the
lesser of the following values, T4
and T3 + 150ms
Methodology for Calculating Power
Power consumption is expressed
in normalized value (p.u.) to the
registered nominal power of the WTG
tested. Similarly, energy consumption
values are expressed in normalized
values of power by time unit in
milliseconds (ms p.u.)
The voltage and current levels
registered in the test, as well as data
obtained from simulations must be
included in the report form as per
Table 1.
The Elspec Test
The 1.5 MW turbine can be supplied
with an automatic power factor
correction system that makes it
compliant with even very demanding
grid codes; the turbine has ride-
through capacity for all normal faults.
Test Setup
The RTC and the Equalizer RT
containers were located in adjacent
to the Turbine. The RTC container
was connected to the medium voltage
(20kV) in order to simulate voltage
dips according to the Spanish Grid
Code PO12.3. Elspec Equalizer RT
system was connected at the turbine
transformer output (690V). Elspec
Equalizer RT container comprises
also 4 Elspec G4K BLACKBOX model
EG4420, advanced power analyzer in
order to carry out measurements in
the following network points:
•	 Grid input to the RTC container
system 20kV.
•	 RTC container system output to
the turbine: approximately 20%
of the medium voltage (during the
dips).
•	 Transformer output of the
turbine - 690V (measurements
of the turbines generator and the
Equalizer RT system).
•	 Equalizer RT system output
The measurements were carried out
continuously during the test period.
All network parameters were recorded
cycle by cycle at 1024 samples per
cycle for voltages and 256 samples per
cycle for currents. For more details,
please refer to the G4k catalog web
site www.elspec-ltd.com at products
and services.
*)The value is changed in proportion to the voltage
Energy and Power Registry
Low Power Conditions
magnitude
Test Description Low Power
Low Power Test (10% - 30% of
nominal)
The test comprises six tests as
follows:
Three sequential unbalanced tests
Three sequential balanced tests
The following table provides the
reactive current and energy values
which were required from the Equalizer
RT system in order to comply with
PO12.3. The values were confirmed
by qualified company for the PO12.3
test procedure, which was carried
out by the supplier Ride Through test
container.
Zone Reactive Current Reactive Energy
A Above 2000A Above 800kVAr
B Above 2000A Above 800kVAr
C 2000A to 3500A 800 to 3300kVAr (*)
(*)The value is changed in proportion to the voltage
magnitude
Low Power Measurements
Elspec Power Quality Solutions	 www.elspec-ltd.com3
Low Power Results
The effect of the Equalizer RT on the
Grid at low power mode of operation of
the turbine (<30%) is seen in Figure
4. It illustrates the consumption of
the reactive energy and the current
in MV at the connection point of the
turbine to the Grid. It also provides
the current waveform of the Equalizer
RT in Low Voltage.
Without Equalizer RT, the consumption
of reactive energy during Zone C
almost reached 3 MVAR. With the
Equalizer RT, it reduced to less than
500kVAR. In Zone A & B, the Equalizer
RT contributes substantial reactive
energy to the Grid (above 800kVAR).
High Power Test (more than 1300kW)
The test comprises the same set of
parameters as the Low Power Test.
Three sequential unbalanced tests
Three sequential balanced tests
Equalizer RT solution: With and Without
High Power Equalizer RT Measurements
(*)The value is changed in proportion to the voltage
magnitude
International
Elspec Ltd.
P.O. Box 3019
4 HaShoham St., Zone 23
Caesarea Industrial Park
38900, Israel
Tel: +972-4-6272-470
Fax: +972-4-6272-465
email: info@elspec-ltd.com
North America
Elspec North America, Inc.
500 West South Street
Freeport, IL 61032
USA
Tel: +1-815-266-4210
Fax: +1-815-266-8910
email: info@elspecna.com
Europe
Elspec Portugal Lda.
Zona Industrial 1a Fase
4900-231 Chafe
Viana do Castelo
Portugal
Tel: +315-258-351-920
Fax: +315-258-351-607
email: info@elspecportugal.com
This document contains Elspec proprietary material. The information contained in this document is believed to be reliable and accurate.
©2008 Elspec Ltd.
All rights reserved.
SMC-
The following table provides the
relative current values which were
required from the Equalizer RT
system in order to comply with the
PO12.3. The values were confirmed
by a qualified company for PO12.3
algorithm.
Zone Reactive Current Reactive Energy
A Above 3300A Above 1500kVAr
B Above 3300A Above 1500kVAr
C 3500A-5500A 1500-6500kVAr (*)
(*)The value is changed in proportion to the voltage
magnitude
High Power Results
The effect of the Equalizer RT on the
Grid at high power mode of operation
of the turbine (>1300kW) is seen in
Figure 6. It illustrates the consumption
of the reactive energy and the current
in MV at the connection point of the
turbine to the Grid. It also provides
the active power of the turbine.
Without the Equalizer RT, the
consumption of reactive energy during
Zone C almost reached 7 MVAR. With
the Equalizer RT, it reduced to almost
zero. In Zone A & B, the Equalizer
RT contributes substantial reactive
energy to the Grid (above 1500kVAR).
High Power Conditions
High Power Results

More Related Content

What's hot

Automatic power factor controller by microcontroller
Automatic power factor controller by microcontrollerAutomatic power factor controller by microcontroller
Automatic power factor controller by microcontrollerSanket Shitole
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportTheory to Practical
 
Automatic Power Factor Correction using Microcontroller 8051
Automatic Power Factor Correction using Microcontroller 8051Automatic Power Factor Correction using Microcontroller 8051
Automatic Power Factor Correction using Microcontroller 8051Neehar NLN
 
Automatic Power Factor Improvement.Pptx
Automatic Power Factor Improvement.PptxAutomatic Power Factor Improvement.Pptx
Automatic Power Factor Improvement.PptxSveris COE Pandharpur
 
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeed
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeedAnalyses of reactive power compensation schemes in MV/LV Networks with RE infeed
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeedAushiq Ali Memon
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation ControlBirju Besra
 
Contingency analysis
Contingency analysisContingency analysis
Contingency analysisSajan Sahu
 
Power point of automatic power factor controller
Power point of automatic power factor controllerPower point of automatic power factor controller
Power point of automatic power factor controllerSatyapal Singh
 
TCSC
TCSCTCSC
TCSCAli
 
Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...
Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...
Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...IRJET Journal
 
Automatic Power Factor Improvement by Using PLC & SCADA
Automatic Power Factor Improvement by Using PLC & SCADAAutomatic Power Factor Improvement by Using PLC & SCADA
Automatic Power Factor Improvement by Using PLC & SCADAferozpatowary
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERNitish NIT
 
Design of a 3-phase FC-TCR Static Var Compensator for Power factor correction...
Design of a 3-phase FC-TCR Static Var Compensator for Power factor correction...Design of a 3-phase FC-TCR Static Var Compensator for Power factor correction...
Design of a 3-phase FC-TCR Static Var Compensator for Power factor correction...Hardik Parikh, E.I.T.
 

What's hot (20)

Automatic power factor controller by microcontroller
Automatic power factor controller by microcontrollerAutomatic power factor controller by microcontroller
Automatic power factor controller by microcontroller
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System Report
 
Statcom
StatcomStatcom
Statcom
 
Automatic Power Factor Correction using Microcontroller 8051
Automatic Power Factor Correction using Microcontroller 8051Automatic Power Factor Correction using Microcontroller 8051
Automatic Power Factor Correction using Microcontroller 8051
 
Anees ppt on hcc
Anees ppt on hccAnees ppt on hcc
Anees ppt on hcc
 
Reactive power compensation using statcom
Reactive power compensation using statcomReactive power compensation using statcom
Reactive power compensation using statcom
 
Facts
FactsFacts
Facts
 
Automatic Power Factor Improvement.Pptx
Automatic Power Factor Improvement.PptxAutomatic Power Factor Improvement.Pptx
Automatic Power Factor Improvement.Pptx
 
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeed
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeedAnalyses of reactive power compensation schemes in MV/LV Networks with RE infeed
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeed
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation Control
 
Contingency analysis
Contingency analysisContingency analysis
Contingency analysis
 
Power point of automatic power factor controller
Power point of automatic power factor controllerPower point of automatic power factor controller
Power point of automatic power factor controller
 
FACTS Controller.
FACTS Controller.FACTS Controller.
FACTS Controller.
 
TCSC
TCSCTCSC
TCSC
 
Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...
Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...
Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...
 
Automatic Power Factor Improvement by Using PLC & SCADA
Automatic Power Factor Improvement by Using PLC & SCADAAutomatic Power Factor Improvement by Using PLC & SCADA
Automatic Power Factor Improvement by Using PLC & SCADA
 
STATCOM
STATCOMSTATCOM
STATCOM
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLER
 
Design of a 3-phase FC-TCR Static Var Compensator for Power factor correction...
Design of a 3-phase FC-TCR Static Var Compensator for Power factor correction...Design of a 3-phase FC-TCR Static Var Compensator for Power factor correction...
Design of a 3-phase FC-TCR Static Var Compensator for Power factor correction...
 

Similar to Elspec equalizer rt_datasheet

Enhancing Power Quality in Transmission System Using Fc-Tcr
Enhancing Power Quality in Transmission System Using Fc-TcrEnhancing Power Quality in Transmission System Using Fc-Tcr
Enhancing Power Quality in Transmission System Using Fc-TcrIJMER
 
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...ijiert bestjournal
 
Implementation of FC-TCR for Reactive Power Control
Implementation of FC-TCR for Reactive Power ControlImplementation of FC-TCR for Reactive Power Control
Implementation of FC-TCR for Reactive Power ControlIOSR Journals
 
Three Phase Digitally Controlled Power Factor Improvement System
Three Phase Digitally Controlled Power Factor Improvement SystemThree Phase Digitally Controlled Power Factor Improvement System
Three Phase Digitally Controlled Power Factor Improvement SystemIOSR Journals
 
ijre paper
ijre paperijre paper
ijre paperNithin S
 
Fuzzy Logic Controller Based High Frequency Link AC-AC Converter For Voltage ...
Fuzzy Logic Controller Based High Frequency Link AC-AC Converter For Voltage ...Fuzzy Logic Controller Based High Frequency Link AC-AC Converter For Voltage ...
Fuzzy Logic Controller Based High Frequency Link AC-AC Converter For Voltage ...IJTET Journal
 
Study On Speed Control of DC MOTOR Using Thyristor
Study On Speed Control of DC MOTOR Using ThyristorStudy On Speed Control of DC MOTOR Using Thyristor
Study On Speed Control of DC MOTOR Using ThyristorIRJET Journal
 
129 venezuelan static var compensator
129 venezuelan static var compensator129 venezuelan static var compensator
129 venezuelan static var compensatorwmelis
 
A Novel Single-Phase AC-AC Converter for Circuit Breaker Testing Appli...
A Novel Single-Phase AC-AC Converter for        Circuit Breaker Testing Appli...A Novel Single-Phase AC-AC Converter for        Circuit Breaker Testing Appli...
A Novel Single-Phase AC-AC Converter for Circuit Breaker Testing Appli...ANU143SRA
 
Analog and Digital Electronics Lab Manual
Analog and Digital Electronics Lab ManualAnalog and Digital Electronics Lab Manual
Analog and Digital Electronics Lab ManualChirag Shetty
 
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV System
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV SystemPower Angle Control Scheme for Integration of UPQC In Grid Connected PV System
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV SystemIRJET Journal
 
Enhancement of Power System Dynamics Using a Novel Series Compensation Scheme
Enhancement of Power System Dynamics Using a Novel Series Compensation SchemeEnhancement of Power System Dynamics Using a Novel Series Compensation Scheme
Enhancement of Power System Dynamics Using a Novel Series Compensation SchemeIJMER
 
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...IRJET Journal
 
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...IRJET Journal
 

Similar to Elspec equalizer rt_datasheet (20)

Enhancing Power Quality in Transmission System Using Fc-Tcr
Enhancing Power Quality in Transmission System Using Fc-TcrEnhancing Power Quality in Transmission System Using Fc-Tcr
Enhancing Power Quality in Transmission System Using Fc-Tcr
 
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
 
Implementation of FC-TCR for Reactive Power Control
Implementation of FC-TCR for Reactive Power ControlImplementation of FC-TCR for Reactive Power Control
Implementation of FC-TCR for Reactive Power Control
 
Three Phase Digitally Controlled Power Factor Improvement System
Three Phase Digitally Controlled Power Factor Improvement SystemThree Phase Digitally Controlled Power Factor Improvement System
Three Phase Digitally Controlled Power Factor Improvement System
 
ijre paper
ijre paperijre paper
ijre paper
 
A Novel Control Strategy for Compensation of Voltage Quality Problem in AC Dr...
A Novel Control Strategy for Compensation of Voltage Quality Problem in AC Dr...A Novel Control Strategy for Compensation of Voltage Quality Problem in AC Dr...
A Novel Control Strategy for Compensation of Voltage Quality Problem in AC Dr...
 
Fuzzy Logic Controller Based High Frequency Link AC-AC Converter For Voltage ...
Fuzzy Logic Controller Based High Frequency Link AC-AC Converter For Voltage ...Fuzzy Logic Controller Based High Frequency Link AC-AC Converter For Voltage ...
Fuzzy Logic Controller Based High Frequency Link AC-AC Converter For Voltage ...
 
Study On Speed Control of DC MOTOR Using Thyristor
Study On Speed Control of DC MOTOR Using ThyristorStudy On Speed Control of DC MOTOR Using Thyristor
Study On Speed Control of DC MOTOR Using Thyristor
 
Latex_Final_Bryan_F
Latex_Final_Bryan_FLatex_Final_Bryan_F
Latex_Final_Bryan_F
 
129 venezuelan static var compensator
129 venezuelan static var compensator129 venezuelan static var compensator
129 venezuelan static var compensator
 
“POWER FACTOR IMPROVEMENT BY SIMULATION AND IMPLEMENTATION OF FC-TCR”
“POWER FACTOR IMPROVEMENT BY SIMULATION AND IMPLEMENTATION OF FC-TCR”“POWER FACTOR IMPROVEMENT BY SIMULATION AND IMPLEMENTATION OF FC-TCR”
“POWER FACTOR IMPROVEMENT BY SIMULATION AND IMPLEMENTATION OF FC-TCR”
 
Performance Analysis of FC-TCR
Performance Analysis of FC-TCRPerformance Analysis of FC-TCR
Performance Analysis of FC-TCR
 
seminar.pptx
seminar.pptxseminar.pptx
seminar.pptx
 
Unit 3 FACTS Technology
Unit 3 FACTS TechnologyUnit 3 FACTS Technology
Unit 3 FACTS Technology
 
A Novel Single-Phase AC-AC Converter for Circuit Breaker Testing Appli...
A Novel Single-Phase AC-AC Converter for        Circuit Breaker Testing Appli...A Novel Single-Phase AC-AC Converter for        Circuit Breaker Testing Appli...
A Novel Single-Phase AC-AC Converter for Circuit Breaker Testing Appli...
 
Analog and Digital Electronics Lab Manual
Analog and Digital Electronics Lab ManualAnalog and Digital Electronics Lab Manual
Analog and Digital Electronics Lab Manual
 
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV System
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV SystemPower Angle Control Scheme for Integration of UPQC In Grid Connected PV System
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV System
 
Enhancement of Power System Dynamics Using a Novel Series Compensation Scheme
Enhancement of Power System Dynamics Using a Novel Series Compensation SchemeEnhancement of Power System Dynamics Using a Novel Series Compensation Scheme
Enhancement of Power System Dynamics Using a Novel Series Compensation Scheme
 
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
 
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
 

More from Angus Sankaran

Hioki 9272 10_clamp_on_sensor_datasheet
Hioki 9272 10_clamp_on_sensor_datasheetHioki 9272 10_clamp_on_sensor_datasheet
Hioki 9272 10_clamp_on_sensor_datasheetAngus Sankaran
 
Hioki 9650 clamp_on_sensor_datasheetâ 
Hioki 9650 clamp_on_sensor_datasheetâ Hioki 9650 clamp_on_sensor_datasheetâ 
Hioki 9650 clamp_on_sensor_datasheetâ Angus Sankaran
 
Hioki 9651 clamp_on_sensor_datasheet 
Hioki 9651 clamp_on_sensor_datasheet Hioki 9651 clamp_on_sensor_datasheet 
Hioki 9651 clamp_on_sensor_datasheet Angus Sankaran
 
Hioki 8860 memory_hi_corder_datasheet
Hioki 8860 memory_hi_corder_datasheetHioki 8860 memory_hi_corder_datasheet
Hioki 8860 memory_hi_corder_datasheetAngus Sankaran
 
Global energy innovation_dynapulse_3648_battery_restoration_conditioner_syste...
Global energy innovation_dynapulse_3648_battery_restoration_conditioner_syste...Global energy innovation_dynapulse_3648_battery_restoration_conditioner_syste...
Global energy innovation_dynapulse_3648_battery_restoration_conditioner_syste...Angus Sankaran
 
Flir i5 infrared_camera_datasheet
Flir i5 infrared_camera_datasheetFlir i5 infrared_camera_datasheet
Flir i5 infrared_camera_datasheetAngus Sankaran
 
Elspec g4420 blackbox_fixed_power_quality_analyzer_datasheet
Elspec g4420 blackbox_fixed_power_quality_analyzer_datasheetElspec g4420 blackbox_fixed_power_quality_analyzer_datasheet
Elspec g4420 blackbox_fixed_power_quality_analyzer_datasheetAngus Sankaran
 
Mirus solv harmonic_analysis_software_datasheet
Mirus solv harmonic_analysis_software_datasheetMirus solv harmonic_analysis_software_datasheet
Mirus solv harmonic_analysis_software_datasheetAngus Sankaran
 
Mirus onics harmonic_mitigating_power_center_datasheet
Mirus onics harmonic_mitigating_power_center_datasheetMirus onics harmonic_mitigating_power_center_datasheet
Mirus onics harmonic_mitigating_power_center_datasheetAngus Sankaran
 
Mirus lineator hp_harmonic_mitigation_filters_datasheet
Mirus lineator hp_harmonic_mitigation_filters_datasheetMirus lineator hp_harmonic_mitigation_filters_datasheet
Mirus lineator hp_harmonic_mitigation_filters_datasheetAngus Sankaran
 
Mirus harmony 3-e_isolation_transformers_and_auto_transformers_datasheet
Mirus harmony 3-e_isolation_transformers_and_auto_transformers_datasheetMirus harmony 3-e_isolation_transformers_and_auto_transformers_datasheet
Mirus harmony 3-e_isolation_transformers_and_auto_transformers_datasheetAngus Sankaran
 
Mirus lineator 1_q3_1-phase_to_quasi_3-phase_harmonic_filter_datasheet
Mirus lineator 1_q3_1-phase_to_quasi_3-phase_harmonic_filter_datasheetMirus lineator 1_q3_1-phase_to_quasi_3-phase_harmonic_filter_datasheet
Mirus lineator 1_q3_1-phase_to_quasi_3-phase_harmonic_filter_datasheetAngus Sankaran
 
Mirus harmony 2-e_isolation_transformers_and_auto_transformers_datasheet
Mirus harmony 2-e_isolation_transformers_and_auto_transformers_datasheetMirus harmony 2-e_isolation_transformers_and_auto_transformers_datasheet
Mirus harmony 2-e_isolation_transformers_and_auto_transformers_datasheetAngus Sankaran
 
Mirus drive 12_24_transformers_datasheet
Mirus drive 12_24_transformers_datasheetMirus drive 12_24_transformers_datasheet
Mirus drive 12_24_transformers_datasheetAngus Sankaran
 
Mirus drive tamers_transformers_datasheet
Mirus drive tamers_transformers_datasheetMirus drive tamers_transformers_datasheet
Mirus drive tamers_transformers_datasheetAngus Sankaran
 
Mirus 5 7-neutral_current_eliminator_datasheet
Mirus 5 7-neutral_current_eliminator_datasheetMirus 5 7-neutral_current_eliminator_datasheet
Mirus 5 7-neutral_current_eliminator_datasheetAngus Sankaran
 
Mirus drive 24_transformers_datasheet
Mirus drive 24_transformers_datasheetMirus drive 24_transformers_datasheet
Mirus drive 24_transformers_datasheetAngus Sankaran
 
Mirus 5 13-neutral_current_eliminator_datasheet
Mirus 5 13-neutral_current_eliminator_datasheetMirus 5 13-neutral_current_eliminator_datasheet
Mirus 5 13-neutral_current_eliminator_datasheetAngus Sankaran
 
Mirus genlink dissimiliar_pitch_neutral_limiter_datasheet
Mirus genlink dissimiliar_pitch_neutral_limiter_datasheetMirus genlink dissimiliar_pitch_neutral_limiter_datasheet
Mirus genlink dissimiliar_pitch_neutral_limiter_datasheetAngus Sankaran
 
Mirus drive 18_transformers_datasheet
Mirus drive 18_transformers_datasheetMirus drive 18_transformers_datasheet
Mirus drive 18_transformers_datasheetAngus Sankaran
 

More from Angus Sankaran (20)

Hioki 9272 10_clamp_on_sensor_datasheet
Hioki 9272 10_clamp_on_sensor_datasheetHioki 9272 10_clamp_on_sensor_datasheet
Hioki 9272 10_clamp_on_sensor_datasheet
 
Hioki 9650 clamp_on_sensor_datasheetâ 
Hioki 9650 clamp_on_sensor_datasheetâ Hioki 9650 clamp_on_sensor_datasheetâ 
Hioki 9650 clamp_on_sensor_datasheetâ 
 
Hioki 9651 clamp_on_sensor_datasheet 
Hioki 9651 clamp_on_sensor_datasheet Hioki 9651 clamp_on_sensor_datasheet 
Hioki 9651 clamp_on_sensor_datasheet 
 
Hioki 8860 memory_hi_corder_datasheet
Hioki 8860 memory_hi_corder_datasheetHioki 8860 memory_hi_corder_datasheet
Hioki 8860 memory_hi_corder_datasheet
 
Global energy innovation_dynapulse_3648_battery_restoration_conditioner_syste...
Global energy innovation_dynapulse_3648_battery_restoration_conditioner_syste...Global energy innovation_dynapulse_3648_battery_restoration_conditioner_syste...
Global energy innovation_dynapulse_3648_battery_restoration_conditioner_syste...
 
Flir i5 infrared_camera_datasheet
Flir i5 infrared_camera_datasheetFlir i5 infrared_camera_datasheet
Flir i5 infrared_camera_datasheet
 
Elspec g4420 blackbox_fixed_power_quality_analyzer_datasheet
Elspec g4420 blackbox_fixed_power_quality_analyzer_datasheetElspec g4420 blackbox_fixed_power_quality_analyzer_datasheet
Elspec g4420 blackbox_fixed_power_quality_analyzer_datasheet
 
Mirus solv harmonic_analysis_software_datasheet
Mirus solv harmonic_analysis_software_datasheetMirus solv harmonic_analysis_software_datasheet
Mirus solv harmonic_analysis_software_datasheet
 
Mirus onics harmonic_mitigating_power_center_datasheet
Mirus onics harmonic_mitigating_power_center_datasheetMirus onics harmonic_mitigating_power_center_datasheet
Mirus onics harmonic_mitigating_power_center_datasheet
 
Mirus lineator hp_harmonic_mitigation_filters_datasheet
Mirus lineator hp_harmonic_mitigation_filters_datasheetMirus lineator hp_harmonic_mitigation_filters_datasheet
Mirus lineator hp_harmonic_mitigation_filters_datasheet
 
Mirus harmony 3-e_isolation_transformers_and_auto_transformers_datasheet
Mirus harmony 3-e_isolation_transformers_and_auto_transformers_datasheetMirus harmony 3-e_isolation_transformers_and_auto_transformers_datasheet
Mirus harmony 3-e_isolation_transformers_and_auto_transformers_datasheet
 
Mirus lineator 1_q3_1-phase_to_quasi_3-phase_harmonic_filter_datasheet
Mirus lineator 1_q3_1-phase_to_quasi_3-phase_harmonic_filter_datasheetMirus lineator 1_q3_1-phase_to_quasi_3-phase_harmonic_filter_datasheet
Mirus lineator 1_q3_1-phase_to_quasi_3-phase_harmonic_filter_datasheet
 
Mirus harmony 2-e_isolation_transformers_and_auto_transformers_datasheet
Mirus harmony 2-e_isolation_transformers_and_auto_transformers_datasheetMirus harmony 2-e_isolation_transformers_and_auto_transformers_datasheet
Mirus harmony 2-e_isolation_transformers_and_auto_transformers_datasheet
 
Mirus drive 12_24_transformers_datasheet
Mirus drive 12_24_transformers_datasheetMirus drive 12_24_transformers_datasheet
Mirus drive 12_24_transformers_datasheet
 
Mirus drive tamers_transformers_datasheet
Mirus drive tamers_transformers_datasheetMirus drive tamers_transformers_datasheet
Mirus drive tamers_transformers_datasheet
 
Mirus 5 7-neutral_current_eliminator_datasheet
Mirus 5 7-neutral_current_eliminator_datasheetMirus 5 7-neutral_current_eliminator_datasheet
Mirus 5 7-neutral_current_eliminator_datasheet
 
Mirus drive 24_transformers_datasheet
Mirus drive 24_transformers_datasheetMirus drive 24_transformers_datasheet
Mirus drive 24_transformers_datasheet
 
Mirus 5 13-neutral_current_eliminator_datasheet
Mirus 5 13-neutral_current_eliminator_datasheetMirus 5 13-neutral_current_eliminator_datasheet
Mirus 5 13-neutral_current_eliminator_datasheet
 
Mirus genlink dissimiliar_pitch_neutral_limiter_datasheet
Mirus genlink dissimiliar_pitch_neutral_limiter_datasheetMirus genlink dissimiliar_pitch_neutral_limiter_datasheet
Mirus genlink dissimiliar_pitch_neutral_limiter_datasheet
 
Mirus drive 18_transformers_datasheet
Mirus drive 18_transformers_datasheetMirus drive 18_transformers_datasheet
Mirus drive 18_transformers_datasheet
 

Recently uploaded

VIP Call Girl Saharanpur Aashi 8250192130 Independent Escort Service Saharanpur
VIP Call Girl Saharanpur Aashi 8250192130 Independent Escort Service SaharanpurVIP Call Girl Saharanpur Aashi 8250192130 Independent Escort Service Saharanpur
VIP Call Girl Saharanpur Aashi 8250192130 Independent Escort Service SaharanpurSuhani Kapoor
 
(SANA) Call Girls Landewadi ( 7001035870 ) HI-Fi Pune Escorts Service
(SANA) Call Girls Landewadi ( 7001035870 ) HI-Fi Pune Escorts Service(SANA) Call Girls Landewadi ( 7001035870 ) HI-Fi Pune Escorts Service
(SANA) Call Girls Landewadi ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Call Girls Delhi {Rs-10000 Laxmi Nagar] 9711199012 Whats Up Number
Call Girls Delhi {Rs-10000 Laxmi Nagar] 9711199012 Whats Up NumberCall Girls Delhi {Rs-10000 Laxmi Nagar] 9711199012 Whats Up Number
Call Girls Delhi {Rs-10000 Laxmi Nagar] 9711199012 Whats Up NumberMs Riya
 
Kalyan callg Girls, { 07738631006 } || Call Girl In Kalyan Women Seeking Men ...
Kalyan callg Girls, { 07738631006 } || Call Girl In Kalyan Women Seeking Men ...Kalyan callg Girls, { 07738631006 } || Call Girl In Kalyan Women Seeking Men ...
Kalyan callg Girls, { 07738631006 } || Call Girl In Kalyan Women Seeking Men ...Pooja Nehwal
 
如何办理(NUS毕业证书)新加坡国立大学毕业证成绩单留信学历认证原版一比一
如何办理(NUS毕业证书)新加坡国立大学毕业证成绩单留信学历认证原版一比一如何办理(NUS毕业证书)新加坡国立大学毕业证成绩单留信学历认证原版一比一
如何办理(NUS毕业证书)新加坡国立大学毕业证成绩单留信学历认证原版一比一ga6c6bdl
 
(ANIKA) Wanwadi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(ANIKA) Wanwadi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(ANIKA) Wanwadi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(ANIKA) Wanwadi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Gaya Call Girls #9907093804 Contact Number Escorts Service Gaya
Gaya Call Girls #9907093804 Contact Number Escorts Service GayaGaya Call Girls #9907093804 Contact Number Escorts Service Gaya
Gaya Call Girls #9907093804 Contact Number Escorts Service Gayasrsj9000
 
Lucknow 💋 Call Girls Adil Nagar | ₹,9500 Pay Cash 8923113531 Free Home Delive...
Lucknow 💋 Call Girls Adil Nagar | ₹,9500 Pay Cash 8923113531 Free Home Delive...Lucknow 💋 Call Girls Adil Nagar | ₹,9500 Pay Cash 8923113531 Free Home Delive...
Lucknow 💋 Call Girls Adil Nagar | ₹,9500 Pay Cash 8923113531 Free Home Delive...anilsa9823
 
VIP Call Girls Kavuri Hills ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With ...
VIP Call Girls Kavuri Hills ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With ...VIP Call Girls Kavuri Hills ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With ...
VIP Call Girls Kavuri Hills ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With ...Suhani Kapoor
 
(PARI) Alandi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(PARI) Alandi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(PARI) Alandi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(PARI) Alandi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Russian Call Girls Kolkata Chhaya 🤌 8250192130 🚀 Vip Call Girls Kolkata
Russian Call Girls Kolkata Chhaya 🤌  8250192130 🚀 Vip Call Girls KolkataRussian Call Girls Kolkata Chhaya 🤌  8250192130 🚀 Vip Call Girls Kolkata
Russian Call Girls Kolkata Chhaya 🤌 8250192130 🚀 Vip Call Girls Kolkataanamikaraghav4
 
VVIP Pune Call Girls Warje (7001035870) Pune Escorts Nearby with Complete Sat...
VVIP Pune Call Girls Warje (7001035870) Pune Escorts Nearby with Complete Sat...VVIP Pune Call Girls Warje (7001035870) Pune Escorts Nearby with Complete Sat...
VVIP Pune Call Girls Warje (7001035870) Pune Escorts Nearby with Complete Sat...Call Girls in Nagpur High Profile
 
定制宾州州立大学毕业证(PSU毕业证) 成绩单留信学历认证原版一比一
定制宾州州立大学毕业证(PSU毕业证) 成绩单留信学历认证原版一比一定制宾州州立大学毕业证(PSU毕业证) 成绩单留信学历认证原版一比一
定制宾州州立大学毕业证(PSU毕业证) 成绩单留信学历认证原版一比一ga6c6bdl
 
Call Girls Service Kolkata Aishwarya 🤌 8250192130 🚀 Vip Call Girls Kolkata
Call Girls Service Kolkata Aishwarya 🤌  8250192130 🚀 Vip Call Girls KolkataCall Girls Service Kolkata Aishwarya 🤌  8250192130 🚀 Vip Call Girls Kolkata
Call Girls Service Kolkata Aishwarya 🤌 8250192130 🚀 Vip Call Girls Kolkataanamikaraghav4
 
Dubai Call Girls O528786472 Call Girls In Dubai Wisteria
Dubai Call Girls O528786472 Call Girls In Dubai WisteriaDubai Call Girls O528786472 Call Girls In Dubai Wisteria
Dubai Call Girls O528786472 Call Girls In Dubai WisteriaUnited Arab Emirates
 
Pallawi 9167673311 Call Girls in Thane , Independent Escort Service Thane
Pallawi 9167673311  Call Girls in Thane , Independent Escort Service ThanePallawi 9167673311  Call Girls in Thane , Independent Escort Service Thane
Pallawi 9167673311 Call Girls in Thane , Independent Escort Service ThanePooja Nehwal
 
Vip Noida Escorts 9873940964 Greater Noida Escorts Service
Vip Noida Escorts 9873940964 Greater Noida Escorts ServiceVip Noida Escorts 9873940964 Greater Noida Escorts Service
Vip Noida Escorts 9873940964 Greater Noida Escorts Serviceankitnayak356677
 
如何办理(Adelaide毕业证)阿德莱德大学毕业证成绩单Adelaide学历认证真实可查
如何办理(Adelaide毕业证)阿德莱德大学毕业证成绩单Adelaide学历认证真实可查如何办理(Adelaide毕业证)阿德莱德大学毕业证成绩单Adelaide学历认证真实可查
如何办理(Adelaide毕业证)阿德莱德大学毕业证成绩单Adelaide学历认证真实可查awo24iot
 

Recently uploaded (20)

Low rate Call girls in Delhi Justdial | 9953330565
Low rate Call girls in Delhi Justdial | 9953330565Low rate Call girls in Delhi Justdial | 9953330565
Low rate Call girls in Delhi Justdial | 9953330565
 
VIP Call Girl Saharanpur Aashi 8250192130 Independent Escort Service Saharanpur
VIP Call Girl Saharanpur Aashi 8250192130 Independent Escort Service SaharanpurVIP Call Girl Saharanpur Aashi 8250192130 Independent Escort Service Saharanpur
VIP Call Girl Saharanpur Aashi 8250192130 Independent Escort Service Saharanpur
 
(SANA) Call Girls Landewadi ( 7001035870 ) HI-Fi Pune Escorts Service
(SANA) Call Girls Landewadi ( 7001035870 ) HI-Fi Pune Escorts Service(SANA) Call Girls Landewadi ( 7001035870 ) HI-Fi Pune Escorts Service
(SANA) Call Girls Landewadi ( 7001035870 ) HI-Fi Pune Escorts Service
 
Call Girls Delhi {Rs-10000 Laxmi Nagar] 9711199012 Whats Up Number
Call Girls Delhi {Rs-10000 Laxmi Nagar] 9711199012 Whats Up NumberCall Girls Delhi {Rs-10000 Laxmi Nagar] 9711199012 Whats Up Number
Call Girls Delhi {Rs-10000 Laxmi Nagar] 9711199012 Whats Up Number
 
Kalyan callg Girls, { 07738631006 } || Call Girl In Kalyan Women Seeking Men ...
Kalyan callg Girls, { 07738631006 } || Call Girl In Kalyan Women Seeking Men ...Kalyan callg Girls, { 07738631006 } || Call Girl In Kalyan Women Seeking Men ...
Kalyan callg Girls, { 07738631006 } || Call Girl In Kalyan Women Seeking Men ...
 
如何办理(NUS毕业证书)新加坡国立大学毕业证成绩单留信学历认证原版一比一
如何办理(NUS毕业证书)新加坡国立大学毕业证成绩单留信学历认证原版一比一如何办理(NUS毕业证书)新加坡国立大学毕业证成绩单留信学历认证原版一比一
如何办理(NUS毕业证书)新加坡国立大学毕业证成绩单留信学历认证原版一比一
 
(ANIKA) Wanwadi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(ANIKA) Wanwadi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(ANIKA) Wanwadi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(ANIKA) Wanwadi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Gaya Call Girls #9907093804 Contact Number Escorts Service Gaya
Gaya Call Girls #9907093804 Contact Number Escorts Service GayaGaya Call Girls #9907093804 Contact Number Escorts Service Gaya
Gaya Call Girls #9907093804 Contact Number Escorts Service Gaya
 
Lucknow 💋 Call Girls Adil Nagar | ₹,9500 Pay Cash 8923113531 Free Home Delive...
Lucknow 💋 Call Girls Adil Nagar | ₹,9500 Pay Cash 8923113531 Free Home Delive...Lucknow 💋 Call Girls Adil Nagar | ₹,9500 Pay Cash 8923113531 Free Home Delive...
Lucknow 💋 Call Girls Adil Nagar | ₹,9500 Pay Cash 8923113531 Free Home Delive...
 
VIP Call Girls Kavuri Hills ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With ...
VIP Call Girls Kavuri Hills ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With ...VIP Call Girls Kavuri Hills ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With ...
VIP Call Girls Kavuri Hills ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With ...
 
(PARI) Alandi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(PARI) Alandi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(PARI) Alandi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(PARI) Alandi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Russian Call Girls Kolkata Chhaya 🤌 8250192130 🚀 Vip Call Girls Kolkata
Russian Call Girls Kolkata Chhaya 🤌  8250192130 🚀 Vip Call Girls KolkataRussian Call Girls Kolkata Chhaya 🤌  8250192130 🚀 Vip Call Girls Kolkata
Russian Call Girls Kolkata Chhaya 🤌 8250192130 🚀 Vip Call Girls Kolkata
 
VVIP Pune Call Girls Warje (7001035870) Pune Escorts Nearby with Complete Sat...
VVIP Pune Call Girls Warje (7001035870) Pune Escorts Nearby with Complete Sat...VVIP Pune Call Girls Warje (7001035870) Pune Escorts Nearby with Complete Sat...
VVIP Pune Call Girls Warje (7001035870) Pune Escorts Nearby with Complete Sat...
 
定制宾州州立大学毕业证(PSU毕业证) 成绩单留信学历认证原版一比一
定制宾州州立大学毕业证(PSU毕业证) 成绩单留信学历认证原版一比一定制宾州州立大学毕业证(PSU毕业证) 成绩单留信学历认证原版一比一
定制宾州州立大学毕业证(PSU毕业证) 成绩单留信学历认证原版一比一
 
Call Girls Service Kolkata Aishwarya 🤌 8250192130 🚀 Vip Call Girls Kolkata
Call Girls Service Kolkata Aishwarya 🤌  8250192130 🚀 Vip Call Girls KolkataCall Girls Service Kolkata Aishwarya 🤌  8250192130 🚀 Vip Call Girls Kolkata
Call Girls Service Kolkata Aishwarya 🤌 8250192130 🚀 Vip Call Girls Kolkata
 
Dubai Call Girls O528786472 Call Girls In Dubai Wisteria
Dubai Call Girls O528786472 Call Girls In Dubai WisteriaDubai Call Girls O528786472 Call Girls In Dubai Wisteria
Dubai Call Girls O528786472 Call Girls In Dubai Wisteria
 
Pallawi 9167673311 Call Girls in Thane , Independent Escort Service Thane
Pallawi 9167673311  Call Girls in Thane , Independent Escort Service ThanePallawi 9167673311  Call Girls in Thane , Independent Escort Service Thane
Pallawi 9167673311 Call Girls in Thane , Independent Escort Service Thane
 
9953330565 Low Rate Call Girls In Jahangirpuri Delhi NCR
9953330565 Low Rate Call Girls In Jahangirpuri  Delhi NCR9953330565 Low Rate Call Girls In Jahangirpuri  Delhi NCR
9953330565 Low Rate Call Girls In Jahangirpuri Delhi NCR
 
Vip Noida Escorts 9873940964 Greater Noida Escorts Service
Vip Noida Escorts 9873940964 Greater Noida Escorts ServiceVip Noida Escorts 9873940964 Greater Noida Escorts Service
Vip Noida Escorts 9873940964 Greater Noida Escorts Service
 
如何办理(Adelaide毕业证)阿德莱德大学毕业证成绩单Adelaide学历认证真实可查
如何办理(Adelaide毕业证)阿德莱德大学毕业证成绩单Adelaide学历认证真实可查如何办理(Adelaide毕业证)阿德莱德大学毕业证成绩单Adelaide学历认证真实可查
如何办理(Adelaide毕业证)阿德莱德大学毕业证成绩单Adelaide学历认证真实可查
 

Elspec equalizer rt_datasheet

  • 1. Elspec Power Quality Solutions www.elspec-ltd.com 1 In This Document while the reactive power is proportional to the second power of the voltage (V²). The Elspec Solution Elspec Ride Through solution for asynchronous Turbine is based on Elspec Real Time Static Var Compensation technology which is used worldwide. The Equalizer, a transient free static compensation system, was modified in order to boost supplied kVAr capacity for short time voltage dips applications. The commercial name of the new system is known as Equalizer RT. The Equalizer RT system is based on the following features: • Transient-free connection of capacitors • Voltage Control operation mode – optimized to fulfill the PO12.3 Grid Code requirements. • Ultra fast acquisition time - full compensation within less than 10mSec Spanish PO12.3 Grid Code Compliance The purpose of this code is to provide a procedure to ensure the uniformity of tests and simulations, the precision of measurements, and the assessment of the response of wind farms in the event of voltage dips. Case Study Elspec Develops the World’s 1st Ride Through Compliant SVC “kVAR Booster” solution: Equalizer RT Lanternoso Site Overview Asynchronous generators, including doubly-fed rotors, are widely used in wind farms. During voltage drops, any slight speed deviation of these rotors consumes large amounts of reactive energy. Due to the large demand for reactive power during significant voltage drops, FRT regulations have been implemented in many modern grid codes. A typical voltage drop event is the result of a short circuit on one of the network branches. It takes at least 100-200 ms to isolate the faulty substation, potentially deteriorating the voltage stability. The majority of modern grid standards require reactive energy to be generated by local networks during a fault. The most reliable reactive energy solutions are based on capacitor banks, Static VAR Compensation (SVC).  However, utilizing an SVC as a ride-through solution has its disadvantages.  The provided reactive current is proportional to the voltage, Measurement Techniques The code requires that for all field tests, all of the records of voltage and current sampled for each phase must be carried out at a sampling frequency of 5 kHz minimum. Note: T1-T4 are defined by the dip threshold (IEC 61000—4-30). Zone Classification A, B, and C below are used to define three zones during the voltage dip. These zones are classified as a function of the dip threshold and the residual voltage. See figure 2. • Zone A: all of the values of voltage Uef (1/4) between T2 and T2 + 150 ms. • Zone B: all of the values of voltage Uef (1/4) between T2 + 150 ms and T3. Voltage Dip Classification Read how the Elspec Equalizer RT test installation: • Successfully provided dynamic ride through compensation for an asyn- chronous 1.5 MS turbine • Provided results that proved the Equalizer RT can be a solution for the FRT Spanish PO 12.3 Grid Code requirements
  • 2. Elspec Power Quality Solutions www.elspec-ltd.com2 • Zone C: all of the values of voltage Uef (1/4) between T3 and the lesser of the following values, T4 and T3 + 150ms Methodology for Calculating Power Power consumption is expressed in normalized value (p.u.) to the registered nominal power of the WTG tested. Similarly, energy consumption values are expressed in normalized values of power by time unit in milliseconds (ms p.u.) The voltage and current levels registered in the test, as well as data obtained from simulations must be included in the report form as per Table 1. The Elspec Test The 1.5 MW turbine can be supplied with an automatic power factor correction system that makes it compliant with even very demanding grid codes; the turbine has ride- through capacity for all normal faults. Test Setup The RTC and the Equalizer RT containers were located in adjacent to the Turbine. The RTC container was connected to the medium voltage (20kV) in order to simulate voltage dips according to the Spanish Grid Code PO12.3. Elspec Equalizer RT system was connected at the turbine transformer output (690V). Elspec Equalizer RT container comprises also 4 Elspec G4K BLACKBOX model EG4420, advanced power analyzer in order to carry out measurements in the following network points: • Grid input to the RTC container system 20kV. • RTC container system output to the turbine: approximately 20% of the medium voltage (during the dips). • Transformer output of the turbine - 690V (measurements of the turbines generator and the Equalizer RT system). • Equalizer RT system output The measurements were carried out continuously during the test period. All network parameters were recorded cycle by cycle at 1024 samples per cycle for voltages and 256 samples per cycle for currents. For more details, please refer to the G4k catalog web site www.elspec-ltd.com at products and services. *)The value is changed in proportion to the voltage Energy and Power Registry Low Power Conditions magnitude Test Description Low Power Low Power Test (10% - 30% of nominal) The test comprises six tests as follows: Three sequential unbalanced tests Three sequential balanced tests The following table provides the reactive current and energy values which were required from the Equalizer RT system in order to comply with PO12.3. The values were confirmed by qualified company for the PO12.3 test procedure, which was carried out by the supplier Ride Through test container. Zone Reactive Current Reactive Energy A Above 2000A Above 800kVAr B Above 2000A Above 800kVAr C 2000A to 3500A 800 to 3300kVAr (*) (*)The value is changed in proportion to the voltage magnitude Low Power Measurements
  • 3. Elspec Power Quality Solutions www.elspec-ltd.com3 Low Power Results The effect of the Equalizer RT on the Grid at low power mode of operation of the turbine (<30%) is seen in Figure 4. It illustrates the consumption of the reactive energy and the current in MV at the connection point of the turbine to the Grid. It also provides the current waveform of the Equalizer RT in Low Voltage. Without Equalizer RT, the consumption of reactive energy during Zone C almost reached 3 MVAR. With the Equalizer RT, it reduced to less than 500kVAR. In Zone A & B, the Equalizer RT contributes substantial reactive energy to the Grid (above 800kVAR). High Power Test (more than 1300kW) The test comprises the same set of parameters as the Low Power Test. Three sequential unbalanced tests Three sequential balanced tests Equalizer RT solution: With and Without High Power Equalizer RT Measurements (*)The value is changed in proportion to the voltage magnitude
  • 4. International Elspec Ltd. P.O. Box 3019 4 HaShoham St., Zone 23 Caesarea Industrial Park 38900, Israel Tel: +972-4-6272-470 Fax: +972-4-6272-465 email: info@elspec-ltd.com North America Elspec North America, Inc. 500 West South Street Freeport, IL 61032 USA Tel: +1-815-266-4210 Fax: +1-815-266-8910 email: info@elspecna.com Europe Elspec Portugal Lda. Zona Industrial 1a Fase 4900-231 Chafe Viana do Castelo Portugal Tel: +315-258-351-920 Fax: +315-258-351-607 email: info@elspecportugal.com This document contains Elspec proprietary material. The information contained in this document is believed to be reliable and accurate. ©2008 Elspec Ltd. All rights reserved. SMC- The following table provides the relative current values which were required from the Equalizer RT system in order to comply with the PO12.3. The values were confirmed by a qualified company for PO12.3 algorithm. Zone Reactive Current Reactive Energy A Above 3300A Above 1500kVAr B Above 3300A Above 1500kVAr C 3500A-5500A 1500-6500kVAr (*) (*)The value is changed in proportion to the voltage magnitude High Power Results The effect of the Equalizer RT on the Grid at high power mode of operation of the turbine (>1300kW) is seen in Figure 6. It illustrates the consumption of the reactive energy and the current in MV at the connection point of the turbine to the Grid. It also provides the active power of the turbine. Without the Equalizer RT, the consumption of reactive energy during Zone C almost reached 7 MVAR. With the Equalizer RT, it reduced to almost zero. In Zone A & B, the Equalizer RT contributes substantial reactive energy to the Grid (above 1500kVAR). High Power Conditions High Power Results