Three Best Practices for Optimizing your IT Infrastructure  May 14, 2008  42U Confidential ©2008 42U All rights reserved
Agenda ,[object Object],[object Object],[object Object],[object Object],[object Object],42U Confidential ©2008 42U All rights reserved
IT and Data Center – The Problem and the Solution   42U Confidential ©2008 42U All rights reserved “ Today, it takes less than half the energy to produce a dollar of economic output as it did in 1970…Information & communication technologies have played a critical role in reducing energy waste…from sensors & microprocessors, to smart grids & virtualization…” Information and Communication Technologies: The Power of Productivity, ACEEE Report #E081, Feb. 2008
State of the US Industry – EPA Report to Congress 42U Confidential ©2008 42U All rights reserved Trends in Data Center Energy Use: •  Data center sector consumed about 61 billion KWh in 2006 –  Equates to ~1.5% total U.S. electricity consumption and ~$4.5 billion •  Projected to increase to 100 billion kWh in 2011 –  Equates to ~2.5% of total U.S. electricity consumption and ~$7.4 billion
The Power Impact of High-Density Data Centers   42U Confidential ©2008 42U All rights reserved
Where Does Energy Go?   42U Confidential ©2008 42U All rights reserved ,[object Object],[object Object],[object Object],[object Object],Source: The Green Grid
The Cascading Effect of Energy Consumption and Savings  42U Confidential ©2008 42U All rights reserved Source: Energy Logic
#1: Benchmark your data center environment 42U Confidential ©2008 42U All rights reserved
How much energy ARE you using?  42U Confidential ©2008 42U All rights reserved Source: The Green Grid   Revised:  DCiE
Where Are You Measuring the Energy Usage in Your Data Center?  42U Confidential ©2008 42U All rights reserved Source: The Green Grid   M M M M M M M M M M M M M M M M M M M M M M M M M M M M Utility Meter Facility Meters IT Meters M
Detailed Load Analysis  42U Confidential ©2008 42U All rights reserved ,[object Object],[object Object],[object Object],[object Object]
Cooling Airflow Management 42U Confidential ©2008 42U All rights reserved ,[object Object],[object Object],[object Object],[object Object]
Assessing Your Current Environment Should Result In… ,[object Object],[object Object],[object Object],[object Object],[object Object],[object Object],[object Object],[object Object],42U Confidential ©2008 42U All rights reserved
Getting Started…  ,[object Object],[object Object],[object Object],[object Object],[object Object],42U Confidential ©2008 42U All rights reserved
#2: Optimize your cooling approach 42U Confidential ©2008 42U All rights reserved
The Effects of Creating High-Density Data Centers 42U Confidential ©2008 42U All rights reserved * Source IDC 2008
[object Object],Basic Cooling Design 42U Confidential ©2008 42U All rights reserved
What Are the Options? 42U Confidential ©2008 42U All rights reserved Close Coupled Cooling Rear Door Air Cooled Supplemental  In Row Solutions Active Air 0 2 10 15 20 28 35 40 kW Chip + Enclosure Cooling
Differentiating Close Coupled Cooling   42U Confidential ©2008 42U All rights reserved + = Cooling Unit  Server Cabinet  High-Performance Solution top view HEX
Differentiating Close Coupled Cooling 42U Confidential ©2008 42U All rights reserved HEX fan alternative 2 top view
Cooling: Redundancy Considerations 42U Confidential ©2008 42U All rights reserved M1 M2 M3
TCO: Real Estate Cost Analysis 42U Confidential ©2008 42U All rights reserved Available 60KW, 3 rack space   with LCP 30KW 30 – 40 KW common   60KW  10 rack sp. 6KW 6KW 6KW 6KW 6KW 6KW 6KW 6KW 4KW 6KW 6KW L C P L C P 30KW Available 60+KW, 2 rack space   L C P L C P 60 KW
Cooling: Total Cost of Ownership ,[object Object],[object Object],[object Object],[object Object],[object Object],[object Object],[object Object],[object Object],42U Confidential ©2008 42U All rights reserved
#3: Design power infrastructure for maximum efficiency 42U Confidential ©2008 42U All rights reserved
Data Center Power Flow 42U Confidential ©2008 42U All rights reserved
42U Confidential ©2008 42U All rights reserved ,[object Object],[object Object],[object Object],High Efficency UPS
High Voltage PDUs  ,[object Object],[object Object],[object Object],42U Confidential ©2008 42U All rights reserved
Next Steps ,[object Object],[object Object],[object Object],[object Object],42U Confidential ©2008 42U All rights reserved
Q & A  42U Confidential ©2008 42U All rights reserved To Receive a Copy of Today’s Presentation:  rebecca.mccue@42u.com

More Related Content

What's hot

Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationGreg Stover
 
Betty Bezos: bicsi 002 data center standard
Betty Bezos: bicsi 002 data center standardBetty Bezos: bicsi 002 data center standard
Betty Bezos: bicsi 002 data center standardDCC Mission Critical
 
Implementing Hot and Cold Air Containment in Existing Data Centers
Implementing Hot and Cold Air Containment in Existing Data CentersImplementing Hot and Cold Air Containment in Existing Data Centers
Implementing Hot and Cold Air Containment in Existing Data CentersSchneider Electric
 
Hot Aisle & Cold Aisle Containment Solutions & Case Studies
Hot Aisle & Cold Aisle Containment Solutions & Case StudiesHot Aisle & Cold Aisle Containment Solutions & Case Studies
Hot Aisle & Cold Aisle Containment Solutions & Case Studies42U Data Center Solutions
 
The Science Behind Airflow Management Best Practices
The Science Behind Airflow Management Best PracticesThe Science Behind Airflow Management Best Practices
The Science Behind Airflow Management Best PracticesUpsite Technologies
 
Cooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center CoolingCooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center CoolingUpsite Technologies
 
Data center power infrastructure
Data center power infrastructureData center power infrastructure
Data center power infrastructureLivin Jose
 
Data Center Tiers Explained
Data Center Tiers ExplainedData Center Tiers Explained
Data Center Tiers ExplainedData Cave
 
Energy efficiency data center overview
Energy efficiency data center overviewEnergy efficiency data center overview
Energy efficiency data center overviewSchneider Electric
 
Importance of data centers
Importance of data centersImportance of data centers
Importance of data centersTyrone Systems
 
Datwyler data center presentation info tech middle east
Datwyler data center presentation info tech middle eastDatwyler data center presentation info tech middle east
Datwyler data center presentation info tech middle eastAli Shoaee
 
Data Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroomData Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroommarlisaclark
 
European Data Centre Standards
European Data Centre StandardsEuropean Data Centre Standards
European Data Centre StandardsICT FOOTPRINT .eu
 
4 steps to quickly improve pue through airflow management
4 steps to quickly improve pue through airflow management4 steps to quickly improve pue through airflow management
4 steps to quickly improve pue through airflow managementUpsite Technologies
 
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...Upsite Technologies
 
Data center Building & General Specification
Data center Building & General Specification Data center Building & General Specification
Data center Building & General Specification Ali Mirfallah
 

What's hot (20)

Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure Optimization
 
Betty Bezos: bicsi 002 data center standard
Betty Bezos: bicsi 002 data center standardBetty Bezos: bicsi 002 data center standard
Betty Bezos: bicsi 002 data center standard
 
Data centerefficiency
Data centerefficiencyData centerefficiency
Data centerefficiency
 
Modular Data Center Design
Modular Data Center DesignModular Data Center Design
Modular Data Center Design
 
Implementing Hot and Cold Air Containment in Existing Data Centers
Implementing Hot and Cold Air Containment in Existing Data CentersImplementing Hot and Cold Air Containment in Existing Data Centers
Implementing Hot and Cold Air Containment in Existing Data Centers
 
Hot Aisle & Cold Aisle Containment Solutions & Case Studies
Hot Aisle & Cold Aisle Containment Solutions & Case StudiesHot Aisle & Cold Aisle Containment Solutions & Case Studies
Hot Aisle & Cold Aisle Containment Solutions & Case Studies
 
The Science Behind Airflow Management Best Practices
The Science Behind Airflow Management Best PracticesThe Science Behind Airflow Management Best Practices
The Science Behind Airflow Management Best Practices
 
Cooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center CoolingCooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center Cooling
 
Data center power infrastructure
Data center power infrastructureData center power infrastructure
Data center power infrastructure
 
Data Center Tiers Explained
Data Center Tiers ExplainedData Center Tiers Explained
Data Center Tiers Explained
 
Energy efficiency data center overview
Energy efficiency data center overviewEnergy efficiency data center overview
Energy efficiency data center overview
 
Importance of data centers
Importance of data centersImportance of data centers
Importance of data centers
 
Datwyler data center presentation info tech middle east
Datwyler data center presentation info tech middle eastDatwyler data center presentation info tech middle east
Datwyler data center presentation info tech middle east
 
Data Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroomData Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroom
 
Data center
Data centerData center
Data center
 
European Data Centre Standards
European Data Centre StandardsEuropean Data Centre Standards
European Data Centre Standards
 
4 steps to quickly improve pue through airflow management
4 steps to quickly improve pue through airflow management4 steps to quickly improve pue through airflow management
4 steps to quickly improve pue through airflow management
 
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
 
Data center Building & General Specification
Data center Building & General Specification Data center Building & General Specification
Data center Building & General Specification
 
HVAC for Data Centers
HVAC for Data CentersHVAC for Data Centers
HVAC for Data Centers
 

Similar to Data Center Optimization Best Practices

Data Center Energy Efficiency Best Practices
Data Center Energy Efficiency Best PracticesData Center Energy Efficiency Best Practices
Data Center Energy Efficiency Best Practices42U Data Center Solutions
 
PUE Reconsidered - AFCOM (MI), July 2009
PUE Reconsidered - AFCOM (MI), July 2009PUE Reconsidered - AFCOM (MI), July 2009
PUE Reconsidered - AFCOM (MI), July 2009Henry Hsu
 
Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingGraybar
 
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRES
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRESCOMMON PROBLEMS AND CHALLENGES IN DATA CENTRES
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRESKamran Hassan
 
インドネシア JCM事業 FS報告会
インドネシア JCM事業 FS報告会インドネシア JCM事業 FS報告会
インドネシア JCM事業 FS報告会Takeshi Mitsuishi
 
Presentation on green computing .pptx
Presentation on green computing    .pptxPresentation on green computing    .pptx
Presentation on green computing .pptxArchanaMohandas6
 
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)42U Data Center Solutions
 
Green Data Centre for banks
Green Data Centre for banksGreen Data Centre for banks
Green Data Centre for banksPritam Raha Roy
 
Data Center PUE Reconsidered
Data Center PUE Reconsidered Data Center PUE Reconsidered
Data Center PUE Reconsidered Raritan
 
Green data center_rahul ppt
Green data center_rahul pptGreen data center_rahul ppt
Green data center_rahul pptRAHUL KAUSHAL
 

Similar to Data Center Optimization Best Practices (20)

Data Center Energy Efficiency Best Practices
Data Center Energy Efficiency Best PracticesData Center Energy Efficiency Best Practices
Data Center Energy Efficiency Best Practices
 
Data Center Power Strategies
Data Center Power StrategiesData Center Power Strategies
Data Center Power Strategies
 
Data Center Cooling Strategies
Data Center Cooling StrategiesData Center Cooling Strategies
Data Center Cooling Strategies
 
Data Center Server Rack Strategies
Data Center Server Rack StrategiesData Center Server Rack Strategies
Data Center Server Rack Strategies
 
Data Center Measurement
Data Center MeasurementData Center Measurement
Data Center Measurement
 
Data Center Energy Efficiency Leadership
Data Center Energy Efficiency LeadershipData Center Energy Efficiency Leadership
Data Center Energy Efficiency Leadership
 
Green ICT
Green ICTGreen ICT
Green ICT
 
PUE Reconsidered - AFCOM (MI), July 2009
PUE Reconsidered - AFCOM (MI), July 2009PUE Reconsidered - AFCOM (MI), July 2009
PUE Reconsidered - AFCOM (MI), July 2009
 
B7 merlin
B7 merlinB7 merlin
B7 merlin
 
Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for Cooling
 
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRES
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRESCOMMON PROBLEMS AND CHALLENGES IN DATA CENTRES
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRES
 
Indonesia JCM
Indonesia JCM Indonesia JCM
Indonesia JCM
 
インドネシア JCM事業 FS報告会
インドネシア JCM事業 FS報告会インドネシア JCM事業 FS報告会
インドネシア JCM事業 FS報告会
 
PUE Reconsidered
PUE ReconsideredPUE Reconsidered
PUE Reconsidered
 
Presentation on green computing .pptx
Presentation on green computing    .pptxPresentation on green computing    .pptx
Presentation on green computing .pptx
 
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)
 
Green Data Centre for banks
Green Data Centre for banksGreen Data Centre for banks
Green Data Centre for banks
 
Data Center PUE Reconsidered
Data Center PUE Reconsidered Data Center PUE Reconsidered
Data Center PUE Reconsidered
 
Case Study Caso Thor
Case Study Caso ThorCase Study Caso Thor
Case Study Caso Thor
 
Green data center_rahul ppt
Green data center_rahul pptGreen data center_rahul ppt
Green data center_rahul ppt
 

More from 42U Data Center Solutions

What is the Goal of Data Center Racks & Enclosures
What is the Goal of Data Center Racks & EnclosuresWhat is the Goal of Data Center Racks & Enclosures
What is the Goal of Data Center Racks & Enclosures42U Data Center Solutions
 
What is the Goal of High Performance KVM Switch Solutions
What is the Goal of High Performance KVM Switch SolutionsWhat is the Goal of High Performance KVM Switch Solutions
What is the Goal of High Performance KVM Switch Solutions42U Data Center Solutions
 
What is the Goal of Integrated Data Center Solutions
What is the Goal of Integrated Data Center SolutionsWhat is the Goal of Integrated Data Center Solutions
What is the Goal of Integrated Data Center Solutions42U Data Center Solutions
 
What is the Goal of Data Center Airflow Management
What is the Goal of Data Center Airflow ManagementWhat is the Goal of Data Center Airflow Management
What is the Goal of Data Center Airflow Management42U Data Center Solutions
 
UPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with JenUPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with Jen42U Data Center Solutions
 
KVM Solutions for the Next Generation Data Center with Jen
KVM Solutions for the Next Generation Data Center with JenKVM Solutions for the Next Generation Data Center with Jen
KVM Solutions for the Next Generation Data Center with Jen42U Data Center Solutions
 
High Density Cooling Solutions for the Next Generation Data Center with Jen
High Density Cooling Solutions for the Next Generation Data Center with JenHigh Density Cooling Solutions for the Next Generation Data Center with Jen
High Density Cooling Solutions for the Next Generation Data Center with Jen42U Data Center Solutions
 
DCIM & Monitoring Solutions for the Next Generation Data Center with Jen
DCIM & Monitoring Solutions for the Next Generation Data Center with JenDCIM & Monitoring Solutions for the Next Generation Data Center with Jen
DCIM & Monitoring Solutions for the Next Generation Data Center with Jen42U Data Center Solutions
 
Power & Cooling Solutions for the Next Generation Data Center with Jen
Power & Cooling Solutions for the Next Generation Data Center with JenPower & Cooling Solutions for the Next Generation Data Center with Jen
Power & Cooling Solutions for the Next Generation Data Center with Jen42U Data Center Solutions
 
The Data Center in Real Time: Monitoring Tools Overview & Demo
The Data Center in Real Time: Monitoring Tools Overview & DemoThe Data Center in Real Time: Monitoring Tools Overview & Demo
The Data Center in Real Time: Monitoring Tools Overview & Demo42U Data Center Solutions
 

More from 42U Data Center Solutions (20)

What is the Goal of Server Rack Accessories
What is the Goal of Server Rack AccessoriesWhat is the Goal of Server Rack Accessories
What is the Goal of Server Rack Accessories
 
What is the Goal of Data Center Security
What is the Goal of Data Center SecurityWhat is the Goal of Data Center Security
What is the Goal of Data Center Security
 
What is the Goal of Power Distribution
What is the Goal of Power DistributionWhat is the Goal of Power Distribution
What is the Goal of Power Distribution
 
What is the Goal of Data Center Racks & Enclosures
What is the Goal of Data Center Racks & EnclosuresWhat is the Goal of Data Center Racks & Enclosures
What is the Goal of Data Center Racks & Enclosures
 
What is the Goal of High Performance KVM Switch Solutions
What is the Goal of High Performance KVM Switch SolutionsWhat is the Goal of High Performance KVM Switch Solutions
What is the Goal of High Performance KVM Switch Solutions
 
What is the Goal of Integrated Data Center Solutions
What is the Goal of Integrated Data Center SolutionsWhat is the Goal of Integrated Data Center Solutions
What is the Goal of Integrated Data Center Solutions
 
What is the Goal of Digital Signage
What is the Goal of Digital SignageWhat is the Goal of Digital Signage
What is the Goal of Digital Signage
 
What is the Goal of Data Center Containment
What is the Goal of Data Center ContainmentWhat is the Goal of Data Center Containment
What is the Goal of Data Center Containment
 
What is the Goal of Data Center Cooling
What is the Goal of Data Center CoolingWhat is the Goal of Data Center Cooling
What is the Goal of Data Center Cooling
 
What is the Goal of Data Center Airflow Management
What is the Goal of Data Center Airflow ManagementWhat is the Goal of Data Center Airflow Management
What is the Goal of Data Center Airflow Management
 
What is the Goal of Technical Furniture
What is the Goal of Technical FurnitureWhat is the Goal of Technical Furniture
What is the Goal of Technical Furniture
 
UPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with JenUPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with Jen
 
KVM Solutions for the Next Generation Data Center with Jen
KVM Solutions for the Next Generation Data Center with JenKVM Solutions for the Next Generation Data Center with Jen
KVM Solutions for the Next Generation Data Center with Jen
 
High Density Cooling Solutions for the Next Generation Data Center with Jen
High Density Cooling Solutions for the Next Generation Data Center with JenHigh Density Cooling Solutions for the Next Generation Data Center with Jen
High Density Cooling Solutions for the Next Generation Data Center with Jen
 
DCIM & Monitoring Solutions for the Next Generation Data Center with Jen
DCIM & Monitoring Solutions for the Next Generation Data Center with JenDCIM & Monitoring Solutions for the Next Generation Data Center with Jen
DCIM & Monitoring Solutions for the Next Generation Data Center with Jen
 
Power & Cooling Solutions for the Next Generation Data Center with Jen
Power & Cooling Solutions for the Next Generation Data Center with JenPower & Cooling Solutions for the Next Generation Data Center with Jen
Power & Cooling Solutions for the Next Generation Data Center with Jen
 
The Data Center in Real Time: Monitoring Tools Overview & Demo
The Data Center in Real Time: Monitoring Tools Overview & DemoThe Data Center in Real Time: Monitoring Tools Overview & Demo
The Data Center in Real Time: Monitoring Tools Overview & Demo
 
Uncovering the Myths Behind Remote Power
Uncovering the Myths Behind Remote PowerUncovering the Myths Behind Remote Power
Uncovering the Myths Behind Remote Power
 
Eliminating Data Center Hot Spots
Eliminating Data Center Hot SpotsEliminating Data Center Hot Spots
Eliminating Data Center Hot Spots
 
Data Center Cooling Study on Liquid Cooling
Data Center Cooling Study on Liquid CoolingData Center Cooling Study on Liquid Cooling
Data Center Cooling Study on Liquid Cooling
 

Recently uploaded

Sample pptx for embedding into website for demo
Sample pptx for embedding into website for demoSample pptx for embedding into website for demo
Sample pptx for embedding into website for demoHarshalMandlekar2
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek SchlawackFwdays
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii SoldatenkoFwdays
 
The State of Passkeys with FIDO Alliance.pptx
The State of Passkeys with FIDO Alliance.pptxThe State of Passkeys with FIDO Alliance.pptx
The State of Passkeys with FIDO Alliance.pptxLoriGlavin3
 
TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024Lonnie McRorey
 
SALESFORCE EDUCATION CLOUD | FEXLE SERVICES
SALESFORCE EDUCATION CLOUD | FEXLE SERVICESSALESFORCE EDUCATION CLOUD | FEXLE SERVICES
SALESFORCE EDUCATION CLOUD | FEXLE SERVICESmohitsingh558521
 
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxUse of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxLoriGlavin3
 
What is Artificial Intelligence?????????
What is Artificial Intelligence?????????What is Artificial Intelligence?????????
What is Artificial Intelligence?????????blackmambaettijean
 
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptxThe Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptxLoriGlavin3
 
Training state-of-the-art general text embedding
Training state-of-the-art general text embeddingTraining state-of-the-art general text embedding
Training state-of-the-art general text embeddingZilliz
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc
 
DSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningDSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningLars Bell
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenHervé Boutemy
 
A Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersA Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersNicole Novielli
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersRaghuram Pandurangan
 
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxLoriGlavin3
 
SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024Lorenzo Miniero
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxLoriGlavin3
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr BaganFwdays
 

Recently uploaded (20)

Sample pptx for embedding into website for demo
Sample pptx for embedding into website for demoSample pptx for embedding into website for demo
Sample pptx for embedding into website for demo
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko
 
The State of Passkeys with FIDO Alliance.pptx
The State of Passkeys with FIDO Alliance.pptxThe State of Passkeys with FIDO Alliance.pptx
The State of Passkeys with FIDO Alliance.pptx
 
TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024
 
SALESFORCE EDUCATION CLOUD | FEXLE SERVICES
SALESFORCE EDUCATION CLOUD | FEXLE SERVICESSALESFORCE EDUCATION CLOUD | FEXLE SERVICES
SALESFORCE EDUCATION CLOUD | FEXLE SERVICES
 
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxUse of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
 
What is Artificial Intelligence?????????
What is Artificial Intelligence?????????What is Artificial Intelligence?????????
What is Artificial Intelligence?????????
 
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptxThe Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
 
Training state-of-the-art general text embedding
Training state-of-the-art general text embeddingTraining state-of-the-art general text embedding
Training state-of-the-art general text embedding
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
 
DSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningDSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine Tuning
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache Maven
 
A Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersA Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software Developers
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information Developers
 
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
 
SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan
 

Data Center Optimization Best Practices

  • 1. Three Best Practices for Optimizing your IT Infrastructure May 14, 2008 42U Confidential ©2008 42U All rights reserved
  • 2.
  • 3. IT and Data Center – The Problem and the Solution 42U Confidential ©2008 42U All rights reserved “ Today, it takes less than half the energy to produce a dollar of economic output as it did in 1970…Information & communication technologies have played a critical role in reducing energy waste…from sensors & microprocessors, to smart grids & virtualization…” Information and Communication Technologies: The Power of Productivity, ACEEE Report #E081, Feb. 2008
  • 4. State of the US Industry – EPA Report to Congress 42U Confidential ©2008 42U All rights reserved Trends in Data Center Energy Use: • Data center sector consumed about 61 billion KWh in 2006 – Equates to ~1.5% total U.S. electricity consumption and ~$4.5 billion • Projected to increase to 100 billion kWh in 2011 – Equates to ~2.5% of total U.S. electricity consumption and ~$7.4 billion
  • 5. The Power Impact of High-Density Data Centers 42U Confidential ©2008 42U All rights reserved
  • 6.
  • 7. The Cascading Effect of Energy Consumption and Savings 42U Confidential ©2008 42U All rights reserved Source: Energy Logic
  • 8. #1: Benchmark your data center environment 42U Confidential ©2008 42U All rights reserved
  • 9. How much energy ARE you using? 42U Confidential ©2008 42U All rights reserved Source: The Green Grid Revised: DCiE
  • 10. Where Are You Measuring the Energy Usage in Your Data Center? 42U Confidential ©2008 42U All rights reserved Source: The Green Grid M M M M M M M M M M M M M M M M M M M M M M M M M M M M Utility Meter Facility Meters IT Meters M
  • 11.
  • 12.
  • 13.
  • 14.
  • 15. #2: Optimize your cooling approach 42U Confidential ©2008 42U All rights reserved
  • 16. The Effects of Creating High-Density Data Centers 42U Confidential ©2008 42U All rights reserved * Source IDC 2008
  • 17.
  • 18. What Are the Options? 42U Confidential ©2008 42U All rights reserved Close Coupled Cooling Rear Door Air Cooled Supplemental In Row Solutions Active Air 0 2 10 15 20 28 35 40 kW Chip + Enclosure Cooling
  • 19. Differentiating Close Coupled Cooling 42U Confidential ©2008 42U All rights reserved + = Cooling Unit Server Cabinet High-Performance Solution top view HEX
  • 20. Differentiating Close Coupled Cooling 42U Confidential ©2008 42U All rights reserved HEX fan alternative 2 top view
  • 21. Cooling: Redundancy Considerations 42U Confidential ©2008 42U All rights reserved M1 M2 M3
  • 22. TCO: Real Estate Cost Analysis 42U Confidential ©2008 42U All rights reserved Available 60KW, 3 rack space with LCP 30KW 30 – 40 KW common 60KW 10 rack sp. 6KW 6KW 6KW 6KW 6KW 6KW 6KW 6KW 4KW 6KW 6KW L C P L C P 30KW Available 60+KW, 2 rack space L C P L C P 60 KW
  • 23.
  • 24. #3: Design power infrastructure for maximum efficiency 42U Confidential ©2008 42U All rights reserved
  • 25. Data Center Power Flow 42U Confidential ©2008 42U All rights reserved
  • 26.
  • 27.
  • 28.
  • 29. Q & A 42U Confidential ©2008 42U All rights reserved To Receive a Copy of Today’s Presentation: rebecca.mccue@42u.com

Editor's Notes

  1. Ladies and Gentlemen: Thanks for standing by and welcome to today’s session in the 42U web Seminar Series. Today’s presentation is entitled: “ Three Best Practices for Optimizing your IT Infrastructure” During the presentation, all participants will be in a listen only mode. However, we encourage your questions or comments at anytime through the “chat” feature located at the lower left of your screen. These questions will be addressed as time allows. As a reminder, this Web Seminar is being recorded, today, May 14th 2008 and a recording will be sent to all attendees within 48 hours.
  2. Transition: Thank you, Rebecca. I’d like to keep this as a very focused discussion today, so I’m going to outline a very specific agenda. First up, we’re going to talk about how the growth in energy demands are impacting many areas of the data center environment. Next, we’ll address what we have seen as best practices towards optimization, and what we feel are the three primary focus areas. #1, Benchmarking your current environment to get a real sense of where you are starting from in your level of efficiency. #2, the refinement of your cooling approach- what we’ve seen in the way of new technologies that are really helping people get a handle on both the impact of higher density environments and the bottom line. And finally #3- designing your power infrastructure in a way that promotes throughput efficiency, while at the same time reducing overall consumption. Without further ado, I’d like to turn it over to Patrick. Patrick?
  3. Transition: That’s a pretty powerful statement by the ACEEE. Has the US Government has spent any of our tax dollars on studying this issue as well? I’ve noticed they like to get involved in these kinds of things from time to time.
  4. Transition: That information from the EPA study is pretty interesting, too- and shows that this problem is getting some real focus. Patrick, do you have any information on what exactly is driving this power increase these studies identified?
  5. With the cost of energy skyrocketing at the same time as user demand for more performance is increasing, IT managers are facing a power, space and cost crunch. Some data center managers have already reported that the cost of electricity and cooling in the data center are exceeding the cost of the equipment itself. IDC estimates for every $1.00 spent on new data center hardware, an additional $0.50 is spent on power and cooling, more than double the amount of five years ago. According to Gartner, 70 percent of CIO's are reporting that power and/or cooling issues are now their single largest problem in the data center. Gartner estimates that 50 percent of data centers in 2008 will have insufficient power and cooling capacity to meet demand with 48 percent of the data center budget being spent on energy, up from 8 percent a few years ago. It is clear that IT managers need new ways to reduce power as they increase data center performance. Blade servers are a key server consolidation and infrastructure management technology whose deployment can deliver the needed increase in performance while giving data center managers new ways to cut power consumption and costs. It may seem counterintuitive. Blade servers pack more horsepower into smaller chassis and enable a greater concentration of compute power in the data center. With multiple, highly compact blade servers, a single blade server chassis can deliver more compute resources than racks of individual server towers or rows of server racks. But this increased density can translate into higher power consumption per square foot. How does one get around this physical limitation? Besides adopting blade server architectures in the data center, it takes smarter planning, superior power management tools and effective utilization of advanced new technologies such as virtualization.
  6. Transition: Interesting to see that broken out- it certainly seems that even small percentage increases in efficiency can make a significant difference in your energy costs. Can you even provide any other detail on where this energy goes?
  7. Thanks for that, Patrick. From this slide, it’s pretty clear that those tiny wattage savings can add up to a pretty big number. It really seems that any positive changes you can make to the efficiency of the parts that make up a data center are becoming more and more beneficial. I guess the next thing to do would be to go ahead and start looking at the physical ways to begin optimizing the environment. I believe we identified three ways to begin, and the first was to establish a benchmark. How do we go about doing that?
  8. Power Usage Effectiveness and Data center infrastructure efficiency Transition: Hey, that’s some great technical information- can we take a look at a good graphic to help us tie this all together?
  9. Is energy measured at the component level? Is CPU throttling enabled on the servers, and the performance lab measures the range of power consumed under a variety of loads. Is thermal profiling is used to identify hot spots and overcooling? Are energy capacities monitored on a total data center level, all the say down to the circuit-level? Is energy usage continuously monitored to determine peak and low energy demands. Is feedback of live data is available to individual organizations, allowing them to react appropriately Is the energy savings plan is documented? Transition: It certainly seems that measuring power at multiple points in the flow is important and necessary to get a complete picture. Is the technology available today to really capture the information we need, wherever we want to measure it? ((PATRICK CHATS ABOUT THIS TECHNOLOGY))
  10. Transition 2: Interesting. But power seems to be only one part of the equation. What other information do we need to gather to be able to get the greatest accuracy in our benchmark results?
  11. Cables, pipes, etc. Cable openings, perforated tile placement, etc. Cabinet layout, cooling unit orientation, ceiling height, etc. Patrick <paraphrase>: This leads to the manifestation of hot spots? Transition: Fantastic information on improving cooling efficiency- again, it seems that examining and improving the small details really seem to add up to make a big impact. So what should people expect out of benchmarking your data center?
  12. Data Center reliability Optimization of your current cooling infrastructure Enablement of precision cooling to eliminate hot spots Reduction in bypass airflow ASHRAE compliance Complete understanding of your data center’s environment, including cooling requirements and deficiencies Transition: The data we’ve found sure seems to point to the fact that by doing this assessment, a company can get a lot of good, measurable data to help form their efficiency strategy. What have you seen as the best way to get started?
  13. Transition: Okay, that makes sense. Just as a quick note, so far in our best practices discussion we’ve talked about benchmarking to really know where you’re starting from. Okay, let’s say we’ve got that benchmarking task complete. Now what’s next? Would this be a good time to start talking about optimizing the cooling approach?
  14. Here is what industry analysts are saying: Significant increase in kW per rack Energy prices are increasing Space utilization numbers are down because dc are now full from the power and cooling perspective Transition: That’s a really interesting slide, Patrick- power, heat, and utility costs are increasing, and the space you can use in the racks to house the equipment is shrinking! Seems like the wrong direction to be headed everywhere you look. Can you talk about basic cooling designs- kind of where we’ve been, and where we’re going?
  15. Cold air escapes through cable cutouts Escaping cold air reduces static pressure resulting in insufficient cold aisle airflow Result is vertical and zone hotspots in high heat load areas Transition: Patrick- hang on- does this hot & cold aisle scenario best address the needs of today’s high density server environments? Seems like this kind of solution has been out there a while- there’s got to be a better way.
  16. Transition: We’ve actually seen some early success stories using the close coupled cooling solution. Some customers are cooling up to 30KW per rack, with still further expansion capability. Patrick, could you go into any more detail on that?
  17. How would you set this up in an N+1 configuration? Transition: Okay, this type of solution continues to look interesting. But here’s a question for you- in most data centers, redundancy is a key concern. Can you address that in this sort of cooling scenario?
  18. Transition: Hey, I hate to say this, but I do see one potential problem here. In this case, aren’t you using a lot of floor space? Real estate’s not getting any cheaper, you know!
  19. Transition: Okay- got it. You’re actually increasing the cooling capacity in a lot less space- pretty neat. How does this affect your Total Cost of Ownership calculations from a budget perspective?
  20. Patrick to discuss slide: - Best case scenario – 45% real estate savings - Best case scenario – 20% Energy Savings Transition: This makes a lot of sense, Patrick. This kind of solution really allows you to consolidate your equipment into fewer cabinets, as well as showing some serious energy savings. Okay, I’m understanding the cooling part pretty well. Now, what about improving the efficiency of your power? How does that work- you just plug stuff in, and that’s it- right?
  21. Transition: Gadzooks, that slide has a lot of information. Can you help me break this down into some smaller, more easily digestible areas of focus for an efficiency improvement discussion?
  22. Give brief 40 second introduction to the design and capabilities of the system. This will lead into the market drivers and conditions regarding MAC’s, Concept of Modularity, and the market the product was designed for. Transition: (( AFTER PATRICK SAYS FLYWHEEL)) FLYWHEELS? That sounds neat, but is that really practical for a high load data center environment? I’m all about new technology, but I’ve heard that you can only get about 15 seconds of carryover with those things! Is that really helpful? Transition 2: Okay, high efficiency UPS is one area of focus- what do you think of PDU’s- would that be another area of interest?
  23. Transition: It’s amazing that the UPS and PDU’s in the data center can have so much impact in how power is used, and how it affects the equipment it gives life to. Alright, these seem like good best practice focus areas. Let’s say a company wanted to move forward with these things we’ve been discussing- what would you recommend to them?
  24. Thanks for all that great information, Patrick! At this time we’re going to open up our conference for Q&A. As a reminder, if you have a question, please type it into the box in the lower left-hand corner of your screen, and then choose the ‘Chat’ button. We’ve had several questions already, so we’ll just start with those first as the rest come in. Also, if you’d like to receive a copy of today’s presentation, please email the address shown. (((DO THE Q&A))) At this time, it looks like we don’t have any time for more questions. I would like to once again thank Patrick for joining us today. Thanks also to everyone for joining our presentation. Don’t forget, if you’d like more specific information on a particular application for what we’ve been discussing, we’re here to help- do get in touch. Have a great day!