A Study of SVC’s Impact Simulation and Analysis for
Distance Protection Relay on Transmission Lines
Ngo Minh Khoa*1
, Nguyen Huu Hieu2
, and Dinh Thanh Viet3
1
Quynhon University, Quynhon city, Vietnam
2,3
The University of Danang - University of Science and Technology, Danang city, Vietnam
Article Info
Article history:
Received: Feb 15, 2017
Revised: May 24, 2017
Accepted: Jun 9, 2017
Keyword:
Distance relay
Measured impedance
Matlab/Simulink
SVC
Power transmission line
ABSTRACT
This paper focuses on analyzing and evaluating impact of a Static Var Compensator (SVC)
on the measured impedance at distance protection relay location on power transmission
lines. The measured impedance at the relay location when a fault occurs on the line is
determined by using voltage and current signals from voltage and current transformers at
the relay and the type of fault occurred on the line. The MHO characteristic is applied to
analyze impact of SVC on the distance protection relay. Based on the theory, the authors
in this paper develop a simulation program on Matlab/Simulink software to analyze im-
pact of SVC on the distance protection relay. In the power system model, it is supposed
that the SVC is located at mid-point of the transmission line to study impact of SVC on
the distance relay. The simulation results show that SVC will impact on the measured
impedance at the relay when the fault occurs after the location of the SVC on the power
transmission line.
Copyright c 2017 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
Ngo Minh Khoa
Faculty of Engineering and Technology, Quynhon University
170 An Duong Vuong street, Quynhon city, Vietnam
Phone: +84 988 371 737
Email: ngominhkhoa@qnu.edu.vn
1. INTRODUCTION
Nowadays, Flexible Alternating Current Transmission System (FACTS) devices are applied to power sys-
tems in order to improve the transmission capacity of the lines, enhance the power system stability and provide the
optimum utilization of the system capability [1], [2]. The measured impedance at the relay location is the basis of
the distance protection operation. There are several factors affecting the measured impedance at the relay location
as presented in [1], [2]. Some of these factors are related to the power system parameters prior to the fault instance,
which can be categorized into two groups [3]-[5]. The first group is structural conditions, represented by the short
circuit levels at the transmission line ends, whereas the second group is the operational conditions, represented by
the line load angle and the voltage magnitude ratio at the line ends. However, with the presence of FACTS devices
such as SVC in particular, the conventional distance characteristics such as MHO and Quadrilateral are greatly
subjected to mal-operation in the form of over-reaching or under-reaching the fault point [6]-[8].
Generally three installation positions are considered for the SVC; at the near end bus, at the mid-point of
the line and at the remote end bus [9], [10]. In the case of ends buses, SVC is not present in the fault loop and
therefore not affecting the distance relay operation. When SVC is installed at the mid-point, if the fault locates
between the relaying point and the midpoint, the SVC is not present in the fault loop, otherwise SVC would be
included in the fault loop. When SVC is not present in the fault loop for zero fault resistance, the measured
impedance is equal to the actual impedance of the line section between the relay and fault locations. On the other
hand, when SVC is within the fault loop, even in the case of zero fault resistance, the measured impedance would
be deviated from its actual value. Therefore, the conventional distance relays are exposed to the mal-operation,
in the form of over-reaching or underreaching. In this case, the effect of SVC on the protective zones should be
considered accurately [9]-[11]. Thus, it is essential to study effects of FACTS devices on the protective systems,
Journal Homepage: http://iaesjournal.com/online/index.php/IJECE
Institute of Advanced Engineering and Science
w w w . i a e s j o u r n a l . c o m
, DOI: 10.11591/ijece.v7i4.pp1686-1695
IJECE ISSN: 2088-8708 1687
especially the distance protection, which is the main protective device at Extra High Voltage (EHV) level.
This paper presents the SVC impact analysis on the performance of distance protection relay on the power
transmission line using Matlab/Simulink software. At first a review of the effects of a SVC connected at the
midpoint of a transmission line on the performance of distance protection relays is presented. Followed by a
detailed simulation study for various types of faults applied on a transmission line protected by distance relay. The
rest of the paper is organized as follows. The MHO characteristic and SVC operation principle are explained in
Section 2. In Section 3, SVC impact analysis to the distance relay is presented in detail. The simulation results,
analysis and evaluation are also showed in this section. Finally, the conclusion of this paper is included in Section
4.
2. MHO CHARACTERISTICS AND SVC
2.1. MHO characteristics
MHO distance protection is based on an electrical measure of distance along a transmission line to a
fault. The distance along the transmission line is directly proportional to the series electrical impedance of the
transmission line (ZL) between busbar A and B as shown in Figure 1. The distance protection measures distance
to a fault by means of a measured voltage to measured current ratio computation [12]. The philosophy of setting
relay at Sonelgaz Group [2] is three forward zones (Z1, Z2 and Z3) for protection the line HV between busbar A
and B with total impedance ZAB.
Figure 1. Setting zones of distance protection relay
The setting zones for protected transmission line without shunt FACTS devices are expressed by [11]-[15].
Z1 = 0.8ZAB = 0.8 (RAB + jXAB)
Z2 = RAB + jXAB + 0.2 (RBC + jXBC)
Z3 = RAB + jXAB + 1.2 (RBC + jXBC)
(1)
where:
Z1, Z2 and Z3: The impedance of Zone 1, 2 and 3.
RAB, XAB: The resistance and reactance of the line AB.
RBC, XBC: The resistance and reactance of the line BC.
The total impedance (ZAB) of transmission line AB measured by the distance relay is given by:
Zmeas = KZZL =
KT U
KT I
ZL (2)
where:
KT U , KT I is the ratio of voltage and current transformers installed at the busbar A.
Zmeas is the measured impedance from the relay to the fault location.
ZL is the actual impedance of line from the relay to the fault location.
2.2. The measured impedance at relay
This section considers the making of a distance relay by calculating the apparent impedance and comparing
the result against some geometric shape. In this paper, we refer to this approach as the Z = V/I method. This
A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay... (Ngo Minh Khoa)
1688 ISSN: 2088-8708
method is appealing in that it only requires one impedance calculation per fault loop. Multiple zones (or geometric
shapes) only require more geometric tests of the result. These measured impedance equations are listed in Table 1.
Table 1. Apparent Impedance Equations [7]
Fault type
R
V R
I meas R R
Z V I
AG
a
V 0a
I KI  0a a
V I KI
BG
b
V 0b
I KI  0b b
V I KI
CG
c
V 0c
I KI  0c c
V I KI
AB/ABG
a b
V V a b
I I    a b a b
V V I I 
AC/ACG
a c
V V a c
I I    a c a c
V V I I 
BC/BCG
b c
V V b c
I I    b c b c
V V I I 
ABC/ABCG or ora b c
V V V or ora b c
I I I
or ora b c
a b c
V V V
I I I
where:
˙Ia, ˙Ib, ˙Ic: The current of phase A, B and C respectively.
˙Va, ˙Vb, ˙Vc: The voltage of phase A, B and C respectively.
˙I0 = ( ˙Ia + ˙Ib + ˙Ic)/3: The zero sequence current.
K = (z0 − z1)/z1. z0, z1: The zero-sequence and positive-sequence impedances of the line respectively.
2.3. Operation principle of SVC [6]
SVCs are devices that can quickly and reliably control line voltages. A SVC will typically regulate and
control the voltage to the required set point under normal steady state and contingency conditions and thereby
provide dynamic, fast response reactive power following system contingencies (e.g. network short circuits, line and
generator disconnections). In addition, a SVC can also increase transfer capability, reduce losses, mitigate active
power oscillations and prevent over-voltages at loss of load.
The SVC is customized to fit each customer with their specific needs. The SVC consists of a number of
fixed or switched branches, of which at least one branch includes thyristors, and the combination of branches can
be varied a lot depending on requirements. A SVC (Figure 2) typically includes a combination of at least two of the
given items below (e.g. TCR/FC or TCR/TSC/FC): thyristor controlled reactor (TCR), thyristor switched capacitor
(TSC), harmonic filter (FC) and Mechanically switched capacitor bank (MSC) or reactor bank (MSR) [6], [10].
Figure 2. Simple control diagram of SVC [6]
IJECE Vol. 7, No. 4, August 2017: 1686 – 1695
IJECE ISSN: 2088-8708 1689
2.4. Modeling of SVC
A typical terminal voltage versus output current of a static var compensator with a specific slope is shown
in Figure 3. In most of applications, the static var compensator is not used as a perfect terminal voltage regulation,
but rather the terminal voltage is allowed to vary in proportion with the compensating current. This regulation slope
is defined as [6].
Slope =
∆VC max
IC max
=
∆VL max
IL max
(3)
The regulation slope allows to extend the linear operating range of the compensator, to improve the stability
of the voltage regulation loop and to enforce automatic load sharing between static var compensator as well as other
voltage regulating devices.
Figure 3. V-I characteristic of SVC
The voltage at which the static compensator neither absorbs nor generates reactive power is the reference
voltage Vref shown in Figure 3. In practice, this reference voltage can be adjusted within the typical range of
10%. The slope of the characteristic represents a change in voltage with compensator current and, therefore, can be
considered as a slope reactance. The SVC response to the voltage variation is, then, determined from:
VT = Vref + XSLISV C (4)
Referring to Figure 3, the control range of a SVC is defined as follows [6]:
Imin < ISV C < Imax
Vmin < VSV C < Vmax
(5)
In this range, the SVC is represented as a PV-node (generator node) at an auxiliary bus with P = 0,
V = Vref . A reactance of (XSL) equivalent to the slope of the V-I characteristic is added between the auxiliary
node and the node of coupling to the system. The node at the point of common coupling is a PQ-node with P = 0,
Q = 0, shown in Figure 4.
When SVC operates outside the control range, it is represented as a shunt element with the susceptance
(jB) on the operating point (see Figure 4.b), B is defined as:
If V < Vmin : B =
1
XC
If V > Vmax : B = −
1
XL
(6)
where XC and XL are the reactances of the capacitor and reactor, respectively.
A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay... (Ngo Minh Khoa)
1690 ISSN: 2088-8708
Figure 4. Equivalent model of SVC
3. SVC’S IMPACT ANALYSIS TO DISTANCE RELAY
3.1. The studying power system model
Matlab is a high-performance language for technical computing. It integrates computation, visualization,
and programming in an easy-to-use environment where problems and solutions are expressed in familiar mathe-
matical notation. It is also applied in computing electrical engineering problems such as power quality analysis
[16]-[18], modeling protection relays in power systems [19]-[20], etc. Therefore, to test and analyze the impact
of SVC when a fault occurs on the power transmission line, the authors have developed a computer simulation
program using Matlab GUI shown in Figure 5 to simulate the operation of distance protection relays in the power
systems. In this model, the power system elements have the parameters as shown in Table 2.
Figure 5. Distance relay simulation model with SVC in Matlab
The transmission line in the model is protected by the distance relays at the ends of the line and the SVC
is located at the mid-point of the protected line. It is assumed that there are two fault locations which occur on
the line including F1 (before SVC’s location) and F2 (after SVC’s location). Depending on the type of fault, the
relay will determine the current and voltage signals from the current transformers and voltage transformers. Then,
the measured currents at relay are compared to the current thresholds to identify the fault type and the measured
impedance from the relay location to the fault location is also determined from the measured current and voltage.
Finally, the relay will determine the fault which zone of MHO characteristic the fault belongs to. The main display
functions on the graphical user interface are as follows:
+ A, B, C and G: The signals of fault type identification on the faulted phases A, B, C and G respectively.
+ Zone 1, Zone 2 and Zone 3: The signals of Zone 1, Zone 2 and Zone 3 respectively.
+ IA, IB, IC and I0: The measured current on the phase A, B, C and zero-sequence at the relay location
respectively.
+ UA, UB, UC and U0: The measured voltage on the phase A, B, C and zero-sequence at the relay location
respectively.
+ Z: the measured impedance at the relay location.
+ L: The fault location on the transmission line.
IJECE Vol. 7, No. 4, August 2017: 1686 – 1695
IJECE ISSN: 2088-8708 1691
Table 2. The Element Parameters
Element Parameters
Source    
 
50 Hz ; 220 kV
9000 MVA ; 1
LL
N
f V
S X R
 
 
Transmission line  
 
 
 
 
1
0
-9
1
-9
0
0.01273 0.2933 Ω km
0.3864 1.2963 Ω km
12.74.10 F km
7.751.10 F km
200 km
z j
z j
C
C
L
 
 



SVC  
   
220 kV
200 200 MVAR
LL
SVC
V
Q

  
+ MODEL: The button to open the three-phase system.
+ TEST: The button to run the program.
+ RECORDS: The button to record the simulation results.
+ RESET: The button to reset the program to the initial values.
3.2. Response of SVC for faults
Assuming an one-phase to ground fault occurs on the line, the parameters of the SVC is shown in Figure
6. In normal operation mode before fault (0-5s), the voltage on the SVC is the rated voltage value (1.0 pu) shown
in Figure 6(a). The value of the SVC substance is negative as shown in Figure 6(b), which shows the power system
with capacitive properties. The SVC consumes a small amount of reactive power from the system QSV C > 0
shown in Figure 6(c). When the fault occurs (at 5 seconds), the voltage of SVC rapidly decreases to zero shown
in Figure 6(a). The value of SVC substance increases to 1 p.u shown in Figure 6(b). However, since the terminal
voltage of SVC is decreased to zero, there is no reactive power of SVC generated or consumed shown in Figure
6(c).
0 1 2 3 4 5 6 7 8 9 10
−2
−1
0
1
2
a)
Time (s)
Vsvc
(p.u)
0 1 2 3 4 5 6 7 8 9 10
−2
−1
0
1
2
b)
Time (s)
Bsvc
(p.u)
0 1 2 3 4 5 6 7 8 9 10
−0.5
−0.25
0
0.25
0.5
c)
Time (s)
Qsvc
(p.u)
Figure 6. The SVC’s parameters for one-phase to ground fault at location 100 km on the transmission line
3.3. Measured impedance at relay with/without SVC
It is assumed that the fault types occurring at different locations on the transmission line are in turn sepa-
rated by a distance of 20 km from the relay location. Table 3 shows the simulation results of measured impedance
A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay... (Ngo Minh Khoa)
1692 ISSN: 2088-8708
at the relay location with and without SVC which is connected at mid-point of the line.
Table 3. Mesured Impedance for Fault Types
Fault
location
(km)
Actual
Impedance
Zact (Ω)
Measured impedance Zmeas (Ω)
Without SVC With SVC
LLLG LL LLG LG LLLG LL LLG LG
20 5.872 5.873 5.878 5.878 5.872 5.874 5.873 5.873 5.869
40 11.744 11.745 11.752 11.887 11.743 11.75 11.752 11.752 11.733
60 17.616 17.611 17.599 17.685 17.615 17.641 17.641 17.641 17.597
80 23.489 23.483 23.393 23.404 23.49 23.546 23.548 23.548 23.456
100 29.361 29.359 29.334 29.251 29.364 29.477 29.476 29.476 29.321
120 35.233 35.233 35.256 35.169 35.225 35.578 35.581 35.581 36.083
140 41.105 41.104 41.219 41.119 41.108 42.036 42.035 42.035 43.179
160 46.977 46.958 47.112 47.058 46.987 48.874 48.876 48.876 50.614
180 52.849 52.844 52.835 52.95 52.768 56.145 56.147 56.147 58.369
200 58.721 57.706 58.806 58.773 58.829 63.896 63.896 63.896 66.346
The results in Table 3 show that when a fault occurs at the particular location on the line with any types of
fault, the relay also determines the same measured impedance. Therefore, the fault location will be determined as
the same result. However, if a SVC is connected to mid-point of the line, the measured impedance at the relay will
have different results comparing to the without SVC case. This simulation result is shown in Figure 7. In Figure 7,
the trajectory of measured impedance at the relay when a one-phase to ground fault occurs at the location 120 km on
the line calculated from the relay location. The results show that if there is no SVC, the measured impedance point
will belong to Zone 2 of MHO characteristic, but if the SVC is connected to the mid-point of line, the measured
impedance at the relay location will belong to Zone 3.
−80 −60 −40 −20 0 20 40 60 80
0
20
40
60
80
100
120
140
Zone 3
Zone 2
Zone 1
← Line impedance
with SVC
without SVC
R (Ω)
jX(Ω)
Figure 7. Apparent impedance with SVC at mid-point of the line
In order to evaluate the error between the measured impedance at the relay location and the actual impedance
of the line calculated from the relay location to the fault location, this paper proposes an error which is given as
follows:
Error% =
Zmeas − Zact
Zact
100 (7)
The percentage error result of the measured impedance for all fault types which occur at the different
locations on the line in two cases including with and without SVC is shown in Figure 8. For all fault types, if the
location is before SVC location, the SVC will not affect the measured impedance at the relay. So the measured
impedance in both cases (without SVC and with SVC) is almost equal as shown in Figure 8 (from 0-100 km). If a
fault occurs after the SVC location, the measured impedance at the relay in both two cases is different. Specifically,
the measured impedance with SVC will be much larger than the measured impedance without SVC in the same
location as shown in Figure 8 (from 100 to 200 km). So when there is a fault occurring in the location before it has
errors SVC impedance measuring nearly 0 even when there is a fault occurring and farther behind SVC placement,
the level of total return measured error will be greater.
IJECE Vol. 7, No. 4, August 2017: 1686 – 1695
IJECE ISSN: 2088-8708 1693
20 40 60 80 100 120 140 160 180 200
−5
0
5
10
15
L (km)
Error(%)
a)
Without SVC
With SVC
20 40 60 80 100 120 140 160 180 200
−5
0
5
10
15
L (km)
Error(%)
b)
Without SVC
With SVC
20 40 60 80 100 120 140 160 180 200
−5
0
5
10
15
L (km)
Error(%)
c)
Without SVC
With SVC
20 40 60 80 100 120 140 160 180 200
−5
0
5
10
15
L (km)
Error(%)
d)
Without SVC
With SVC
Figure 8. Error of measured impedance at relay for fault types at different locations. a) Three-phase to ground fault,
b) Phase to phase fault, c) Two-phase to ground fault, d) Phase to ground fault
Fault resistances affect the measured impedance at the relay because they can make the voltage and current
at the relay different with the direct fault without resistance. So this paper also studied the impact of the fault
resistance on the distance relay as shown in Figure 9. Figure 9(a) shows the error of the measured impedance at the
relay when direct faults occur at different locations on the line. It clearly shows that the error depends on the fault
resistance and location. When SVC is connected to mid-point of the line, the error increases significantly for faults
occurring after the SVC location as shown in Figure 9(b).
40 80 120 160 200
0
10
20
30
40
50
−20
0
20
40
L (km)
a)
Rf
(Ω)
Error(%)
0
5
10
15
20
L (km)
Rf
(Ω)
c)
40 80 120 160 200
0
10
20
30
40
50
0
5
10
15
20
40 80 120 160 200
0
10
20
30
40
50
−20
0
20
40
L (km)
b)
Rf
(Ω)
Error(%)
0
10
20
30
L (km)
Rf
(Ω)
d)
40 80 120 160 200
0
10
20
30
40
50
0
10
20
30
Figure 9. Error of measured impedance at relay according to the fault resistances and locations. a-b) The 3D plots
of the error without and with SVC, c-d) The contour plots of the error without and with SVC
4. CONCLUSION
This paper studies the influence analysis of SVC to the measurement impedance determination of the
distance protection relay in the power system. The voltage and current measured at the relay location depend on the
faults’ location and type which occur on the transmission line. Then the measured impedance is determined from
these signals. MHO characteristic is used to determine the fault zone.
SVC is located at the mid-point of the power transmission line to analyze and evaluate in this paper. From
the simulation model built on Matlab/Simulink software, this paper has analysed and showed that the SVC will
A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay... (Ngo Minh Khoa)
1694 ISSN: 2088-8708
affect the measured impedance at distance protection relay if the fault occurs after SVC’s location. SVC can make
the position of the fault fall in the different zones other than the case of without SVC. This can make the trip signal
incorrectly and not guarantee the selective feature of the relay.
REFERENCES
[1] A. Kazemi, S. Jamali and H. Shateri, ”Measured Impedance by Distance Relay in Presence of SVC on Trans-
mission Line,” International Review of Electrical Engineering. 2006; 5: 2214-2219, 2006.
[2] Mohamed Zellagui and Abdelaiz Chaghi, ”Impact of SVC Devices on Distance Protection Settings Zones in
400kV Transmission Line,” UPB Scientific Bulletin, Series C: Electrical Engineering, Vol. 75, Iss. 2, pp. 249-
262, 2013.
[3] Azriyenni Azriyenni, Mohd Wazir Mustafa, ”Application of ANFIS for Distance Relay Protection in Trans-
mission Line,” International Journal of Electrical and Computer Engineering, Vol. 5, No. 6, pp. 1311-1318,
2015.
[4] A N Sarwade, P K Katti, J G Ghodekar, ”Reach and Operating Time Correction of Digital Distance Relay,”
International Journal of Electrical and Computer Engineering, Vol. 7, No. 1, pp. 58-67, 2017.
[5] Aejaz Ahmed K R, Mohd. Z. A. Ansari, Mohamed Jalaluddin, ”Simulation Analysis of a Power System Pro-
tection using Artificial Neural Network,” International Journal of Electrical and Computer Engineering, Vol.
3, No. 1, pp. 78-82, 2013.
[6] M. Noroozian, Modelling of SVC in Power System Studies, ABB Power Systems, 1996.
[7] Ahmed Kareem Lafta Al-Behadili, Performance Analysis of Distance Relay on Shunt/Series Facts-
Compensated Transmission Line, Master’s Theses, Western Michigan University, 2015.
[8] Carson W. Taylor, ”Static Var Compensator Models for Power Flow and Dynamic Performance Simulation,”
IEEE Trans. on Power Systems, Vol. 9, No. 1 , pp. 229-240, 1994.
[9] F.A. Albasri; T.S. Sidhu; R.K. Varma, ”Impact of Shunt-FACTS on Distance Protection of Transmission Lines,”
Power Systems Conf.: Adv. Metering, Protection, Control, Communication, and Distributed Resources, pp.
249-256, 2006.
[10] F.A. Albasri, T.S. Sidhu, R.K. Varma, ”Mitigation of Adverse Effects of Midpoint Shunt-FACTS Compensated
Transmission Lines on Distance Protection Schemes,” Power Engineering Society General Meeting, pp 1-8,
2007.
[11] Sabyasachi Behera; P. Raja; S. Moorthi, ”Modelling and simulation of the impact of SVC on existing distance
relay for transmission line protection,” 2015 International Conference on Condition Assessment Techniques in
Electrical Systems (CATCON), pp. 151-156, 2015.
[12] Xiao-Ping Zhang, Christian Rehtanz, Bikash Pal, Flexible AC Transmission Systems: Modelling and Control
(Power Systems), 2nd ed. 2012 Edition, Springer, 2012.
[13] Amir Ghorbania, Mojtaba Khederzadehb, Babak Mozafaria, ”Impact of SVC on the protection of transmission
lines,” International Journal of Electrical Power and Energy Systems, Vol. 42, Iss. 1, pp. 702-709, 2012.
[14] David G Philip; Arun Rajendran, ”Numerical conic distance relay,” 2015 International Conference on Inno-
vations in Information, Embedded and Communication Systems (ICIIECS), pp. 15, 2015
[15] David G Philip; Arun Rajendran, ”Development of a Multi-characteristic Distance Relay,” 2015 International
Conference on Technological Advancements in Power and Energy (TAP Energy), pp. 176 181, 2015.
[16] Dinh Thanh Viet, Nguyen Huu Hieu, Ngo Minh Khoa, ”A Method for Monitoring Voltage Disturbances
Based on Discrete Wavelet Transform and Adaptive Linear Neural Network,” International Review of Electrical
Engineering, Vol. 11, No. 3, pp. 314-322, 2016
[17] Dinh Thanh Viet, Nguyen Huu Hieu, Nguyen Le Hoa, Ngo Minh Khoa, ”A Control Strategy for Dynamic
Voltage Restorer,” Proceedings of The 11th IEEE International Conference on Power Electronics and Drive
Systems (PEDS 2015), 9 - 12, Sydney, Australia, June 2015.
[18] Ngo Minh Khoa, Dinh Thanh Viet, Nguyen Huu Hieu, ”Classification of Power Quality Disturbances Using
Wavelet Transform and K-Nearest Neighbor Classifier,” Proceedings of The 22nd IEEE International Sympo-
sium on Industrial Electronics (ISIE 2013), Taipei, Taiwan, May 2013.
[19] Li-Cheng Wu; Chih-Wen Liu; Ching-Shan Chen, ”Modeling and testing of a digital distance relay MAT-
LAB/SIMULINK,” Proceedings of The 37th Annual North American Power Symposium, pp. 253-259, 2005.
[20] Nur Hazwani Hussin; Muhd Hafizi Idris; Melaty Amirruddin; Mohd Saufi Ahmad; Mohd Alif Ismail; Farrah
Salwani Abdullah; Nurhakimah Mohd Mukhta, ”Modeling and simulation of inverse time overcurrent relay
using Matlab/Simulink,” Proceedings of 2016 IEEE International Conference on Automatic Control and Intel-
ligent Systems (I2CACIS), pp. 40-44, 2016.
IJECE Vol. 7, No. 4, August 2017: 1686 – 1695
IJECE ISSN: 2088-8708 1695
BIOGRAPHIES OF AUTHORS
Ngo Minh Khoa received the MS and PhD degrees in Electrical Engineering from The University
of Danang - University of Science and Technology, Danang City, Vietnam, in 2010 and 2017,
respectively. He is currently teaching at Quynhon University, Quynhon city, Vietnam. His research
interests include protection relay, power quality, and smart grid.
Nguyen Huu Hieu received PhD degree in Electrical Engineering from Joseph Fourier, Grenoble,
France in 2008. He is currently Dean of Electrical Engineering Department, The University of
Danang - University of Science and Technology, Danang city, Vietnam. His research interests
include power quality, optimization method, and power system design.
Dinh Thanh Viet received PhD degree in Electrical Engineering from Vinnitsya Technical State
University, Ukraine in 1997. Currently he is Associate Professor at Department of Electrical Engi-
neering, The University of Danang - University of Science and Technology, Danang city, Vietnam.
His research interests include power system analysis and control, power quality, transformer diag-
nosis, and deregulated market.
A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay... (Ngo Minh Khoa)

More Related Content

What's hot

COMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWERCOMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWERST Chowhury
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protectionRishi Tandon
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)J. FR
 
Distribution Transformer testing, West Bengal, India
Distribution Transformer testing,  West Bengal, IndiaDistribution Transformer testing,  West Bengal, India
Distribution Transformer testing, West Bengal, IndiaRajuMondal18
 
Ppt of 132kv gss sitapura jaipur
Ppt of 132kv gss sitapura jaipurPpt of 132kv gss sitapura jaipur
Ppt of 132kv gss sitapura jaipurkishankky
 
Summer internship at pgcil
Summer internship at pgcilSummer internship at pgcil
Summer internship at pgcilAnurag Savarn
 
Water indicator Circuit to measure the level of any liquid
Water indicator Circuit to measure the level of any liquidWater indicator Circuit to measure the level of any liquid
Water indicator Circuit to measure the level of any liquidBarani Tharan
 
substation 220 kv
substation 220 kv substation 220 kv
substation 220 kv student
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordinationmichaeljmack
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformerRitesh Verma
 
underground cable fault location using aruino,gsm&gps
underground cable fault location using aruino,gsm&gps underground cable fault location using aruino,gsm&gps
underground cable fault location using aruino,gsm&gps Mohd Sohail
 
Testing of Circuit Breakers.pptx
Testing of Circuit Breakers.pptxTesting of Circuit Breakers.pptx
Testing of Circuit Breakers.pptxTafhim Bin Nasir
 
Autotransformer and three phase transformer
Autotransformer and three phase transformerAutotransformer and three phase transformer
Autotransformer and three phase transformerRitu Rajan
 

What's hot (20)

LCL filter design for grid-connected single-phase flyback microinverter: a st...
LCL filter design for grid-connected single-phase flyback microinverter: a st...LCL filter design for grid-connected single-phase flyback microinverter: a st...
LCL filter design for grid-connected single-phase flyback microinverter: a st...
 
COMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWERCOMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWER
 
Bucholz relay
Bucholz relayBucholz relay
Bucholz relay
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protection
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 
Distribution Transformer testing, West Bengal, India
Distribution Transformer testing,  West Bengal, IndiaDistribution Transformer testing,  West Bengal, India
Distribution Transformer testing, West Bengal, India
 
Gss herapura report
Gss herapura reportGss herapura report
Gss herapura report
 
Ppt of 132kv gss sitapura jaipur
Ppt of 132kv gss sitapura jaipurPpt of 132kv gss sitapura jaipur
Ppt of 132kv gss sitapura jaipur
 
Summer internship at pgcil
Summer internship at pgcilSummer internship at pgcil
Summer internship at pgcil
 
Water indicator Circuit to measure the level of any liquid
Water indicator Circuit to measure the level of any liquidWater indicator Circuit to measure the level of any liquid
Water indicator Circuit to measure the level of any liquid
 
substation 220 kv
substation 220 kv substation 220 kv
substation 220 kv
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordination
 
Facts controller
Facts controllerFacts controller
Facts controller
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
 
underground cable fault location using aruino,gsm&gps
underground cable fault location using aruino,gsm&gps underground cable fault location using aruino,gsm&gps
underground cable fault location using aruino,gsm&gps
 
Testing of Circuit Breakers.pptx
Testing of Circuit Breakers.pptxTesting of Circuit Breakers.pptx
Testing of Circuit Breakers.pptx
 
Autotransformer and three phase transformer
Autotransformer and three phase transformerAutotransformer and three phase transformer
Autotransformer and three phase transformer
 
Fuse characteristics
Fuse characteristicsFuse characteristics
Fuse characteristics
 
1 phase semiconverter
1 phase semiconverter1 phase semiconverter
1 phase semiconverter
 

Similar to A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay on Transmission Lines

Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...IJAPEJOURNAL
 
Performance Analysis of the Distance Relay Characteristics in a Compensated T...
Performance Analysis of the Distance Relay Characteristics in a Compensated T...Performance Analysis of the Distance Relay Characteristics in a Compensated T...
Performance Analysis of the Distance Relay Characteristics in a Compensated T...MohammadMomani26
 
Circuit-based method for extracting the resistive leakage current of metal ox...
Circuit-based method for extracting the resistive leakage current of metal ox...Circuit-based method for extracting the resistive leakage current of metal ox...
Circuit-based method for extracting the resistive leakage current of metal ox...journalBEEI
 
Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...
Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...
Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...MohammadMomani26
 
Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
Impact Analysis of Midpoint Connected STATCOM on Distance Relay PerformanceImpact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
Impact Analysis of Midpoint Connected STATCOM on Distance Relay PerformanceRadita Apriana
 
Minimization of Power Loss in Distribution System using SVC and STATCOM
Minimization of Power Loss in Distribution System using SVC and STATCOMMinimization of Power Loss in Distribution System using SVC and STATCOM
Minimization of Power Loss in Distribution System using SVC and STATCOMIRJET Journal
 
The Impact of Line Resistance on the Performance of Controllable Series Compe...
The Impact of Line Resistance on the Performance of Controllable Series Compe...The Impact of Line Resistance on the Performance of Controllable Series Compe...
The Impact of Line Resistance on the Performance of Controllable Series Compe...Editor Jacotech
 
Consideration of Three Phase Faults on Transmission Line with Distance Protec...
Consideration of Three Phase Faults on Transmission Line with Distance Protec...Consideration of Three Phase Faults on Transmission Line with Distance Protec...
Consideration of Three Phase Faults on Transmission Line with Distance Protec...ijtsrd
 
Meet sarayni
Meet sarayniMeet sarayni
Meet saraynithavasik
 
Meet sarayni
Meet sarayniMeet sarayni
Meet saraynithavasik
 
Meet sarayni
Meet sarayniMeet sarayni
Meet saraynithavasik
 
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...Premier Publishers
 
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...IJERA Editor
 
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...IJERA Editor
 
Errors analysis in distance relay readings with presence of facts devices
Errors analysis in distance relay readings with presence of facts devicesErrors analysis in distance relay readings with presence of facts devices
Errors analysis in distance relay readings with presence of facts devicesAlexander Decker
 
Investigation of the Common Mode Voltage for a Neutral-Point-Clamped Multilev...
Investigation of the Common Mode Voltage for a Neutral-Point-Clamped Multilev...Investigation of the Common Mode Voltage for a Neutral-Point-Clamped Multilev...
Investigation of the Common Mode Voltage for a Neutral-Point-Clamped Multilev...IJPEDS-IAES
 
ENHANCEMENT OF ACTIVE POWER FLOW CAPACITY OF A TRANSMISSION LINE USING MSC‐TC...
ENHANCEMENT OF ACTIVE POWER FLOW CAPACITY OF A TRANSMISSION LINE USING MSC‐TC...ENHANCEMENT OF ACTIVE POWER FLOW CAPACITY OF A TRANSMISSION LINE USING MSC‐TC...
ENHANCEMENT OF ACTIVE POWER FLOW CAPACITY OF A TRANSMISSION LINE USING MSC‐TC...ijiert bestjournal
 

Similar to A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay on Transmission Lines (20)

Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
 
Performance Analysis of the Distance Relay Characteristics in a Compensated T...
Performance Analysis of the Distance Relay Characteristics in a Compensated T...Performance Analysis of the Distance Relay Characteristics in a Compensated T...
Performance Analysis of the Distance Relay Characteristics in a Compensated T...
 
Circuit-based method for extracting the resistive leakage current of metal ox...
Circuit-based method for extracting the resistive leakage current of metal ox...Circuit-based method for extracting the resistive leakage current of metal ox...
Circuit-based method for extracting the resistive leakage current of metal ox...
 
Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...
Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...
Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...
 
Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
Impact Analysis of Midpoint Connected STATCOM on Distance Relay PerformanceImpact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
 
Minimization of Power Loss in Distribution System using SVC and STATCOM
Minimization of Power Loss in Distribution System using SVC and STATCOMMinimization of Power Loss in Distribution System using SVC and STATCOM
Minimization of Power Loss in Distribution System using SVC and STATCOM
 
The Impact of Line Resistance on the Performance of Controllable Series Compe...
The Impact of Line Resistance on the Performance of Controllable Series Compe...The Impact of Line Resistance on the Performance of Controllable Series Compe...
The Impact of Line Resistance on the Performance of Controllable Series Compe...
 
Consideration of Three Phase Faults on Transmission Line with Distance Protec...
Consideration of Three Phase Faults on Transmission Line with Distance Protec...Consideration of Three Phase Faults on Transmission Line with Distance Protec...
Consideration of Three Phase Faults on Transmission Line with Distance Protec...
 
Meet sarayni
Meet sarayniMeet sarayni
Meet sarayni
 
Meet sarayni
Meet sarayniMeet sarayni
Meet sarayni
 
Meet sarayni
Meet sarayniMeet sarayni
Meet sarayni
 
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
 
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
 
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
 
Errors analysis in distance relay readings with presence of facts devices
Errors analysis in distance relay readings with presence of facts devicesErrors analysis in distance relay readings with presence of facts devices
Errors analysis in distance relay readings with presence of facts devices
 
Investigation of the Common Mode Voltage for a Neutral-Point-Clamped Multilev...
Investigation of the Common Mode Voltage for a Neutral-Point-Clamped Multilev...Investigation of the Common Mode Voltage for a Neutral-Point-Clamped Multilev...
Investigation of the Common Mode Voltage for a Neutral-Point-Clamped Multilev...
 
Dp35648654
Dp35648654Dp35648654
Dp35648654
 
ENHANCEMENT OF ACTIVE POWER FLOW CAPACITY OF A TRANSMISSION LINE USING MSC‐TC...
ENHANCEMENT OF ACTIVE POWER FLOW CAPACITY OF A TRANSMISSION LINE USING MSC‐TC...ENHANCEMENT OF ACTIVE POWER FLOW CAPACITY OF A TRANSMISSION LINE USING MSC‐TC...
ENHANCEMENT OF ACTIVE POWER FLOW CAPACITY OF A TRANSMISSION LINE USING MSC‐TC...
 
I41045662
I41045662I41045662
I41045662
 
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
 

More from IJECEIAES

Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...IJECEIAES
 
Prediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regressionPrediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regressionIJECEIAES
 
Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...IJECEIAES
 
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...IJECEIAES
 
Improving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learningImproving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learningIJECEIAES
 
Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...IJECEIAES
 
Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...IJECEIAES
 
Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...IJECEIAES
 
Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...IJECEIAES
 
A systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancyA systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancyIJECEIAES
 
Agriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimizationAgriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimizationIJECEIAES
 
Three layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performanceThree layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performanceIJECEIAES
 
Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...IJECEIAES
 
Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...IJECEIAES
 
Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...IJECEIAES
 
Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...IJECEIAES
 
On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...IJECEIAES
 
Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...IJECEIAES
 
A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...IJECEIAES
 
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...IJECEIAES
 

More from IJECEIAES (20)

Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...
 
Prediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regressionPrediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regression
 
Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...
 
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...
 
Improving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learningImproving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learning
 
Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...
 
Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...
 
Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...
 
Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...
 
A systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancyA systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancy
 
Agriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimizationAgriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimization
 
Three layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performanceThree layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performance
 
Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...
 
Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...
 
Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...
 
Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...
 
On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...
 
Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...
 
A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...
 
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
 

Recently uploaded

(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 

Recently uploaded (20)

(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 

A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay on Transmission Lines

  • 1. International Journal of Electrical and Computer Engineering (IJECE) Vol. 7, No. 4, August 2017, pp. 1686 – 1695 ISSN: 2088-8708 1686 Institute of Advanced Engineering and Science w w w . i a e s j o u r n a l . c o m A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay on Transmission Lines Ngo Minh Khoa*1 , Nguyen Huu Hieu2 , and Dinh Thanh Viet3 1 Quynhon University, Quynhon city, Vietnam 2,3 The University of Danang - University of Science and Technology, Danang city, Vietnam Article Info Article history: Received: Feb 15, 2017 Revised: May 24, 2017 Accepted: Jun 9, 2017 Keyword: Distance relay Measured impedance Matlab/Simulink SVC Power transmission line ABSTRACT This paper focuses on analyzing and evaluating impact of a Static Var Compensator (SVC) on the measured impedance at distance protection relay location on power transmission lines. The measured impedance at the relay location when a fault occurs on the line is determined by using voltage and current signals from voltage and current transformers at the relay and the type of fault occurred on the line. The MHO characteristic is applied to analyze impact of SVC on the distance protection relay. Based on the theory, the authors in this paper develop a simulation program on Matlab/Simulink software to analyze im- pact of SVC on the distance protection relay. In the power system model, it is supposed that the SVC is located at mid-point of the transmission line to study impact of SVC on the distance relay. The simulation results show that SVC will impact on the measured impedance at the relay when the fault occurs after the location of the SVC on the power transmission line. Copyright c 2017 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: Ngo Minh Khoa Faculty of Engineering and Technology, Quynhon University 170 An Duong Vuong street, Quynhon city, Vietnam Phone: +84 988 371 737 Email: ngominhkhoa@qnu.edu.vn 1. INTRODUCTION Nowadays, Flexible Alternating Current Transmission System (FACTS) devices are applied to power sys- tems in order to improve the transmission capacity of the lines, enhance the power system stability and provide the optimum utilization of the system capability [1], [2]. The measured impedance at the relay location is the basis of the distance protection operation. There are several factors affecting the measured impedance at the relay location as presented in [1], [2]. Some of these factors are related to the power system parameters prior to the fault instance, which can be categorized into two groups [3]-[5]. The first group is structural conditions, represented by the short circuit levels at the transmission line ends, whereas the second group is the operational conditions, represented by the line load angle and the voltage magnitude ratio at the line ends. However, with the presence of FACTS devices such as SVC in particular, the conventional distance characteristics such as MHO and Quadrilateral are greatly subjected to mal-operation in the form of over-reaching or under-reaching the fault point [6]-[8]. Generally three installation positions are considered for the SVC; at the near end bus, at the mid-point of the line and at the remote end bus [9], [10]. In the case of ends buses, SVC is not present in the fault loop and therefore not affecting the distance relay operation. When SVC is installed at the mid-point, if the fault locates between the relaying point and the midpoint, the SVC is not present in the fault loop, otherwise SVC would be included in the fault loop. When SVC is not present in the fault loop for zero fault resistance, the measured impedance is equal to the actual impedance of the line section between the relay and fault locations. On the other hand, when SVC is within the fault loop, even in the case of zero fault resistance, the measured impedance would be deviated from its actual value. Therefore, the conventional distance relays are exposed to the mal-operation, in the form of over-reaching or underreaching. In this case, the effect of SVC on the protective zones should be considered accurately [9]-[11]. Thus, it is essential to study effects of FACTS devices on the protective systems, Journal Homepage: http://iaesjournal.com/online/index.php/IJECE Institute of Advanced Engineering and Science w w w . i a e s j o u r n a l . c o m , DOI: 10.11591/ijece.v7i4.pp1686-1695
  • 2. IJECE ISSN: 2088-8708 1687 especially the distance protection, which is the main protective device at Extra High Voltage (EHV) level. This paper presents the SVC impact analysis on the performance of distance protection relay on the power transmission line using Matlab/Simulink software. At first a review of the effects of a SVC connected at the midpoint of a transmission line on the performance of distance protection relays is presented. Followed by a detailed simulation study for various types of faults applied on a transmission line protected by distance relay. The rest of the paper is organized as follows. The MHO characteristic and SVC operation principle are explained in Section 2. In Section 3, SVC impact analysis to the distance relay is presented in detail. The simulation results, analysis and evaluation are also showed in this section. Finally, the conclusion of this paper is included in Section 4. 2. MHO CHARACTERISTICS AND SVC 2.1. MHO characteristics MHO distance protection is based on an electrical measure of distance along a transmission line to a fault. The distance along the transmission line is directly proportional to the series electrical impedance of the transmission line (ZL) between busbar A and B as shown in Figure 1. The distance protection measures distance to a fault by means of a measured voltage to measured current ratio computation [12]. The philosophy of setting relay at Sonelgaz Group [2] is three forward zones (Z1, Z2 and Z3) for protection the line HV between busbar A and B with total impedance ZAB. Figure 1. Setting zones of distance protection relay The setting zones for protected transmission line without shunt FACTS devices are expressed by [11]-[15]. Z1 = 0.8ZAB = 0.8 (RAB + jXAB) Z2 = RAB + jXAB + 0.2 (RBC + jXBC) Z3 = RAB + jXAB + 1.2 (RBC + jXBC) (1) where: Z1, Z2 and Z3: The impedance of Zone 1, 2 and 3. RAB, XAB: The resistance and reactance of the line AB. RBC, XBC: The resistance and reactance of the line BC. The total impedance (ZAB) of transmission line AB measured by the distance relay is given by: Zmeas = KZZL = KT U KT I ZL (2) where: KT U , KT I is the ratio of voltage and current transformers installed at the busbar A. Zmeas is the measured impedance from the relay to the fault location. ZL is the actual impedance of line from the relay to the fault location. 2.2. The measured impedance at relay This section considers the making of a distance relay by calculating the apparent impedance and comparing the result against some geometric shape. In this paper, we refer to this approach as the Z = V/I method. This A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay... (Ngo Minh Khoa)
  • 3. 1688 ISSN: 2088-8708 method is appealing in that it only requires one impedance calculation per fault loop. Multiple zones (or geometric shapes) only require more geometric tests of the result. These measured impedance equations are listed in Table 1. Table 1. Apparent Impedance Equations [7] Fault type R V R I meas R R Z V I AG a V 0a I KI  0a a V I KI BG b V 0b I KI  0b b V I KI CG c V 0c I KI  0c c V I KI AB/ABG a b V V a b I I    a b a b V V I I  AC/ACG a c V V a c I I    a c a c V V I I  BC/BCG b c V V b c I I    b c b c V V I I  ABC/ABCG or ora b c V V V or ora b c I I I or ora b c a b c V V V I I I where: ˙Ia, ˙Ib, ˙Ic: The current of phase A, B and C respectively. ˙Va, ˙Vb, ˙Vc: The voltage of phase A, B and C respectively. ˙I0 = ( ˙Ia + ˙Ib + ˙Ic)/3: The zero sequence current. K = (z0 − z1)/z1. z0, z1: The zero-sequence and positive-sequence impedances of the line respectively. 2.3. Operation principle of SVC [6] SVCs are devices that can quickly and reliably control line voltages. A SVC will typically regulate and control the voltage to the required set point under normal steady state and contingency conditions and thereby provide dynamic, fast response reactive power following system contingencies (e.g. network short circuits, line and generator disconnections). In addition, a SVC can also increase transfer capability, reduce losses, mitigate active power oscillations and prevent over-voltages at loss of load. The SVC is customized to fit each customer with their specific needs. The SVC consists of a number of fixed or switched branches, of which at least one branch includes thyristors, and the combination of branches can be varied a lot depending on requirements. A SVC (Figure 2) typically includes a combination of at least two of the given items below (e.g. TCR/FC or TCR/TSC/FC): thyristor controlled reactor (TCR), thyristor switched capacitor (TSC), harmonic filter (FC) and Mechanically switched capacitor bank (MSC) or reactor bank (MSR) [6], [10]. Figure 2. Simple control diagram of SVC [6] IJECE Vol. 7, No. 4, August 2017: 1686 – 1695
  • 4. IJECE ISSN: 2088-8708 1689 2.4. Modeling of SVC A typical terminal voltage versus output current of a static var compensator with a specific slope is shown in Figure 3. In most of applications, the static var compensator is not used as a perfect terminal voltage regulation, but rather the terminal voltage is allowed to vary in proportion with the compensating current. This regulation slope is defined as [6]. Slope = ∆VC max IC max = ∆VL max IL max (3) The regulation slope allows to extend the linear operating range of the compensator, to improve the stability of the voltage regulation loop and to enforce automatic load sharing between static var compensator as well as other voltage regulating devices. Figure 3. V-I characteristic of SVC The voltage at which the static compensator neither absorbs nor generates reactive power is the reference voltage Vref shown in Figure 3. In practice, this reference voltage can be adjusted within the typical range of 10%. The slope of the characteristic represents a change in voltage with compensator current and, therefore, can be considered as a slope reactance. The SVC response to the voltage variation is, then, determined from: VT = Vref + XSLISV C (4) Referring to Figure 3, the control range of a SVC is defined as follows [6]: Imin < ISV C < Imax Vmin < VSV C < Vmax (5) In this range, the SVC is represented as a PV-node (generator node) at an auxiliary bus with P = 0, V = Vref . A reactance of (XSL) equivalent to the slope of the V-I characteristic is added between the auxiliary node and the node of coupling to the system. The node at the point of common coupling is a PQ-node with P = 0, Q = 0, shown in Figure 4. When SVC operates outside the control range, it is represented as a shunt element with the susceptance (jB) on the operating point (see Figure 4.b), B is defined as: If V < Vmin : B = 1 XC If V > Vmax : B = − 1 XL (6) where XC and XL are the reactances of the capacitor and reactor, respectively. A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay... (Ngo Minh Khoa)
  • 5. 1690 ISSN: 2088-8708 Figure 4. Equivalent model of SVC 3. SVC’S IMPACT ANALYSIS TO DISTANCE RELAY 3.1. The studying power system model Matlab is a high-performance language for technical computing. It integrates computation, visualization, and programming in an easy-to-use environment where problems and solutions are expressed in familiar mathe- matical notation. It is also applied in computing electrical engineering problems such as power quality analysis [16]-[18], modeling protection relays in power systems [19]-[20], etc. Therefore, to test and analyze the impact of SVC when a fault occurs on the power transmission line, the authors have developed a computer simulation program using Matlab GUI shown in Figure 5 to simulate the operation of distance protection relays in the power systems. In this model, the power system elements have the parameters as shown in Table 2. Figure 5. Distance relay simulation model with SVC in Matlab The transmission line in the model is protected by the distance relays at the ends of the line and the SVC is located at the mid-point of the protected line. It is assumed that there are two fault locations which occur on the line including F1 (before SVC’s location) and F2 (after SVC’s location). Depending on the type of fault, the relay will determine the current and voltage signals from the current transformers and voltage transformers. Then, the measured currents at relay are compared to the current thresholds to identify the fault type and the measured impedance from the relay location to the fault location is also determined from the measured current and voltage. Finally, the relay will determine the fault which zone of MHO characteristic the fault belongs to. The main display functions on the graphical user interface are as follows: + A, B, C and G: The signals of fault type identification on the faulted phases A, B, C and G respectively. + Zone 1, Zone 2 and Zone 3: The signals of Zone 1, Zone 2 and Zone 3 respectively. + IA, IB, IC and I0: The measured current on the phase A, B, C and zero-sequence at the relay location respectively. + UA, UB, UC and U0: The measured voltage on the phase A, B, C and zero-sequence at the relay location respectively. + Z: the measured impedance at the relay location. + L: The fault location on the transmission line. IJECE Vol. 7, No. 4, August 2017: 1686 – 1695
  • 6. IJECE ISSN: 2088-8708 1691 Table 2. The Element Parameters Element Parameters Source       50 Hz ; 220 kV 9000 MVA ; 1 LL N f V S X R     Transmission line           1 0 -9 1 -9 0 0.01273 0.2933 Ω km 0.3864 1.2963 Ω km 12.74.10 F km 7.751.10 F km 200 km z j z j C C L        SVC       220 kV 200 200 MVAR LL SVC V Q     + MODEL: The button to open the three-phase system. + TEST: The button to run the program. + RECORDS: The button to record the simulation results. + RESET: The button to reset the program to the initial values. 3.2. Response of SVC for faults Assuming an one-phase to ground fault occurs on the line, the parameters of the SVC is shown in Figure 6. In normal operation mode before fault (0-5s), the voltage on the SVC is the rated voltage value (1.0 pu) shown in Figure 6(a). The value of the SVC substance is negative as shown in Figure 6(b), which shows the power system with capacitive properties. The SVC consumes a small amount of reactive power from the system QSV C > 0 shown in Figure 6(c). When the fault occurs (at 5 seconds), the voltage of SVC rapidly decreases to zero shown in Figure 6(a). The value of SVC substance increases to 1 p.u shown in Figure 6(b). However, since the terminal voltage of SVC is decreased to zero, there is no reactive power of SVC generated or consumed shown in Figure 6(c). 0 1 2 3 4 5 6 7 8 9 10 −2 −1 0 1 2 a) Time (s) Vsvc (p.u) 0 1 2 3 4 5 6 7 8 9 10 −2 −1 0 1 2 b) Time (s) Bsvc (p.u) 0 1 2 3 4 5 6 7 8 9 10 −0.5 −0.25 0 0.25 0.5 c) Time (s) Qsvc (p.u) Figure 6. The SVC’s parameters for one-phase to ground fault at location 100 km on the transmission line 3.3. Measured impedance at relay with/without SVC It is assumed that the fault types occurring at different locations on the transmission line are in turn sepa- rated by a distance of 20 km from the relay location. Table 3 shows the simulation results of measured impedance A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay... (Ngo Minh Khoa)
  • 7. 1692 ISSN: 2088-8708 at the relay location with and without SVC which is connected at mid-point of the line. Table 3. Mesured Impedance for Fault Types Fault location (km) Actual Impedance Zact (Ω) Measured impedance Zmeas (Ω) Without SVC With SVC LLLG LL LLG LG LLLG LL LLG LG 20 5.872 5.873 5.878 5.878 5.872 5.874 5.873 5.873 5.869 40 11.744 11.745 11.752 11.887 11.743 11.75 11.752 11.752 11.733 60 17.616 17.611 17.599 17.685 17.615 17.641 17.641 17.641 17.597 80 23.489 23.483 23.393 23.404 23.49 23.546 23.548 23.548 23.456 100 29.361 29.359 29.334 29.251 29.364 29.477 29.476 29.476 29.321 120 35.233 35.233 35.256 35.169 35.225 35.578 35.581 35.581 36.083 140 41.105 41.104 41.219 41.119 41.108 42.036 42.035 42.035 43.179 160 46.977 46.958 47.112 47.058 46.987 48.874 48.876 48.876 50.614 180 52.849 52.844 52.835 52.95 52.768 56.145 56.147 56.147 58.369 200 58.721 57.706 58.806 58.773 58.829 63.896 63.896 63.896 66.346 The results in Table 3 show that when a fault occurs at the particular location on the line with any types of fault, the relay also determines the same measured impedance. Therefore, the fault location will be determined as the same result. However, if a SVC is connected to mid-point of the line, the measured impedance at the relay will have different results comparing to the without SVC case. This simulation result is shown in Figure 7. In Figure 7, the trajectory of measured impedance at the relay when a one-phase to ground fault occurs at the location 120 km on the line calculated from the relay location. The results show that if there is no SVC, the measured impedance point will belong to Zone 2 of MHO characteristic, but if the SVC is connected to the mid-point of line, the measured impedance at the relay location will belong to Zone 3. −80 −60 −40 −20 0 20 40 60 80 0 20 40 60 80 100 120 140 Zone 3 Zone 2 Zone 1 ← Line impedance with SVC without SVC R (Ω) jX(Ω) Figure 7. Apparent impedance with SVC at mid-point of the line In order to evaluate the error between the measured impedance at the relay location and the actual impedance of the line calculated from the relay location to the fault location, this paper proposes an error which is given as follows: Error% = Zmeas − Zact Zact 100 (7) The percentage error result of the measured impedance for all fault types which occur at the different locations on the line in two cases including with and without SVC is shown in Figure 8. For all fault types, if the location is before SVC location, the SVC will not affect the measured impedance at the relay. So the measured impedance in both cases (without SVC and with SVC) is almost equal as shown in Figure 8 (from 0-100 km). If a fault occurs after the SVC location, the measured impedance at the relay in both two cases is different. Specifically, the measured impedance with SVC will be much larger than the measured impedance without SVC in the same location as shown in Figure 8 (from 100 to 200 km). So when there is a fault occurring in the location before it has errors SVC impedance measuring nearly 0 even when there is a fault occurring and farther behind SVC placement, the level of total return measured error will be greater. IJECE Vol. 7, No. 4, August 2017: 1686 – 1695
  • 8. IJECE ISSN: 2088-8708 1693 20 40 60 80 100 120 140 160 180 200 −5 0 5 10 15 L (km) Error(%) a) Without SVC With SVC 20 40 60 80 100 120 140 160 180 200 −5 0 5 10 15 L (km) Error(%) b) Without SVC With SVC 20 40 60 80 100 120 140 160 180 200 −5 0 5 10 15 L (km) Error(%) c) Without SVC With SVC 20 40 60 80 100 120 140 160 180 200 −5 0 5 10 15 L (km) Error(%) d) Without SVC With SVC Figure 8. Error of measured impedance at relay for fault types at different locations. a) Three-phase to ground fault, b) Phase to phase fault, c) Two-phase to ground fault, d) Phase to ground fault Fault resistances affect the measured impedance at the relay because they can make the voltage and current at the relay different with the direct fault without resistance. So this paper also studied the impact of the fault resistance on the distance relay as shown in Figure 9. Figure 9(a) shows the error of the measured impedance at the relay when direct faults occur at different locations on the line. It clearly shows that the error depends on the fault resistance and location. When SVC is connected to mid-point of the line, the error increases significantly for faults occurring after the SVC location as shown in Figure 9(b). 40 80 120 160 200 0 10 20 30 40 50 −20 0 20 40 L (km) a) Rf (Ω) Error(%) 0 5 10 15 20 L (km) Rf (Ω) c) 40 80 120 160 200 0 10 20 30 40 50 0 5 10 15 20 40 80 120 160 200 0 10 20 30 40 50 −20 0 20 40 L (km) b) Rf (Ω) Error(%) 0 10 20 30 L (km) Rf (Ω) d) 40 80 120 160 200 0 10 20 30 40 50 0 10 20 30 Figure 9. Error of measured impedance at relay according to the fault resistances and locations. a-b) The 3D plots of the error without and with SVC, c-d) The contour plots of the error without and with SVC 4. CONCLUSION This paper studies the influence analysis of SVC to the measurement impedance determination of the distance protection relay in the power system. The voltage and current measured at the relay location depend on the faults’ location and type which occur on the transmission line. Then the measured impedance is determined from these signals. MHO characteristic is used to determine the fault zone. SVC is located at the mid-point of the power transmission line to analyze and evaluate in this paper. From the simulation model built on Matlab/Simulink software, this paper has analysed and showed that the SVC will A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay... (Ngo Minh Khoa)
  • 9. 1694 ISSN: 2088-8708 affect the measured impedance at distance protection relay if the fault occurs after SVC’s location. SVC can make the position of the fault fall in the different zones other than the case of without SVC. This can make the trip signal incorrectly and not guarantee the selective feature of the relay. REFERENCES [1] A. Kazemi, S. Jamali and H. Shateri, ”Measured Impedance by Distance Relay in Presence of SVC on Trans- mission Line,” International Review of Electrical Engineering. 2006; 5: 2214-2219, 2006. [2] Mohamed Zellagui and Abdelaiz Chaghi, ”Impact of SVC Devices on Distance Protection Settings Zones in 400kV Transmission Line,” UPB Scientific Bulletin, Series C: Electrical Engineering, Vol. 75, Iss. 2, pp. 249- 262, 2013. [3] Azriyenni Azriyenni, Mohd Wazir Mustafa, ”Application of ANFIS for Distance Relay Protection in Trans- mission Line,” International Journal of Electrical and Computer Engineering, Vol. 5, No. 6, pp. 1311-1318, 2015. [4] A N Sarwade, P K Katti, J G Ghodekar, ”Reach and Operating Time Correction of Digital Distance Relay,” International Journal of Electrical and Computer Engineering, Vol. 7, No. 1, pp. 58-67, 2017. [5] Aejaz Ahmed K R, Mohd. Z. A. Ansari, Mohamed Jalaluddin, ”Simulation Analysis of a Power System Pro- tection using Artificial Neural Network,” International Journal of Electrical and Computer Engineering, Vol. 3, No. 1, pp. 78-82, 2013. [6] M. Noroozian, Modelling of SVC in Power System Studies, ABB Power Systems, 1996. [7] Ahmed Kareem Lafta Al-Behadili, Performance Analysis of Distance Relay on Shunt/Series Facts- Compensated Transmission Line, Master’s Theses, Western Michigan University, 2015. [8] Carson W. Taylor, ”Static Var Compensator Models for Power Flow and Dynamic Performance Simulation,” IEEE Trans. on Power Systems, Vol. 9, No. 1 , pp. 229-240, 1994. [9] F.A. Albasri; T.S. Sidhu; R.K. Varma, ”Impact of Shunt-FACTS on Distance Protection of Transmission Lines,” Power Systems Conf.: Adv. Metering, Protection, Control, Communication, and Distributed Resources, pp. 249-256, 2006. [10] F.A. Albasri, T.S. Sidhu, R.K. Varma, ”Mitigation of Adverse Effects of Midpoint Shunt-FACTS Compensated Transmission Lines on Distance Protection Schemes,” Power Engineering Society General Meeting, pp 1-8, 2007. [11] Sabyasachi Behera; P. Raja; S. Moorthi, ”Modelling and simulation of the impact of SVC on existing distance relay for transmission line protection,” 2015 International Conference on Condition Assessment Techniques in Electrical Systems (CATCON), pp. 151-156, 2015. [12] Xiao-Ping Zhang, Christian Rehtanz, Bikash Pal, Flexible AC Transmission Systems: Modelling and Control (Power Systems), 2nd ed. 2012 Edition, Springer, 2012. [13] Amir Ghorbania, Mojtaba Khederzadehb, Babak Mozafaria, ”Impact of SVC on the protection of transmission lines,” International Journal of Electrical Power and Energy Systems, Vol. 42, Iss. 1, pp. 702-709, 2012. [14] David G Philip; Arun Rajendran, ”Numerical conic distance relay,” 2015 International Conference on Inno- vations in Information, Embedded and Communication Systems (ICIIECS), pp. 15, 2015 [15] David G Philip; Arun Rajendran, ”Development of a Multi-characteristic Distance Relay,” 2015 International Conference on Technological Advancements in Power and Energy (TAP Energy), pp. 176 181, 2015. [16] Dinh Thanh Viet, Nguyen Huu Hieu, Ngo Minh Khoa, ”A Method for Monitoring Voltage Disturbances Based on Discrete Wavelet Transform and Adaptive Linear Neural Network,” International Review of Electrical Engineering, Vol. 11, No. 3, pp. 314-322, 2016 [17] Dinh Thanh Viet, Nguyen Huu Hieu, Nguyen Le Hoa, Ngo Minh Khoa, ”A Control Strategy for Dynamic Voltage Restorer,” Proceedings of The 11th IEEE International Conference on Power Electronics and Drive Systems (PEDS 2015), 9 - 12, Sydney, Australia, June 2015. [18] Ngo Minh Khoa, Dinh Thanh Viet, Nguyen Huu Hieu, ”Classification of Power Quality Disturbances Using Wavelet Transform and K-Nearest Neighbor Classifier,” Proceedings of The 22nd IEEE International Sympo- sium on Industrial Electronics (ISIE 2013), Taipei, Taiwan, May 2013. [19] Li-Cheng Wu; Chih-Wen Liu; Ching-Shan Chen, ”Modeling and testing of a digital distance relay MAT- LAB/SIMULINK,” Proceedings of The 37th Annual North American Power Symposium, pp. 253-259, 2005. [20] Nur Hazwani Hussin; Muhd Hafizi Idris; Melaty Amirruddin; Mohd Saufi Ahmad; Mohd Alif Ismail; Farrah Salwani Abdullah; Nurhakimah Mohd Mukhta, ”Modeling and simulation of inverse time overcurrent relay using Matlab/Simulink,” Proceedings of 2016 IEEE International Conference on Automatic Control and Intel- ligent Systems (I2CACIS), pp. 40-44, 2016. IJECE Vol. 7, No. 4, August 2017: 1686 – 1695
  • 10. IJECE ISSN: 2088-8708 1695 BIOGRAPHIES OF AUTHORS Ngo Minh Khoa received the MS and PhD degrees in Electrical Engineering from The University of Danang - University of Science and Technology, Danang City, Vietnam, in 2010 and 2017, respectively. He is currently teaching at Quynhon University, Quynhon city, Vietnam. His research interests include protection relay, power quality, and smart grid. Nguyen Huu Hieu received PhD degree in Electrical Engineering from Joseph Fourier, Grenoble, France in 2008. He is currently Dean of Electrical Engineering Department, The University of Danang - University of Science and Technology, Danang city, Vietnam. His research interests include power quality, optimization method, and power system design. Dinh Thanh Viet received PhD degree in Electrical Engineering from Vinnitsya Technical State University, Ukraine in 1997. Currently he is Associate Professor at Department of Electrical Engi- neering, The University of Danang - University of Science and Technology, Danang city, Vietnam. His research interests include power system analysis and control, power quality, transformer diag- nosis, and deregulated market. A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay... (Ngo Minh Khoa)